Bedienungsanleitung Quadra-Fire QV36-A

42 Seiten 1.91 mb
Download

Zur Seite of 42

Summary
  • Quadra-Fire QV36-A - page 1

    1 - Do not store or use gasoline or other flam- mable vapors and liquids in the vicinity of this or any other appliance. - What to do if you smell gas • Do not try to light any appliance. • Do not touch any electrical switch. • Do not use any phone in your building. • Immediately call your gas supplier from a neighbor's phone. Follow t ...

  • Quadra-Fire QV36-A - page 2

    2 These units MUST use one of the vent systems described in the Installing the Fireplace section of the Installers Guide . NO OTHER vent systems or components MA Y BE USED . This gas fireplace and vent assembly MUST be vented directly to the outside and MUST NEVER be attached to a chimney serving a separate solid fuel burning appliance. Each gas ap ...

  • Quadra-Fire QV36-A - page 3

    3 TABLE OF CONTENTS Safety and Warning Information .......................................................... 2 Service Parts Lists .................................................................................. 4 Section 1: Approvals and Codes ........................................................... 8 Appliance Certification ................ ...

  • Quadra-Fire QV36-A - page 4

    4 QV32-A (NG , LP) Exploded Parts Diagram / Vue éclatée des pièces * Part number list on following page. * La liste des numéros de pièce se trouve à la page suivante. Service Parts 4 3 5 2 16 7 1 6 8 Log Set Assembly 15 12 11 10 14 9 13 u ...

  • Quadra-Fire QV36-A - page 5

    5 ITEM / PIÈCE STANDING PILOT IGNITION / D’ALLUMAGE PAR VEILLEUSE PA RT NUMBER / N° DE PIÈCE On/Off Rock Switc h / Int erupter a bascule marche/arret 060-5 11 F lex Ball Valve Assembly / Fléchir l'Assemblée de Soupape de Balle 302-320A Pie zo Ignitor / Allumage Piézo 291-513 Burner Tu be / Tu be de br ûl eur 567-301A Burner Orifice NG ...

  • Quadra-Fire QV36-A - page 6

    6 9 11 12 13 14 15 QV36-A (NG , LP) Exploded Parts Diagram / (GN, PL) Vue éclatée des pièces * Part number list on following page. * La liste des numéros de pièce se trouve à la page suivante. Service Parts 7 1 2 3 4 5 16 6 8 Log Set Assembly 10 u ...

  • Quadra-Fire QV36-A - page 7

    7 ITEM / PIÈCE STANDING PILOT IGNITION / D’ALLUMAGE PAR VEILLEUSE PA RT NUMBER / N° DE PIÈCE On/Off Rocker Switc h / Int errupteur a bascule marche/arret 060-5 11 F lex Ba ll Valve Assemb ly / F léchir l'Assemblée de So upape de Ba lle 302-320A Pie zo Ignitor / Allumage Piézo 291-513 Burner Tu be / Tu be de br ûl eur 567-301A Burner O ...

  • Quadra-Fire QV36-A - page 8

    8 Approvals and Codes NOTE: THESE MODELS ARE UL LISTED TO UL307B, THE S TA NDARD FOR GAS-BURNING HE A TING APPLI- ANCES FOR MANU FACTURED HOMES AND RECRE- A TIONAL VEHICLES. Installation Codes The fireplace installation must conform to local codes. Before installing the fireplace, consult the local building code agency to ensure that you are in com ...

  • Quadra-Fire QV36-A - page 9

    9 Getting Started Introducing the Village Collection Gas Fireplaces The Village Collection direct vent gas fireplaces are designed to operate with all combustion air siphoned from outside of the building and all exhaust gases expelled to the outside. The information contained in this Installers Guide , unless noted otherwise, applies to all models ...

