Bedienungsanleitung York YCJF24

30 Seiten 0.6 mb
Download

Zur Seite of 30

Summary
  • York YCJF24 - page 1

    TECHNICAL GUIDE SPLIT -SYSTEM AIR CONDITIONERS 14.5 SEER – R-410A MODELS: YCJF24 THRU 60 (2 THRU 5 NOMINA L TONS, 1 PHASE) Due to continuou s pro duc t impro vement, speci f ic a tio ns are subject to chan ge without notice. Vi si t us on the web at ww w .york.com Additional rating informa tion can be found at www .ahridirector y .org ISO 9001 Ce ...

  • York YCJF24 - page 2

    413437-YTG-C-0908 2 Johnson Controls Unitary Products All dimensions are in inches. The y are subject to change with- out notice. Certified dimensions will be provi ded upon request. Physical and Electr ical Dat a MODEL YCJF24S41S1 YCJF30S41S1 YCJF36S41S1 YCJF4 2S41S1 YCJF48S41S1 YCJF60S41S1 Unit Supply V oltage 208-230V , 1 φ, 60Hz Normal V oltag ...

  • York YCJF24 - page 3

    413437-YTG -C-0908 Johnson Controls Unitary Pro ducts 3 Additional R-410A Charge / Orifice Size for V arious Matched Sys tems Out door Unit YCJF24S41S1 YCJF30S41S1 YCJF36S41S1 Y CJF42S41S1 Y CJF48S41S1 YCJF60S41S1 Required Ori fice or TXV 1 1 TVM(902/4F1) 1 TVM(903/4G1) 1 TVM(903/4G1) 1 TVM( 903/4G1) 1 TVM(905/4J1) 1 TVM(906/4K1) Factory Charge, lb ...

  • York YCJF24 - page 4

    413437-YTG-C-0908 4 Johnson Controls Unitary Products PROCEDURES: 1. Unit factory charge listed on the unit nameplate includes re frigerant for the condenser, the smallest evaporator and 15 feet of intercon- necting line tubing. 2. V erify the TXV or orifice and additional charge required for s pecific evaporator coil in t he system using the above ...

  • York YCJF24 - page 5

    413437-YTG -C-0908 Johnson Controls Unitary Pro ducts 5 COOLING CAP ACITY - With Air Handler Coils UNIT MODEL AIR HANDLER COIL MODEL 1 COOLING MODEL W RA TED CFM NET MBH SEER EER TOT AL SE NS . 14.5 SEER AC WITH MA YCJF24S41S1 MA08B 17 FC/MC24B 800 24.8 17.3 14.35 12.15 MA08B 17 FC/MC30B 800 24.8 17.3 14.35 12.15 MA08B 17 FC/MC35B 800 25.0 17.6 14. ...

  • York YCJF24 - page 6

    413437-YTG-C-0908 6 Johnson Controls Unitary Products — = Not applicable. 14.5 SEER AC WITH MV - V ARIABLE SPEED (Contimued) YCJF42S41S1 MV16C 21 FC/MC43C 1400 41.0 30 .8 15.00 12.75 MV16C 21 FC/MC48C 1400 41.5 31 .2 15.50 13.00 MV20D 24 FC/MC48D 1400 42.0 31 .4 15.50 13.00 MV20D 24 FC/MC60D 1400 41.5 31 .4 15.50 13.00 MV20D 24 FC/MC62D 1400 42.0 ...

  • York YCJF24 - page 7

    413437-YTG -C-0908 Johnson Controls Unitary Pro ducts 7 COOLING CAP ACITY - Upflow , Downflow & Horizont al Furnaces and Coils UNIT MODEL FURNACE** COIL MODEL COOLING CFM RANGE (Min.-max.) W RA TE D CFM NET MBH SEER 1 EER TOT AL SE NS . YCJF24S41S1 600 - 1000 14,17 FC/MC/PC24 800 24.8 17.3 14.00 12.00 600 - 1000 14,17 FC/MC/PC30 800 24.8 17.3 1 ...

