    Manual 2100-511 Page 1 of 27 INST ALLA TION INSTRUCTIONS W ALL MOUNTED P ACKAGE HEA T PUMPS MODELS W18H1 W24H1 W30H1 W36H1 W42H1 W48H1 W60H1 Manual : 2100-51 1 Supersedes: NEW File: V olume III T ab 17 Date: 10-14-08 Bard Manufacturing Company , Inc. Bryan, Ohio 43506 Since 1914...Moving ahead just as planned. © Copyright 2008 ...

  • Bard W42H1 - page 2

    Manual 2100-511 Page 2 of 27 Content s Figures Figure 1 Fresh Air Damper Assembly ................... 5 Figure 2 Unit Dimensions ...................................... 7 Figure 3A Mounting Instructions .............................. 8 Figure 3B Mounting Instructions - W18, W24, W30, W36 .... 9 Figure 3C Mounting Instructions - W42, W48, W60 ..... 1 ...

  • Bard W42H1 - page 3

    Manual 2100-511 Page 3 of 27 GETTING OTHER INFORMA TION AND PUBLICA TIONS These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard. National Ele ctrical Code ...................... ANSI/ ...

  • Bard W42H1 - page 4

    Manual 2100-511 Page 4 of 27 W ALL MOUNT GENERAL INFORMA TION HEAT PUMP WALL MOUNT MODEL NOMENCLATURE W 42 H 1– A 10 X X X X X A NOTE: Vent options X, B and M are without exhaust capability. May require separate field supplied barometric relief in buildi ng. SHIPPING DAMAGE Upon receipt of equipment, the carton should be checked for external sign ...

  • Bard W42H1 - page 5

    Manual 2100-511 Page 5 of 27 DUCT WORK All duct work, supply and return, must be properly sized for the design airflow requirement of the equipment. Air Conditioning Contractors of America (ACCA) is an excellent guide to proper sizing. All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conse ...

  • Bard W42H1 - page 6

    Manual 2100-511 Page 6 of 27 s s e c c A e c i v r e S r o f d e r i u q e R s e c n a r a e l C w o l f r i A r e s n e d n o C e t a u q e d A d n a S L E D O M E D I S T F E L E D I S T H G I R H 6 3 W , H 0 3 W , H 4 2 W , H 8 1 W " 5 1 " 0 2 H 0 6 W , H 8 4 W , H 2 4 W " 0 2 " 0 2 o t d e r i u q e R s e c n a r a e l C m u ...

  • Bard W42H1 - page 7

    Manual 2100-511 Page 7 of 27 *Optional top outlet (factory installed only) for W30H and W36H models only. FIGURE 2 ) l a n i m o N ( s t n e m e r i u q e R n o i t a l l a t s n I d n a l a r u t c e t i h c r A r o f t i n U c i s a B f o s n o i s n e m i D L E D O M H T D I W ) W ( H T P E D ) D ( T H G I E H ) H ( Y L P P U SN R U T E R AB C B ...

  • Bard W42H1 - page 8

    Manual 2100-511 Page 8 of 27 FIGURE 3A W18H1, W24H1 MOUNTING INSTRUCTIONS ...

  • Bard W42H1 - page 9

    Manual 2100-511 Page 9 of 27 FIGURE 3B W30H1, W36H1 MOUNTING INSTRUCTIONS ...

  • Bard W42H1 - page 10

    Manual 2100-511 Page 10 of 27 FIGURE 3C W42H1, W48H1, W60H1 MOUNTING INSTRUCTIONS ...

  • Bard W42H1 - page 11

    Manual 2100-511 Page 11 of 27 FIGURE 4 ELECTRIC HEAT CLEARANCE W30H1, W36H1, W42H1, W48H1, W60H1 W ARNING A minimum of 1/4 inch clearance must be maintained between the supply air duct and combustible materials. This is required for the first 3 feet of ducting. It is important to insure that the 1/4 inch minimum sp acing is maintained at all point ...

  • Bard W42H1 - page 12

    Manual 2100-511 Page 12 of 27 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 6 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 – MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS, FIGURE 2, FOR ACTUAL DIMENSIONS IF REQUIRED IF REQUIRED ...

  • Bard W42H1 - page 13

    Manual 2100-511 Page 13 of 27 FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS ...

  • Bard W42H1 - page 14

    Manual 2100-511 Page 14 of 27 WIRING – MAIN POWER Refer to the unit rating plate for wire sizing information and maximum fuse or “HACR” type circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. Depending on the installed KW ...

  • Bard W42H1 - page 15

    Manual 2100-511 Page 15 of 27 ST ART UP THESE UNITS REQUIRE R-410A REFRIGERANT AND POL YOL ESTER OIL. GENERAL: 1. Use separate service equipment to avoid cross contamination of oil and refrigerants. 2. Use recovery equipment rated for R-410A refrigerant. 3. Use manifold gauges rated for R-410A (800 psi/250 psi low). 4. R-410A is a binary blend of H ...