  • Quadra-Fire QV36-A - page 10

    10 Figure 1. Diagram of the QV36-A TOP STANDOFFS GAS CONTROLS ELECTRICAL ACCESS GAS ACCESS RATING PL ATE/ LABELS 5 3/8 (138mm) GAS LINE ACCESS 2 1/4 (56mm) 37 3/4 (960mm) 36 (913mm) 41 (1040mm) 22 (560mm) 34 1/2 (876mm) 3 1/2 (90mm) 8 (203mm) 26 7/8 (683mm) 8 5/8 (219mm) VENT COLLARS DIAMETER ELECTRICAL ACCESS 6 5/8 (168mm) VENT COLLARS DIAMETER 8 ...

  • Quadra-Fire QV36-A - page 11

    11 Figure 2. Diagram of the Q V -32-A 8 (203mm) 23 3/8 (594mm) 8 5/8 (219mm) VENT COLLARS DIAMETER ELECTRICAL ACCESS 3 1/2 (90mm) 36 (913mm) 31 (788mm) 18 3/8 (468mm) 31 (786mm) 32 1/2 (826mm) 5 3/8 (138mm) GAS LINE ACCESS 2 1/4 (56mm) 8 3/4 (222mm) 16 1/4 (413mm) 6 5/8 (168mm) VENT COLLARS DIAMETER 12 7/8 (327mm) 25 3/4 (653mm) TOP STANDOFFS GAS C ...

  • Quadra-Fire QV36-A - page 12

    12 Installing the Fireplace Step 1. Locating the Fireplace The following diagram shows space and clearance require- ments for locating a fireplace within a room. Minimum Clearances from the Fireplace to Combustible Materials Inches mm Glass Front ...................................... 36 ........ 914 Floor .......................................... ...

  • Quadra-Fire QV36-A - page 13

    13 Figure 5. Framing Dimensions Framing should be constructed of 2 X 4 lumber or heavie r. WARNING: To ensure proper clearances the front framing header must be installed on its narrow edge and to the front of the frame. The framing headers may rest on the fireplace stand-offs. VENT FRAMING HOLE E D Model A B C D E * QV36-A 42” 38 1/4” 16 1/4? ...

  • Quadra-Fire QV36-A - page 14

    14 NOTE: PIPES OVERLAP 1-3/8 INCHES (34.93mm) AT EACH JOIN T. Figure 6. D-Series Direct Vent Component Specifications (5-inch inner pipe / 8 5/8-inch outer pipe) DV-36D 5 3/4” (146mm) 8 3/4” (222mm) 11 3/4” (298mm) DV-48D 7 3/8” (187mm) 6 5/32” (156mm) 11 5/8” (295mm) 8 5/8” (220mm) 8 1/2” (216mm) 6 7/16” (164mm) 11 1/16” (281mm ...

  • Quadra-Fire QV36-A - page 15

    15 NOTE: PIPES OVERLAP 1-3/8 INCHES (34.93mm) AT EACH JOIN T. Figure 7 . SL D- Series Direct Vent Component Specifications (4-inch inner pipe / 6 5/8-inch outer pipe) 120” (3048mm) 24” (610mm) 36” (914mm) 60” (1524mm) 9 1/4 6 5/8 6 1/2 6 3/8 6 1/2 9 5/8 9 5/8 6 5/8 6 3/8 8 3/4 SL-09D 12-17 SL-12/17D (SL12-17D) SL-24D SL-36D SL-48D 47 3/4 35 ...

  • Quadra-Fire QV36-A - page 16

    16 ! Figure 8. Vent System Components and Termination Kits Step 3. Installing the Vent System A. Vent System Approvals These models have vent starting collars on both the top and the back of the unit. Depending upon the installation, decide which ONE set of starting collars will be used to attach the vent system. The starting collar sealing cap mus ...

