    P OWER P ROTECTION U SER M A NUAL English 700-2200 VA 120 V PowerSure™ Interactive R DISCONTINUED PR ODUCT ...

  • Liebert 700-2200 VA - page 2

    2 IMPORTANT SAFETY INSTRUCTIONS WARNING: Do not attempt to service this product yourself except to replace the battery. Opening or removing the cover may expose you to dange rous voltages, even when the AC cord is disconne cted from the electrical outlet. Refer all servicing to qualified service pe rsonnel. 1. SAVE THESE INSTRUCTIONS. THIS MANUAL C ...

  • Liebert 700-2200 VA - page 3

    3 it, or the safety ground will be re moved. Operate UPS only from a properly grounded 120 VAC outlet (2 wire plu s ground). 9. The UPS is equipped with a grounded NEMA 5-15P or L5-30P input power plug (depending upon model ). Do not defeat the safety purpose of this plug. If unable to fully insert the plug into the wall outlet, contact a qualified ...

  • Liebert 700-2200 VA - page 4

    4 INTRODUCTION & SYS TEM DESCRIPTION Congratulations on your choice of the Liebert PowerSure™ Interactive Uninterruptible Po wer System (UPS). It provides conditioned power to microcomputers and other sensitive electronic e quipment. Upon generation, AC power is clean and stable. However, during transmission it may be subject to voltage sags, ...

  • Liebert 700-2200 VA - page 5

    5 MAJOR COMPONENTS TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS) AND EMI/RFI FILTERS These UPS components provide sur ge prot ection and filter Electromagnetic Interference (EMI) and Radio Frequenc y Interference (RFI ). They minimize any surges or interference present in the utility li ne and keep the sensitive equipment protected. AUTOMATIC VOLTA GE ...

  • Liebert 700-2200 VA - page 6

    6 MINI-TOWER INSTALLATION 1. Unpack the UPS carefully noting the packi ng method. Retain the bo x and packing material for possible future shipme nt. CAUTION: The UPS is heavy (see spec ificatio ns). Take proper precautio ns when lifting or moving it. 2. Visually inspect the UPS for freig ht dam age. Report damage to the carrier and your dealer. 3. ...

  • Liebert 700-2200 VA - page 7

    7 RACKMOUNT INSTALLATION 1. Unpack the UPS carefully noting th e packing method. Retain box and p acking material for possible future shipment. CAUTION: The UPS is heavy (see s pecifications). Take the proper precautions when lifting or moving the UPS. 2. Visually inspect the UPS for freight damage. Report any damage to the carrier and your dealer. ...

  • Liebert 700-2200 VA - page 8

    8 CONTROLS AND INDICATORS On/Off Button The On/Off button controls output power to connected load(s). CAUTION: Pressing the On/Off button w hen AC utility is not present will cause the UPS to begin operating from battery. This should not be performe d unless the UPS input is connected to a properly grounded receptacle. Load/Battery Lev el Indicator ...

  • Liebert 700-2200 VA - page 9

    9 POWERSURE™ INTERACTIVE MINI-TOWER 4 26 2 64 2 1 1 3 5 4 3 5 1 6 1 5 3 700 VA 1000 / 1400 VA 2200 VA Faul t I ndi cat or Lo ad/B att er y Lev el I ndi cat ors Alar m Silen ce/ Ba tte ry T es t B utt on On /O ff B utt on Util ity H igh /Low Indi cator Util ity/Ba ttery S t atu s Ind ic ato r 1- Output Receptacles 2- DB-9 Interface Port 3- AC Inle ...

  • Liebert 700-2200 VA - page 10

    10 POWERSURE™ INTERA CTI VE RACKMOUNT 2200 Model 1 3 4 62 3 6 1 5 5 5 700-1400 Models *700 Model has detachable cord 1- Output Receptacles 2- DB-9 Interface Port 3- AC Inlet 4- Intellislot™ Communications Port 5- Circuit Protector or Fuse 6- Site Wiring Fault Indicator On / Off Alarm Silence Load / Battery Utility High / Low Utility R On / Off ...

  • Liebert 700-2200 VA - page 11

    11 OPERATION NORMAL MODE OPERA TION During normal operation, utility po wer prov ides energ y to the UPS. The filters and the power conditioning circuit process this power to provide comp uter grade power to connected loads. The UPS maintains the batteries in a fully charged state. The front panel displa ys the percentage of load on the UPS output. ...

  • Liebert 700-2200 VA - page 12

    12 BATTERY MODE OPERATION Battery mode occurs in event of extreme input conditions or comp lete utility failure. The battery system along with the bi-directional conv erter generates power for the connected load. During battery mode an alarm so unds every 10 seconds. This will change to 2 beeps every 5 secon ds when battery runs low (approximatel y ...

  • Liebert 700-2200 VA - page 13

    13 COMMUNICATIONS INTERFACE PORT The PowerSure™ Interactive UPS contains a standar d DB-9F recepticle loc ated on the rear of the UPS unit. Several si gnals are provid ed on this port and are assigned as follows: PIN ASSIGNMENT DESCRIPTION 1 Low Battery (open collector) 2 UPS TxD (typical RS-232 levels) 3 UPS RxD (typical RS-232 levels) 4 Remote ...

