    CONTENTS GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 RENEWAL PARTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 APPROVALS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 INSTALLATION . . . . . . . . ...

  • Johnson Controls 341426-BIM-A-0108 - page 2

    341426-BIM-A-0108 2 Johnson Controls Unitary Products T A BLE OF CONTENTS GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 RENEWAL PARTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 APPROVALS . . . . . . . . . . . . . . . ...

  • Johnson Controls 341426-BIM-A-0108 - page 3

    341426-BIM-A-0108 Johnson Controls Unitary Produ cts 3 GENERAL Model DY A units are cooling/hea ting air conditioners designed for outdoor installation. Only gas pipi ng, electric power and duct connection s are required at th e point of installation. The gas-fired heate rs have spark to pilot ignition . The tubul ar heat exchangers are aluminized ...

  • Johnson Controls 341426-BIM-A-0108 - page 4

    341426-BIM-A-0108 4 Johnson Controls Unitary Products INST ALLA TION LIMIT A TIONS These units must be installed in accordance with the follow- ing national and loca l safety codes. 1. National Electrical Code ANSI/NFPS No. 70 or Canadi an Electrical Code Part 1, C22.1 (latest editions). 2. National Fuel Gas Code Z223.1 or CAN/CGA B149 .1 or .2 Ins ...

  • Johnson Controls 341426-BIM-A-0108 - page 5

    341426-BIM-A-0108 Johnson Controls Unitary Produ cts 5 CLEARANCES All units require certain clearances for proper operation an d service. Refer to T able 10 for the clearances required for combustion, construction, serv icin g and proper unit opera- tion. DUCT WORK These units are adaptable to downflow use as well as rear supply and return air duct ...

  • Johnson Controls 341426-BIM-A-0108 - page 6

    341426-BIM-A-0108 6 Johnson Controls Unitary Products THERMOST A T The room thermostat should be locate d on an inside wall approximately 56" above the floor where it will not be subject to drafts, sun exposure or heat from electrical fixtures or appliances. Follow man ufacturer's instructions enclosed with the thermostat for general inst ...

  • Johnson Controls 341426-BIM-A-0108 - page 7

    341426-BIM-A-0108 Johnson Controls Unitary Produ cts 7 T ABLE 3: NA TURAL GAS APPLICA TION DA T A A V AILABLE ON MODELS INPUT CAPACITY (MBH) 1 OUTPUT CAPACITY (MBH) GAS RATE 2 FT. 3 /HR . NUMBER OF BURNERS T EMP. RISE °F AT FULL INPUT 3 MIN. MAX. 3 & 3-1/2 TON 45 36 42 2 25 55 3 & 3-1/2 TON 70 56 65 3 25 55 4 & 5 TON 80 64 74 3 25 55 3 ...

  • Johnson Controls 341426-BIM-A-0108 - page 8

    341426-BIM-A-0108 8 Johnson Controls Unitary Products GAS PIPING Proper sizing of gas piping d epends on the cubic feet per hour of gas flow required, spec ific gravity of the gas and the length of run. National Fuel Gas Code Z223.1 o r CAN/CGA B149.1 or .2 should be followed in all cases unless super- seded by local codes or gas company requiremen ...

  • Johnson Controls 341426-BIM-A-0108 - page 9

    341426-BIM-A-0108 Johnson Controls Unitary Produ cts 9 i 4. All piping should be cleaned of dirt and scale by ham- mering on the outside of the pipe and blowi ng out the loose dirt and scale. Before initial start-up, be sure that all of the gas l ines external to the u nit have been purged of air . 5. The gas supply should be a separate line and in ...

  • Johnson Controls 341426-BIM-A-0108 - page 10

    341426-BIM-A-0108 10 Johnson Controls Unitary Products T ABLE 7: PHYSICAL DA T A MODEL DY A 036 042 048 060 EV APOR A TOR BLOWER CENTRIFUGAL BLOWER (Dia. x W . in.) 1 1 x 10 1 1 x 10 12 x 1 1 12 x 1 1 F AN MOTOR HP (3 S p eed) 3/4 3/4 1 1 EV APOR A TOR COIL ROWS DEEP 2 3 3 3 FINS PER INCH 15 13 13 13 F ACE AREA (Sq. Ft.) 3.5 3.5 4.5 4.5 CONDENSER F ...

  • Johnson Controls 341426-BIM-A-0108 - page 11

    341426-BIM-A-0108 Johnson Controls Unitary Produ cts 11 FIGURE 7 - UNIT DIMEN SIONS - FRONT All dimensions are in inches. They are subject to change with- out notice. Certified dimensions will be provided upon request. T ABLE 9: UNIT DIMENSIONS FRONT UNIT S IZE DIMENSION “A” “B” 036 and 042 33 -1/2 18-1/4 048 and 060 41 -1/2 23-1/8 T ABLE 1 ...