  • Quadra-Fire QV36-A - page 17

    17 STRAIGHT UP VERTICAL VENTING V (FT .) 45' MAX. (13.7 m) Figure 10. Straight up Vertical Venting Use SL D-Series components onl y. NOTE: For vertical venting over 20 feet a restrictor plate is recommended for improved flame appearance. STRAIGHT OUT HORIZON TAL VENTING H Max. Run 36" (914 mm) Use D-Series components onl y. Figure 11. Str ...

  • Quadra-Fire QV36-A - page 18

    18 V H 1' MIN. (305mm) 2' MAX. (610mm) 2' MIN. (610mm) 4' MAX. (1.22m) 3' MIN. (914mm) 6' MAX. (1.86m) 4' MIN. (1.22m) 8' MAX. (2.4m) V+H=40' MAX. (12.4m) H = 8' MAX. (2.4m) Figure 12. Venting with One 90° Elbow Use D-Series components onl y. V H Figure 13. Venting with One 90° Elbow V (MIN.) 90 o ...

  • Quadra-Fire QV36-A - page 19

    19 V H H + H 1 1' MIN. (305 mm) 2' MAX. (610 mm) 4' MAX. (1.22m) 2' MIN. (610 mm) 4' MAX. (1.22 m) 8' MAX. (2.4m) 3' MIN. (914 mm) 6' MAX. (1.86 m) 12' MAX. (3.6m) 4' MIN. (1.22 m) 8' MAX. (2.48 m) 16' MAX. (4.8m) V+H+H 1 = 40' MAX. (12.4 m) H = 8' MAX. (2.48 m) H+H 1 = 16' ...

  • Quadra-Fire QV36-A - page 20

    20 Figure 15. Venting with Two 90° Elbows Use SL D-Series components onl y. VENTING WITH TWO (2) 90 o ELBOWS NA TURAL GAS H + H 1 MAX. = 16 FT (4.8m) V + H + H 1 MAX. = 40 FT (12.2m) H + H 1 (MAX.) 2 FT (610mm) 3 FT (914mm) 4 FT (1.22m) 6 FT (1.86m) 8 FT (2.48m) 16 FT (4.8m) VENTING WITH TWO (2) 90 o ELBOWS PROP ANE H + H 1 MAX. = 16 FT (4.8m) V + ...

  • Quadra-Fire QV36-A - page 21

    21 Figure 16. Venting with Two 90° Elbows Use SL D-Series components onl y. VENTING WITH TWO (2) 90 o ELBOWS NA TURAL GAS H MAX. = 16 FT (4.8m) V + V 1 + H MAX. = 40 FT (12.2m) H (MAX.) 2 FT (610mm) 3 FT (914mm) 4 FT (1.22m) 6 FT (1.86m) 8 FT (2.48m) 16 FT (4.8m) VENTING WITH TWO (2) 90 o ELBOWS PROP ANE H MAX. = 16 FT (4.8m) V + V 1 + H MAX. = 40 ...

  • Quadra-Fire QV36-A - page 22

    22 Figure 17. Venting with Three 90° elbows 1' MIN. (305 mm) 2' MAX. (610mm) 4' MAX. (1.22m) 2' MIN. (610 mm) 4' MAX. (1.22m) 8' MAX. (2.48m) 3' MIN. (914 mm) 6' MAX. (1.86m) 12' MAX. (3.72m) 4' MIN. (1.22 m) 8' MAX. (2.48m) 16' MAX. (4.8m) V 1 +V+H+H 1 = 40' MAX. (12.4m) H = 8' ...

  • Quadra-Fire QV36-A - page 23

    23 Figure 18. Venting with three 90° elbows Use SL D-Series components onl y. VENTING WITH THREE (3) 90 o ELBOWS NA TURAL GAS VENTING WITH THREE (3) 90 o ELBOWS PROP ANE V + H + V 1 + H 1 MAX. = 40 FT (12.2m) V + H + V 1 + H 1 MAX. = 40 FT (12.2m) V (MIN.) H (MAX.) H + H 1 (MAX.) 90 o Elbow on T op 2 FT (610mm) 4 FT (1.22m) 1 FT (305mm) 3 FT (914m ...