  • Bard W42H1 - page 16

    Manual 2100-511 Page 16 of 27 ST ART UP (Continued) IMPORTANT INSTALLER NOTE For improved start up performance wash the indoor coil with a dish washing detergent. HIGH & LOW PRESSURE SWITCH All W**H wall mounted air conditioner series models are supplied with a remote reset for the high and low pressure switch. If tripped, this pressure switch ...

  • Bard W42H1 - page 17

    Manual 2100-511 Page 17 of 27 SEQUENCE OF OPERATION COOLING – Circuit R-Y makes at thermostat pulling in compressor contactor, starting the compressor and outdoor motor. The G (indoor motor) circuit is automatically completed on any call for cooling operation or can be energized by manual fan switch on subbase for constant air circulation. HEATIN ...

  • Bard W42H1 - page 18

    Manual 2100-511 Page 18 of 27 FIGURE 8 DEFROST CONTROL BOARD ...

  • Bard W42H1 - page 19

    Manual 2100-511 Page 19 of 27 TROUBLESHOOTING SOLID STATE HEAT PUMP CONTROL TROUBLESHOOTING PROCEDURE 1. NOTE: A thorough understanding of the defrost cycle sequence is essential. Review that section earlier in this manual prior to troubleshooting the control. Turn on AC power supply to unit. 2. Turn thermostat blower switch to “fan on” – the ...

  • Bard W42H1 - page 20

    Manual 2100-511 Page 20 of 27 CHECKING TEMPERATURE SENSOR OUTSIDE UNIT CIRCUIT 1. Disconnect temperature sensor from board and from outdoor coil. 2. Use an ohmmeter and measure the resistance of the sensor. Also use ohmmeter to check for short or open. 3. Check resistance reading to chart of resistance. Use sensor ambient temperature. (Tolerance of ...

  • Bard W42H1 - page 21

    Manual 2100-511 Page 21 of 27 TROUBLESHOOTING FIGURE 9 FAN BLADE SETTING MIS-1724 TABLE 2 FAN BLADE DIMENSION REMOVAL OF FAN SHROUD 1. Disconnect all power to the unit. 2. Remove the screws holding both grilles, one on each side of unit, and remove grilles. 3. Remove screws holding fan shroud to condenser and bottom. Nine (9) screws. 4. Unwire cond ...

  • Bard W42H1 - page 22

    Manual 2100-511 Page 22 of 27 TABLE 4A COOLING PRESSURE TABLE Low side pressure ± 4 PSIG High side pressure ± 10 PSIG Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge being in the system, the charge should be removed, system evacuated and recharged to serial plate charge we ...

  • Bard W42H1 - page 23

    Manual 2100-511 Page 23 of 27 TABLE 5 1 Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. 2 Based on 75C copper wire. All wiring must conform to the National Electrical Code and all local codes. 3 These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductor ...

  • Bard W42H1 - page 24

    Manual 2100-511 Page 24 of 27 TABLE 6 RECOMMENDED AIRFLOW TABLE 7 INDOOR BLOWER PERFORMANCE l e d o M d e t a R * M F C d e t a R * P S E d e d n e m m o c e R e g n a R w o l f r i A d e e p S y r o t c a F n o i t c e n n o C H 8 1 W0 0 6 1 0 3 .5 2 7 - 5 7 5h g i H H 4 2 W0 0 80 2 .0 5 9 - 0 0 7h g i H H 0 3 W0 0 0 10 4 .0 0 3 1 - 0 3 9h g i H H ...

  • Bard W42H1 - page 25

    Manual 2100-511 Page 25 of 27 TABLES 8 MAXIMUM ESP OF OPERATION ELECTRIC HEAT ONLY TABLE 9 ELECTRIC HEAT s l e d o M1 - V 0 4 21 - V 8 0 23 - V 0 4 23 - V 8 0 23 - V 0 6 4 W Ks p m AH U T Bs p m AH U T Bs p m AH U T Bs p m AH U T Bs p m AH U T B 47 . 6 10 5 6 3 14 . 4 10 4 2 0 1 58 . 0 25 6 0 7 11 . 8 10 0 8 2 1 64 . 4 10 0 5 0 25 . 2 10 6 3 5 12 . ...