  • York YCJF24 - page 8

    413437-YTG-C-0908 8 Johnson Controls Unitary Products COOLING CAP ACITY - YCJF24S41S1 With V ariable Speed Furnaces V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING RA TED CFM Net MBH SEER EER TOT A L SENS. 14.5 SEER AC WITH V ARIABLE SPEED FURNACES 2 PV8*A12 FC/MC/PC24A 14 750 24.8 17.5 15 .75 12.25 PV9*A12 FC/MC/PC24A 14 800 25.2 17.6 15 .50 ...

  • York YCJF24 - page 9

    413437-YTG -C-0908 Johnson Controls Unitary Pro ducts 9 Y*9C*B12 FC/MC/PC43B 17 800 24.0 16.8 16.00 13.50 Y*(8,L)C*A12 HC30 14 775 24.0 16.8 15.75 13.25 Y*(8,L)C*B12 HC36 17 760 24.0 16.7 15.75 13.50 Y*9C*B12 HC36 17 815 24.0 17.0 15.75 13.50 Y*(8,L)C*A12 HD36 14 805 24.0 16.4 16.00 13.50 Y*(8,L)C*B12 HD36 17 760 24.0 16.2 15.75 13.25 Y*(8,L)C*C16 ...

  • York YCJF24 - page 10

    413437-YTG-C-0908 10 Johnson Controls Unitary Products COOLING CAP ACITY - YCJF30S41S1 With V ariable Speed Furnaces V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING RA TED CFM Net MBH SEER EER TOT A L SENS. 14.5 SEER AC WITH V ARIABLE SPEED FURNACES 2 PV8*A12 FC/MC/PC30A 14 1000 29.2 21.0 15.00 12.75 PV8*B16 FC/MC/PC30B 17 1050 29.6 21.6 15.25 ...

  • York YCJF24 - page 11

    413437-YTG -C-0908 Johnson Controls Unitary Pro ducts 11 PV8*A12 UC30A 14 1000 29.4 21.2 15.25 13.00 PV8*B16 UC30B 17 1050 29.8 21.8 15.50 13.25 PV9*A12 UC30A 14 1000 29.4 21.2 15.00 12.75 Y*(8,L)C*A12 FC/MC/PC30A 14 1090 29.4 21.6 14.50 12.25 Y*(8,L)C*B12 FC/MC/PC30B 17 955 29.0 20.8 15.25 13.00 Y*9C*B12 FC/MC/PC30B 17 1050 29.6 21.8 15.00 13.00 Y ...

  • York YCJF24 - page 12

    413437-YTG-C-0908 12 Johnson Controls Unitary Products G*9V*C16 FC/MC/PC35C 21 1005 29.6 22.0 15.75 13 .25 G*9V*C20 FC/MC/PC35C 21 985 29.6 22 .0 15.75 13.25 G*9V*A12 FC/MC/PC36A 14 1000 29.4 21.2 15.25 12.75 G*9V*B12 FC/MC/PC36B 17 985 29.4 21.4 15.50 13.00 G*9V*C16 FC/MC/PC36C 21 1005 29.6 21.6 15.75 13 .25 G*9V*C20 FC/MC/PC36C 21 1045 29.6 21.6 ...

  • York YCJF24 - page 13

    413437-YTG -C-0908 Johnson Controls Unitary Pro ducts 13 PV8*C16 FC/MC/PC48C 21 1200 35.4 26.0 16.25 13.25 PV8*C20 FC/MC/PC48C 21 1200 35.4 26.0 16.25 13.25 P(C,V)9*C16 FC/MC/PC48C 21 1200 35.2 25.8 16.00 13.25 P(C,V)9*C20 FC/MC/PC48C 21 1200 35.2 25.8 15.75 13.00 P(C,V)9*D20 FC/MC/PC48D 24 1200 35.2 25.8 16.00 13.25 PV8*B16 HC36B 17 1200 34.2 25.0 ...