  • Quadra-Fire QV36-A - page 24

    24 Use SL D-Series components onl y. VENTING WITH THREE (3) 90 o ELBOWS NA TURAL GAS H + H 1 MAX. = 16 FT (4.8m) V + V 1 + H + H 1 MAX. = 40 FT (12.2m) MODEL QV36-A H + H 1 (MAX.) 2 FT (610mm) 3 FT (914mm) 4 FT (1.22m) 6 FT (1.86m) 8 FT (2.48m) 16 FT (4.8m) VENTING WITH THREE (3) 90 o ELBOWS PROP ANE H + H 1 MAX. = 16 FT (4.8m) V + V 1 + H + H 1 MA ...

  • Quadra-Fire QV36-A - page 25

    25 Figure 20. Venting with Four 90° elbows VENTING WITH FOUR (4) 90° ELBOWS NA TURAL AND PROP ANE GAS V (MIN.) H (MAX.) 2' (609mm) 5' (1.52m) V 1 (MIN.) H 1 (MAX.) V 2 (MIN.) 5' (1.52m) 5' (1.52m) 4.5' (1.37m) V + V 1 + V 2 + H + H 1 MAX. = 40' (12.2m) V H V 2 V 1 H 1 Note: There MUST be a 25% reduction in total H wh ...

  • Quadra-Fire QV36-A - page 26

    26 ! STARTING COLLAR STOVE SEALANT BEAD 1 INCH (25.4mm) FIRST VENT COMPONENT If the installation is for a termination cap attached directly to the fireplace, skip to the sections, Install Firestops and Vent Termination . 3/8” (9.5mm) Venting Out the Rear Vent (See Figure 21) Remove the installed rear seal cap from the rear starting collars by cut ...

  • Quadra-Fire QV36-A - page 27

    27 For Vertical Runs - The vent system must be supported every eight (8) feet (2.4m) above the fireplace flue outlet by wall brackets. To install support brackets for vertical runs: • Attach wall brackets to the vent pipe and secure the wall bracket to the framing members with nails or screws. • Position the firestops on both sides of the hole ...

  • Quadra-Fire QV36-A - page 28

    28 For Vertical Runs - One ceiling firestop is REQUIRED at the hole in each ceiling through which the vent passes. To install firestops for vertical runs that pass through ceilings: • Position a plumb bob directly over the center of the verti- cal vent component. • Mark the ceiling to establish the centerpoint of the vent. • Drill a hole or d ...

  • Quadra-Fire QV36-A - page 29

    29 ! C. Vent Termination For Horizontal Terminations - To attach and secure the termination to the last section of horizontal vent: • Rotate and interlock the ends as described at the begin- ning of the Installing Vent Components section. • The termination kit should pass through the wall firestops from the exterior of the building. • Adjust ...

  • Quadra-Fire QV36-A - page 30

    30 ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ ______________________________________________________________________ V = VENT TERMINAL X = AIR SUPP LY INLET = AREA WHERE TERMINAL I ...

  • Quadra-Fire QV36-A - page 31

    31 For Vertical Terminations - To locate the vent and install the vent sections: • Locate and mark the vent centerpoint on the underside of the roof, and drive a nail through the centerpoint. • Make the outline of the roof hole around the centerpoint nail. • The size of the roof hole framing dimensions depend on the pitch of the roof. There M ...

  • Quadra-Fire QV36-A - page 32

    32 Step 4. Positioning, Leveling, and Securing the Fireplace • Place the fireplace into position. • Level the fireplace from side to side and from front to back. • Shim the fireplace with non-combustible material, such as sheet metal, as necessar y. • Secure the fireplace to the framing using nails or screws through the nailing tabs. ! ! Th ...