  • Bard W42H1 - page 26

    Manual 2100-511 Page 26 of 27 W18H1-A W24H1-A W24H1-B W24H1-C W30H1-A W30H1-B W30H1-C W36H1-A W36H1-B W36H1-C W42H1-A W42H1-B W42H1-C W48H1-A W48H1-B W48H1-C W60H1-A W60H1-B W60H1-C TABLE 10 OPTIONAL ACCESSORIES r e b m u N t r a P 4 0 A - A 2 0 H W H EX 8 0 A - A 2 0 H W H EX 4 0 A - H 4 2 W H EX 8 0 A - H 4 2 W H EX 6 0 B - H 4 2 W H EX 5 0 A - 0 ...

  • Bard W42H1 - page 27

    Manual 2100-511 Page 27 of 27 TABLE 11 VENT & CONTROL OPTIONS W18, W24 W30, W36 W42, W48, W60 r e b m u N t r a Pn o i t p i r c s e D 4 1 - C M CT D O XXX 5 1 - C M C) y l n o e s a h P - 1 V 0 3 2 ( t i K t r a t S 1 XXX 1 1 1 K S) y l n o e s a h P - 1 V 0 3 2 ( t i K t r a t S 2 XXX 8 2 - C M CC A L XXX 2 - D A F Bd r a d n a t S - r e p m ...

Produzent Bard Kategorie Heat Pump

Dokumente, die wir vom Produzenten des Geräts Bard W42H1 erhalten, können wir in mehrere Gruppen teilen. Unteranderem in:
- technische Zeichnungen Bard
- Bedienungsanleitungen W42H1
- Produktkarten Bard
- Informationsbroschüren
- oder Energieetiketten Bard W42H1
Jede von ihnen ist wichtig, jedoch finden wir die wichtigsten Informationen für den Nutzer des Geräts in der Bedienungsanleitung Bard W42H1.

Die Dokumentengruppe, die als Bedienungsanleitungen bezeichnet wird, wird ebenfalls in detaillierte Arten geteilt, solche wie: Montageanleitungen Bard W42H1, Wartungsanleitungen, Kurzanleitungen oder Benutzeranleitungen Bard W42H1. Abhängig vom Bedarf, sollten Sie das Dokument finden, das Sie brauchen. In unserem Service können Sie sich die populärste Bedienungsanleitung des Produkts Bard W42H1 ansehen.

Ähnliche Bedienungsanleitungen

Die komplette Bedienungsanleitung des Geräts Bard W42H1, wie sollte sie aussehen?
Die Bedienungsanleitung, auch bezeichnet als Benutzerhandbuch, oder einfach nur „Anleitung”, ist ein technisches Dokument, das dem Benutzer bei der Nutzung von Bard W42H1 hilfreich sein soll. Die Bedienungsanleitungen werden in der Regel von technischen Schriftstellern geschrieben, aber in einer Sprache, die für alle Nutzer von Bard W42H1 verständlich ist.

Eine gänzliche Bedienungsanleitung von Bard sollte einige Grundelemente enthalten. Ein Teil von ihnen ist nicht so wichtig, wie z.B.: die Titelseite oder Autorenseiten. Die restlichen von ihnen jedoch, sollten Informationen liefern, die für den Nutzer von enormer Wichtigkeit sind.

1. Einführung und Hinweise, wie man sich in einer Bedienungsanleitung von Bard W42H1 bewegt - Am Anfang jeder Bedienungsanleitung sollten wir Hinweise bezüglich der Nutzungsart eines bestimmten Ratgebers finden. In ihr sollten sich Informationen über die Lokalisierung des Inhaltsverzeichnisses von Bard W42H1 befinden, FAQ oder über oft auftretende Probleme – also Stellen, die von den Benutzern in jeder Bedienungsanleitung am meisten gesucht werden
2. Inhaltsverzeichnis - Index aller Ratschläge bezüglich Bard W42H1, die wir im aktuellen Dokument finden
3. Ratschläge zur Nutzung der Grundfunktionen des Geräts Bard W42H1 - die uns die ersten Schritte während der Nutzung von Bard W42H1 erleichtern sollten
4. Troubleshooting - geordneter Tätigkeitslauf, der uns bei der Diagnose und als nächstes bei der Lösung wichtiger Probleme mit Bard W42H1 hilft
5. FAQ - häufig gestellte Fragen
6. Kontaktdaten Informationen darüber, wo man Kontakt zum Produzenten / Service von Bard W42H1 im bestimmten Land suchen kann, wenn es nicht gelingt, das Problem selbst zu lösen.

Haben Sie eine Frage bezüglich Bard W42H1?

Nutzen Sie das untere Formular

Wenn Sie mit Hilfe der gefundenen Bedienungsanleitung Ihr Problem mit Bard W42H1 nicht gelöst haben, stellen Sie eine Frage, indem Sie das untere Formular nutzen. Wenn einer der Nutzer ein ähnliches Problem mit Bard W42H1 hatte, ist es möglich, dass er mit Ihnen die Lösung teilen möchte.

Text vom Bild übertragen

Kommentare (0)