  • Johnson Controls 341426-BIM-A-0108 - page 12

    341426-BIM-A-0108 12 Johnson Controls Unitary Products FIGURE 8 - UNIT DIMENSIONS - FRONT & BOTTOM 2 6 - 3 / 4 6 4 - 5 / 8 8 - 7 / 8 1 1 - 7 / 8 1 9 - 1 / 4 H I G H V O L T A G E C O N N . 1 - 3 / 3 2 " D I A . K N O C K O U T F R O N T C O N D E N S A T E D R A I N 3 / 4 " ' N P T I G A S S U P P L Y 1 - 5 / 8 " D I A . K N ...

  • Johnson Controls 341426-BIM-A-0108 - page 13

    341426-BIM-A-0108 Johnson Controls Unitary Produ cts 13 SEQUENCE OF OPERA TION The unit is controlled b y a c onventional heating/cooling ther- mostat common to this class of equipment. HEA TING The control board begins a call for he at when W1 is ener- gized (connected to R). The control ignores W2 until pilot ignition has been established. The co ...

  • Johnson Controls 341426-BIM-A-0108 - page 14

    341426-BIM-A-0108 14 Johnson Controls Unitary Products The control recognize s a call for 2nd stage heat when W2 is energized (connected to "R"). The control e nergizes the hig h gas output and induced draft motor on high speed. If the call for 2nd stage heat go es away a nd the 1st stage call remains, the control de energize s the high g ...

  • Johnson Controls 341426-BIM-A-0108 - page 15

    341426-BIM-A-0108 Johnson Controls Unitary Produ cts 15 2. Pressure Switch (PS) - If the draft moto r should fail, the pressure switch prevents the ignition controls and gas valves from being energi zed. 3. Flame Sensor - The flame sensor and controls are located per Proper Fla me Adjustment, Figure 12 . If an ignition control fails to detect a sig ...

  • Johnson Controls 341426-BIM-A-0108 - page 16

    341426-BIM-A-0108 16 Johnson Controls Unitary Products 2. T urn off all electric power to the appliance if service is to be performed. 3. Remove the control access panel. 4. T urn the gas valve switch to the OFF position. DO NOT FORCE. 5. Replace the control access panel. POST -ST ART CHE CK LIST (GAS) After the entire control circuit has been ener ...

  • Johnson Controls 341426-BIM-A-0108 - page 17

    341426-BIM-A-0108 Johnson Controls Unitary Produ cts 17 T o adjust the pilot flame: 1. Remove the pilot adjustment cover screw . 2. Adjust the pilot adjustment screw to achieve the p roper pilot flame. 3. Replace the pilot adjustment cover screw after the pilot flame is set. T o remove the pilot assembly: 1. Disconnect the wiring from the control b ...

  • Johnson Controls 341426-BIM-A-0108 - page 18

    341426-BIM-A-0108 18 Johnson Controls Unitary Products CHECKING SUPPLY AIR CFM To check the supply ai r CFM after the initial balancin g has been complete d: 1. Remove the two ¼ inch dot plugs in the duct panel. 2. Insert at least 8 inches of ¼ inch tubing into each of these holes for sufficient penetration into the a irflow on both sides of the ...

  • Johnson Controls 341426-BIM-A-0108 - page 19

    341426-BIM-A-0108 Johnson Controls Unitary Produ cts 19 FIGURE 13 - DY A C OIL DELT A P VS. AIRFLOW 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 400 600 800 1000 1200 1400 1600 1800 2000 2200 Ai r f l o w ( CF M ) ID Coil Delta P DYA042 DYA Coi l Del ta P vs Air fl ow DY A0 48 - 060 DYA036 DYA036 DYA042 DYA048-060 T ABLE 13: SUPERHEA T CHARGING T ABLE FOR ...

  • Johnson Controls 341426-BIM-A-0108 - page 20

    341426-BIM-A-0108 20 Johnson Controls Unitary Products T ABLE 14: SUPERHEA T CHARGING T ABLE FOR DY A042 OUTDOOR TEMP . °F SUPERHEA T A T COMPRESSOR SUCTION (F), AIRFLOW = 400 CFM INDOOR WB TEMP . (°F) 55 57 59 61 63 65 67 69 71 73 75 65 18.0 19.7 21.4 23.0 24.7 26.3 28.0 29.1 30.2 31.3 32.4 70 13.4 15.3 17.3 19.3 21.2 23.2 25.2 26.6 28.1 29.6 31 ...

  • Johnson Controls 341426-BIM-A-0108 - page 21

    341426-BIM-A-0108 Johnson Controls Unitary Produ cts 21 FIGURE 14 - TYPICAL WIRING DIAGRAM DY A 036, 042, 048, 060 (208/2 3 0- 3-60 POWER SUPP L Y) ...

  • Johnson Controls 341426-BIM-A-0108 - page 22

    341426-BIM-A-0108 22 Johnson Controls Unitary Products FIGURE 15 - TYPICAL WIRING DIAGRAM DY A 03 6, 042, 048, 060 (460-3-60 POWER SUPPL Y) ...

  • Johnson Controls 341426-BIM-A-0108 - page 23

    341426-BIM-A-0108 Johnson Controls Unitary Produ cts 23 TYPICAL WIRING DIAGRAM NOTES (SEE FIGURES 14 AND 15) 1. All field wiring to be accomplished following ci ty , local and/or national codes in effect at time of installation of this unit. 2. Caution: Label all wires prior to disconnection when ser- vicing controls. Wiring errors can cause improp ...