  • Quadra-Fire QV36-A - page 33

    33 Figure 35. Gas Supply Line • Insert insulation from the outside of the fireplace and pack the insulation tightly to totally seal between the pipe and the outer casing. • At the gas line access hole the gap between the supply piping and gas access hole can be plugged with non- combustible insulation to prevent cold air infiltration. Step 6. T ...

  • Quadra-Fire QV36-A - page 34

    34 Step 8. Wiring the Fireplace NOTE: Electrical wiring must be installed by a licensed electrician. CAUTION: DISCONNECT REMOTE CONTROLS IF AB- SENT FOR EXTENDED TIME PERIODS. THIS WILL PRE- VENT ACCIDENT AL FIREPLACE OPERA TION. For Standing Pilot Ignition Wiring Appliance Requirements • This appliance DOES NOT require 110-120 VAC to operate. WA ...

  • Quadra-Fire QV36-A - page 35

    35 Step 9. Finishing Figure 38 shows the minimum vertical and corresponding maximum horizontal dimensions of fireplace mantels or other combustible projections above the top front edge of the fireplace. See Figures 3 and 4 for other fireplace clearances. Only non-combustible materials may be used to cover the black fireplace front. W ARNING: WHEN F ...

  • Quadra-Fire QV36-A - page 36

    36 Installing the Trim Combustible materials may be brought up to the specified clearances on the side and top front edges of the fireplace, but MUST NEVER overlap onto the front face. The joints between the finished wall and the fireplace top and sides can only be sealed with a 300° F . (149° C) minimum sealant. WA RNING: WHEN FINISHING THE FIRE ...

  • Quadra-Fire QV36-A - page 37

    37 Step 11. Before Lighting the Fireplace Before lighting the fireplace, be sure to do the following: Remove all paperwork from underneath the fireplace. Review safety warnings and cautions • Read the Safety and Warning Information section at the beginning of this Installers Guide . Double-check for gas leaks • Before lighting the fireplace, do ...

  • Quadra-Fire QV36-A - page 38

    38 Step 12. Lighting the Appliance STANDING PILOT IGNITION A. This appliance (standing pilot version) has a pilot that must be lighted by hand. When lighting the pilot, follow these instructions exactl y. B. BEFORE LIGHTING smell all around the appli- ance area for gas. Be sure to smell next to the floor because some gas is heavier than air and wil ...

  • Quadra-Fire QV36-A - page 39

    39 Maintaining and Servicing Your Fireplace Fireplace Maintenance Although the frequency of your fireplace servicing and main- tenance will depend on use and the type of installation, you should have a qualified service technician perform an appli- ance check-up at the beginning of each heating season. See the table below for specific guidelines re ...

  • Quadra-Fire QV36-A - page 40

    40 Troubleshooting W ith proper installation, operation, and maintenance your gas fireplace will provide years of trouble-free service. If you do experience a problem, this troubleshooting guide will assist a qualified service person in the diagnosis of a problem and the corrective action to be taken. This troubleshooting guide can only be used by ...

  • Quadra-Fire QV36-A - page 41

    41 Symptom Possible Cause Corrective Action 3. (Co nt inued) f. H ig h l imit switc h is defecti ve or has reached its ma x im um temperature. A llow the un i t to cool. I f the burner remains lit after the fireplace warms up, the sw i tch is good. 4. Frequent pilot outage problem. a. Pilot flame ma y be too high or too lo w , or blowi ng (high), c ...

  • Quadra-Fire QV36-A - page 42

    42 The Aladdin Hearth Products limited Lifetime Warranty guarantees that the following components will work as de- signed for the lifetime of the stove or Aladdin Hearth Products will repair or replace them. These items include, but are not limited to, steel and cast iron components, all gas burners, gas logs, combustion chambers, heat exchanger sy ...