  • York YCJF24 - page 14

    413437-YTG-C-0908 14 Johnson Controls Unitary Products Y*(8,L)C*C16 FC/PC60C 21 1 195 35.4 26.0 16.25 13 .55 Y*(8,L)C*C20 FC/PC60C 21 1215 35.4 26.0 16.20 13 .50 Y*9C*C16 FC/PC60C 21 1235 35.0 25.8 15.50 13.00 Y*9C*C20 FC/PC60C 21 1330 35.6 27.2 15.65 13.15 Y*(8,L)C*C16 HC42 21 1205 35.0 25 .8 15 .75 13.00 Y*(8,L)C*C20 HC42 21 1 190 35.0 25.8 16.00 ...

  • York YCJF24 - page 15

    413437-YTG -C-0908 Johnson Controls Unitary Pro ducts 15 COOLING CAP ACITY - YCJF42S41S1 Wi th V ariable Speed Furnaces V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING RA TED CFM Net MBH SEER EER TOT AL SE NS . 14.5 SEER AC WITH V ARIAB LE SPEED FURNACES 2 PV8*B16 FC/MC/PC43B 17 1400 41.0 30.6 14.75 12.50 PV8*C20 FC/MC/PC43C 21 1400 41.0 30.8 ...

  • York YCJF24 - page 16

    413437-YTG-C-0908 16 Johnson Controls Unitary Products Y*(8,L)C*B12 HD48 17 1350 41.0 29.8 14.75 12.50 Y*(8,L)C*C16 HD48 21 1435 41.5 30 .8 15 .25 13.00 Y*(8,L)C*C20 HD48 21 1410 42.0 31 .0 15 .25 13.00 Y*9C*B12 HD48 17 1 150 40.0 28.2 14.75 12.50 Y*9C*C16 HD48 21 1395 41 .5 30.8 15.00 12 .75 Y*9C*C20 HD48 21 1430 41 .5 30.8 14.75 12 .50 Y*9C*D20 H ...

  • York YCJF24 - page 17

    413437-YTG -C-0908 Johnson Controls Unitary Pro ducts 17 COOLING CAP ACITY - YCJF48S41S1 Wi th V ariable Speed Furnaces V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING RA TED CFM Net MBH SEER EER TOT AL SE NS . 14.5 SEER AC WITH V ARIAB LE SPEED FURNACES 2 PV8*C16 FC/MC/PC48C 21 1500 46.5 31.8 14.50 12.25 PV8*C20 FC/MC/PC48C 21 1600 47.0 32.8 ...

  • York YCJF24 - page 18

    413437-YTG-C-0908 18 Johnson Controls Unitary Products G*9V*C20 FC/PC60C 21 1655 47 .0 33.0 14.75 12.50 G*9V*D20 FC/MC/PC60D 24 1615 47.0 33.0 14.75 12 .50 G*9V*C20 FC/MC62D 21 1655 47.0 33.2 14.75 12 .50 G*9V*D20 FC/MC62D 24 1630 47.0 33.4 15.00 12 .75 G*9V*D20 HC60 24 1615 45.0 32.4 14.50 12.00 G*9V*C16 HD48 21 1590 46.5 32.4 14.50 12.25 G*9V*C20 ...

  • York YCJF24 - page 19

    413437-YTG -C-0908 Johnson Controls Unitary Pro ducts 19 ACCESSORIES Refer to Price Manua l for specific model numbers. OFF CYCLE TIMER DELA Y - Provides a 5-minute off cycle to prevent rapid recycling of the compressor . ROOM THERMOST A TS - A wide selection of compatible ther- mosets are available to provid e optimum performance and fea- tures fo ...

  • York YCJF24 - page 20

    413437-YTG-C-0908 20 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. For dry bulb temperatures dif ferent th an those listed (betwe en 73- 87 F), sensible cap acity increases by 1060 BTUH per 1000 CFM per degree above the listed tempe ra- ture and decreases by 1060 BTUH per 1000 CF M per d ...