  • Johnson Controls 341426-BIM-A-0108 - page 24

    Subject to change without notice. Pr inted in U.S.A. 341426-BIM-A-0108 Copyright © 2008 b y Johnson Controls, Inc. All rig hts reserved. Supersedes: 284590-BIM-B-0807 Johnson Controls Unita ry Products 5005 York Drive Norman, OK 73069 FIGURE 17 - TYPICAL WIRING DIAGRAM LEGEND LEGEND ALS AUXILARY LIMIT SWITCH ASCT ANTI-SHORT CYCLE TIMER (OPTIONAL) ...

Produzent Johnson Controls Kategorie Air Conditioner

Dokumente, die wir vom Produzenten des Geräts Johnson Controls 341426-BIM-A-0108 erhalten, können wir in mehrere Gruppen teilen. Unteranderem in:
- technische Zeichnungen Johnson Controls
- Bedienungsanleitungen 341426-BIM-A-0108
- Produktkarten Johnson Controls
- Informationsbroschüren
- oder Energieetiketten Johnson Controls 341426-BIM-A-0108
Jede von ihnen ist wichtig, jedoch finden wir die wichtigsten Informationen für den Nutzer des Geräts in der Bedienungsanleitung Johnson Controls 341426-BIM-A-0108.

Die Dokumentengruppe, die als Bedienungsanleitungen bezeichnet wird, wird ebenfalls in detaillierte Arten geteilt, solche wie: Montageanleitungen Johnson Controls 341426-BIM-A-0108, Wartungsanleitungen, Kurzanleitungen oder Benutzeranleitungen Johnson Controls 341426-BIM-A-0108. Abhängig vom Bedarf, sollten Sie das Dokument finden, das Sie brauchen. In unserem Service können Sie sich die populärste Bedienungsanleitung des Produkts Johnson Controls 341426-BIM-A-0108 ansehen.

Ähnliche Bedienungsanleitungen

Die komplette Bedienungsanleitung des Geräts Johnson Controls 341426-BIM-A-0108, wie sollte sie aussehen?
Die Bedienungsanleitung, auch bezeichnet als Benutzerhandbuch, oder einfach nur „Anleitung”, ist ein technisches Dokument, das dem Benutzer bei der Nutzung von Johnson Controls 341426-BIM-A-0108 hilfreich sein soll. Die Bedienungsanleitungen werden in der Regel von technischen Schriftstellern geschrieben, aber in einer Sprache, die für alle Nutzer von Johnson Controls 341426-BIM-A-0108 verständlich ist.

Eine gänzliche Bedienungsanleitung von Johnson Controls sollte einige Grundelemente enthalten. Ein Teil von ihnen ist nicht so wichtig, wie z.B.: die Titelseite oder Autorenseiten. Die restlichen von ihnen jedoch, sollten Informationen liefern, die für den Nutzer von enormer Wichtigkeit sind.

1. Einführung und Hinweise, wie man sich in einer Bedienungsanleitung von Johnson Controls 341426-BIM-A-0108 bewegt - Am Anfang jeder Bedienungsanleitung sollten wir Hinweise bezüglich der Nutzungsart eines bestimmten Ratgebers finden. In ihr sollten sich Informationen über die Lokalisierung des Inhaltsverzeichnisses von Johnson Controls 341426-BIM-A-0108 befinden, FAQ oder über oft auftretende Probleme – also Stellen, die von den Benutzern in jeder Bedienungsanleitung am meisten gesucht werden
2. Inhaltsverzeichnis - Index aller Ratschläge bezüglich Johnson Controls 341426-BIM-A-0108, die wir im aktuellen Dokument finden
3. Ratschläge zur Nutzung der Grundfunktionen des Geräts Johnson Controls 341426-BIM-A-0108 - die uns die ersten Schritte während der Nutzung von Johnson Controls 341426-BIM-A-0108 erleichtern sollten
4. Troubleshooting - geordneter Tätigkeitslauf, der uns bei der Diagnose und als nächstes bei der Lösung wichtiger Probleme mit Johnson Controls 341426-BIM-A-0108 hilft
5. FAQ - häufig gestellte Fragen
6. Kontaktdaten Informationen darüber, wo man Kontakt zum Produzenten / Service von Johnson Controls 341426-BIM-A-0108 im bestimmten Land suchen kann, wenn es nicht gelingt, das Problem selbst zu lösen.

Haben Sie eine Frage bezüglich Johnson Controls 341426-BIM-A-0108?

Nutzen Sie das untere Formular

Wenn Sie mit Hilfe der gefundenen Bedienungsanleitung Ihr Problem mit Johnson Controls 341426-BIM-A-0108 nicht gelöst haben, stellen Sie eine Frage, indem Sie das untere Formular nutzen. Wenn einer der Nutzer ein ähnliches Problem mit Johnson Controls 341426-BIM-A-0108 hatte, ist es möglich, dass er mit Ihnen die Lösung teilen möchte.

Text vom Bild übertragen

Kommentare (0)