Produzent Quadra-Fire Kategorie Indoor Fireplace

Dokumente, die wir vom Produzenten des Geräts Quadra-Fire QV36-A erhalten, können wir in mehrere Gruppen teilen. Unteranderem in:
- technische Zeichnungen Quadra-Fire
- Bedienungsanleitungen QV36-A
- Produktkarten Quadra-Fire
- Informationsbroschüren
- oder Energieetiketten Quadra-Fire QV36-A
Jede von ihnen ist wichtig, jedoch finden wir die wichtigsten Informationen für den Nutzer des Geräts in der Bedienungsanleitung Quadra-Fire QV36-A.

Die Dokumentengruppe, die als Bedienungsanleitungen bezeichnet wird, wird ebenfalls in detaillierte Arten geteilt, solche wie: Montageanleitungen Quadra-Fire QV36-A, Wartungsanleitungen, Kurzanleitungen oder Benutzeranleitungen Quadra-Fire QV36-A. Abhängig vom Bedarf, sollten Sie das Dokument finden, das Sie brauchen. In unserem Service können Sie sich die populärste Bedienungsanleitung des Produkts Quadra-Fire QV36-A ansehen.

Ähnliche Bedienungsanleitungen

Die komplette Bedienungsanleitung des Geräts Quadra-Fire QV36-A, wie sollte sie aussehen?
Die Bedienungsanleitung, auch bezeichnet als Benutzerhandbuch, oder einfach nur „Anleitung”, ist ein technisches Dokument, das dem Benutzer bei der Nutzung von Quadra-Fire QV36-A hilfreich sein soll. Die Bedienungsanleitungen werden in der Regel von technischen Schriftstellern geschrieben, aber in einer Sprache, die für alle Nutzer von Quadra-Fire QV36-A verständlich ist.

Eine gänzliche Bedienungsanleitung von Quadra-Fire sollte einige Grundelemente enthalten. Ein Teil von ihnen ist nicht so wichtig, wie z.B.: die Titelseite oder Autorenseiten. Die restlichen von ihnen jedoch, sollten Informationen liefern, die für den Nutzer von enormer Wichtigkeit sind.

1. Einführung und Hinweise, wie man sich in einer Bedienungsanleitung von Quadra-Fire QV36-A bewegt - Am Anfang jeder Bedienungsanleitung sollten wir Hinweise bezüglich der Nutzungsart eines bestimmten Ratgebers finden. In ihr sollten sich Informationen über die Lokalisierung des Inhaltsverzeichnisses von Quadra-Fire QV36-A befinden, FAQ oder über oft auftretende Probleme – also Stellen, die von den Benutzern in jeder Bedienungsanleitung am meisten gesucht werden
2. Inhaltsverzeichnis - Index aller Ratschläge bezüglich Quadra-Fire QV36-A, die wir im aktuellen Dokument finden
3. Ratschläge zur Nutzung der Grundfunktionen des Geräts Quadra-Fire QV36-A - die uns die ersten Schritte während der Nutzung von Quadra-Fire QV36-A erleichtern sollten
4. Troubleshooting - geordneter Tätigkeitslauf, der uns bei der Diagnose und als nächstes bei der Lösung wichtiger Probleme mit Quadra-Fire QV36-A hilft
5. FAQ - häufig gestellte Fragen
6. Kontaktdaten Informationen darüber, wo man Kontakt zum Produzenten / Service von Quadra-Fire QV36-A im bestimmten Land suchen kann, wenn es nicht gelingt, das Problem selbst zu lösen.

Haben Sie eine Frage bezüglich Quadra-Fire QV36-A?

Nutzen Sie das untere Formular

Wenn Sie mit Hilfe der gefundenen Bedienungsanleitung Ihr Problem mit Quadra-Fire QV36-A nicht gelöst haben, stellen Sie eine Frage, indem Sie das untere Formular nutzen. Wenn einer der Nutzer ein ähnliches Problem mit Quadra-Fire QV36-A hatte, ist es möglich, dass er mit Ihnen die Lösung teilen möchte.

Text vom Bild übertragen

Kommentare (0)