  • York YCJF24 - page 21

    413437-YTG -C-0908 Johnson Controls Unitary Pro ducts 21 V ariable Speed Furnace Coil T .C. S.C. KW PV8*A12 FC/MC/PC24A 1.02 1.05 0.94 PV9*A12 FC/MC/PC24A 1.03 1.06 0.96 P(C,V)9*B12 FC/MC/PC24B 1.03 1.06 0.95 PV8*A12 FC/MC/PC30A 1.02 1.05 0.94 PV9*A12 FC/MC/PC30A 1.03 1.06 0.96 P(C,V)9*B12 FC/MC/PC30B 1.03 1.06 0.95 PV8*A12 FC/MC/PC32A 1.03 1.06 0. ...

  • York YCJF24 - page 22

    413437-YTG-C-0908 22 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those liste d (bet ween 73-87 F), sensible capacit y incr eases by 1060 BTUH per 1000 CFM per degree abo ve the listed temperature and decr eases by 1060 BTUH per 1000 CFM p ...

  • York YCJF24 - page 23

    413437-YTG -C-0908 Johnson Controls Unitary Pro ducts 23 P(C,V)9*C20 FC/MC/PC36C 1.00 0.99 0.93 PV8*A12 FC/MC/PC37A 1.01 1.01 0.96 PV9*A12 FC/MC/PC37A 1.01 1.01 0.97 PV8*B16 FC/MC/PC43B 1.03 1.05 0.93 PV8*C16 FC/MC/PC43C 1.02 1.02 0.92 PV8*C20 FC/MC/PC43C 1.04 1.08 0.93 P(C,V)9*B12 FC/MC/PC43B 1.02 1.02 0.93 P(C,V)9*C16 FC/MC/PC43C 1.02 1.02 0.93 P ...

  • York YCJF24 - page 24

    413437-YTG-C-0908 24 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those liste d (bet ween 73-87 F), sensible capacit y incr eases by 1060 BTUH per 1000 CFM per degree abo ve the listed temperature and decr eases by 1060 BTUH per 1000 CFM p ...

  • York YCJF24 - page 25

    413437-YTG -C-0908 Johnson Controls Unitary Pro ducts 25 V ariable Speed Furnace Coil T .C. S.C. KW PV8*B16 FC/MC/PC35B 0.99 0.99 0.95 PV8*C16 FC/MC/PC35C 0.99 0.99 0.94 PV8*C20 FC/MC/PC35C 1.00 1.00 0.94 P(C,V)9*B12 FC/MC/PC35B 0.99 0.99 0.97 P(C,V)9*C16 FC/MC/PC35C 0.99 0.99 0.94 P(C,V)9*C20 FC/MC/PC35C 0.99 0.99 0.95 PV8*A12 FC/MC/PC36A 0.98 0.9 ...

  • York YCJF24 - page 26

    413437-YTG-C-0908 26 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those liste d (bet ween 73-87 F), sensible capacit y incr eases by 1060 BTUH per 1000 CFM per degree abo ve the listed temperature and decr eases by 1060 BTUH per 1000 CFM p ...

  • York YCJF24 - page 27

    413437-YTG -C-0908 Johnson Controls Unitary Pro ducts 27 V ariable Speed Furnace Coil T .C. S.C. KW PV8*B16 FC/MC/PC43B 1.00 0.99 0.97 PV8*C20 FC/MC/PC43C 1.00 1.00 0.96 P(C,V)9*C16 FC/MC/PC43C 1.00 0.99 0.98 P(C,V)9*C20 FC/MC/PC43C 1.00 1.00 0.96 PV8*C16 FC/MC/PC48C 1.01 1.01 0.97 PV8*C20 FC/MC/PC48C 1.01 1.01 0.96 P(C,V)9*C16 FC/MC/PC48C 1.01 1.0 ...

  • York YCJF24 - page 28

    413437-YTG-C-0908 28 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those liste d (bet ween 73-87 F), sensible capacit y incr eases by 1060 BTUH per 1000 CFM per degree abo ve the listed temperature and decr eases by 1060 BTUH per 1000 CFM p ...

  • York YCJF24 - page 29

    413437-YTG -C-0908 Johnson Controls Unitary Pro ducts 29 V ariable Speed Furnace Coil T .C. S.C. KW PV8*C16 FC/MC/PC48C 0.99 0.97 0.98 PV8*C20 FC/MC/PC48C 1.00 1.00 0.99 P(C,V)9*C16 FC/MC/PC48C 1.00 1.00 1.00 P(C,V)9*C20 FC/MC/PC48C 1.00 1.01 0.98 PV8*C16 FC/MC/PC60C 0.99 0.98 0.98 PV8*C20 FC/MC/PC60C 1.01 1.01 0.98 P(C,V)9*C16 FC/MC/PC60C 1.00 1.0 ...

  • York YCJF24 - page 30

    Subject to change without notice. Printe d in U.S.A. 413437-YTG-C-0908 Copyright © 2008 by Johnson Controls, Inc. All ri ghts reserved. Supersedes: 413437-YTG-B-0608 Johnson Controls Unitary Product s 5005 Y ork Drive Norman, OK 73069 Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif fere ...

Produzent York Kategorie Air Conditioner

Dokumente, die wir vom Produzenten des Geräts York YCJF24 erhalten, können wir in mehrere Gruppen teilen. Unteranderem in:
- technische Zeichnungen York
- Bedienungsanleitungen YCJF24
- Produktkarten York
- Informationsbroschüren
- oder Energieetiketten York YCJF24
Jede von ihnen ist wichtig, jedoch finden wir die wichtigsten Informationen für den Nutzer des Geräts in der Bedienungsanleitung York YCJF24.

Die Dokumentengruppe, die als Bedienungsanleitungen bezeichnet wird, wird ebenfalls in detaillierte Arten geteilt, solche wie: Montageanleitungen York YCJF24, Wartungsanleitungen, Kurzanleitungen oder Benutzeranleitungen York YCJF24. Abhängig vom Bedarf, sollten Sie das Dokument finden, das Sie brauchen. In unserem Service können Sie sich die populärste Bedienungsanleitung des Produkts York YCJF24 ansehen.

Ähnliche Bedienungsanleitungen

Die komplette Bedienungsanleitung des Geräts York YCJF24, wie sollte sie aussehen?
Die Bedienungsanleitung, auch bezeichnet als Benutzerhandbuch, oder einfach nur „Anleitung”, ist ein technisches Dokument, das dem Benutzer bei der Nutzung von York YCJF24 hilfreich sein soll. Die Bedienungsanleitungen werden in der Regel von technischen Schriftstellern geschrieben, aber in einer Sprache, die für alle Nutzer von York YCJF24 verständlich ist.

Eine gänzliche Bedienungsanleitung von York sollte einige Grundelemente enthalten. Ein Teil von ihnen ist nicht so wichtig, wie z.B.: die Titelseite oder Autorenseiten. Die restlichen von ihnen jedoch, sollten Informationen liefern, die für den Nutzer von enormer Wichtigkeit sind.

1. Einführung und Hinweise, wie man sich in einer Bedienungsanleitung von York YCJF24 bewegt - Am Anfang jeder Bedienungsanleitung sollten wir Hinweise bezüglich der Nutzungsart eines bestimmten Ratgebers finden. In ihr sollten sich Informationen über die Lokalisierung des Inhaltsverzeichnisses von York YCJF24 befinden, FAQ oder über oft auftretende Probleme – also Stellen, die von den Benutzern in jeder Bedienungsanleitung am meisten gesucht werden
2. Inhaltsverzeichnis - Index aller Ratschläge bezüglich York YCJF24, die wir im aktuellen Dokument finden
3. Ratschläge zur Nutzung der Grundfunktionen des Geräts York YCJF24 - die uns die ersten Schritte während der Nutzung von York YCJF24 erleichtern sollten
4. Troubleshooting - geordneter Tätigkeitslauf, der uns bei der Diagnose und als nächstes bei der Lösung wichtiger Probleme mit York YCJF24 hilft
5. FAQ - häufig gestellte Fragen
6. Kontaktdaten Informationen darüber, wo man Kontakt zum Produzenten / Service von York YCJF24 im bestimmten Land suchen kann, wenn es nicht gelingt, das Problem selbst zu lösen.