  • Liebert 700-2200 VA - page 14

    14 UPS INTELLIGENT COMMUNICATIONS The PowerSure™ Interactive UPS has the capabi lity to communicate intelli gently with stand alone computers, network workstations, net work servers, or UNIX hosts via the DB-9 female connector locat ed on the rear of the UPS. By purchasi ng the optional Liebert SiteNet® 2 software package (sold sep arately), int ...

  • Liebert 700-2200 VA - page 15

    15 MINI-TOWER BATTERY REPLACEMENT CAUTION- A battery can present a risk of electrical shock and h igh short circuit current. The following precautions should be obs erved before replaci ng the batteries: • Turn off and disconnect the UPS from utility power prior to ope ning the battery replacement door. • Remove rings, watches, and other metal ...

  • Liebert 700-2200 VA - page 16

    16 MINI-TOWER BATTERY REPLACEMENT 700 VA Model To Disconnect: Gentl y pull wiring away To Connect: Connect red wire to red terminal, then black wire to black terminal by pushing towards connector 1000/1400 VA Model To Disconnect: Gentl y pull wiring away To Connect: Connect red wire to red terminal, then black wire to black terminal by pushing upwa ...

  • Liebert 700-2200 VA - page 17

    17 RACKMOUNT BATTERY REPLACEMENT CAUTION- A battery can present a risk of electrical shock and h igh short circuit current. The following precautions should be obs erved before replacin g the batteries: • Turn off and disconnect the UPS from utility power prior to ope ning the battery replacement door. • Remove rings, watches, and other metal o ...

  • Liebert 700-2200 VA - page 18

    18 Figure 3 Figure 5 Figure 4 Figure 1 Figure 2 Fi g ure 6 Figure 7 DISCONTINUED P R O D U C T ...

  • Liebert 700-2200 VA - page 19

    19 TROUBLESHOOTING The information b elow indicates vario us symptoms a user may encounter in the event the PowerSure™ Interactive UPS dev elo ps a problem. Use this inf ormation to determine whether external factors ca use the problem and ho w to remedy the situation. 1. The fault indicator will flash ever y second to indic ate the UPS detected ...

  • Liebert 700-2200 VA - page 20

    20 TROUBLESHOOTING GUIDE PROBLEM CAUSE SOLUTION UPS output short circuited or overloaded. Ensure UPS is off. Disco nnect all loads and ensure noth ing is lodged in output r eceptacles. Ensure loads are not de fective or shorted internally. UPS fails to start when On/Off button is pressed Internal fuse is blown, indicating internal fault. Do not att ...

  • Liebert 700-2200 VA - page 21

    21 POWERSURE™ INTERACTIVE TYPICAL BATTERY DISCHARGE CURVES (Discharge times are at 25° C ambient ) 0 25 50 75 100 0 20 40 60 80 Percent Load R un Ti me (Mi ns ) 0 25 50 75 100 0 20 40 60 80 Percent Load Run Tim e (Mins ) 0 25 50 75 100 0 20 40 60 80 P e r ce n t L oad R un Ti me (Mi ns ) 0 25 50 75 100 0 20 40 60 80 P e r ce n t L oad Run Tim e ...

  • Liebert 700-2200 VA - page 22

    22 AUDIBLE ALARM CONDITIONS CONDITION ALARM Battery mode (utility failure) One short beep every ten seconds; more than t wo minutes of run time remaining Low battery Two short beeps every five seconds; less than t wo minutes of run time remaining Battery replacement Two second beep every minute UPS output overload One short beep ever y second UPS f ...

  • Liebert 700-2200 VA - page 23

    23 MINI-TOWER SPECIFICATIONS Model Number PS700MT-120 PS1000MT- 120 PS1400MT-120 PS2200MT-120 Model Rating VA/W 700 / 450 1000 / 670 1400 / 950 2200 / 1600 DIMENSIONS: in (mm) Unit W x D x H 5.5 x 14.4 x 7.0 (140 x 365 x 178) 6.8 x 17.5 x 8.9 (172 x 447 x 227) 6.8 x 17.5 x 8.9 (172 x 447 x 227) 7.6 x 20.1 x 13.2 (194 x 511 x 336) Shipping W x D x H ...

  • Liebert 700-2200 VA - page 24

    24 RACKMOUNT SPECIFICATIONS Model Number PS700RM-120 PS1000RM-120 PS1400RM-120 PS2200RM-120 Model Rating VA/W 700 / 450 1000 / 670 1400 / 950 2200 / 1600 DIMENSIONS: in (mm) Unit W x D x H 19 x 18 x 5.25 (483 x 457 x 133) 19 x 18 x 5.25 (483 x 457 x 133) 19 x 18 x 5.25 (483 x 457 x 133) 19 x 18 x 7 (483 x 457 x 178) Shipping W x D x H 27.5 x 24 x 1 ...

  • Liebert 700-2200 VA - page 25

    2 5 DISCONTINUED P R O D U C T ...

  • Liebert 700-2200 VA - page 26

    1050 Dearborn Drive Columbus, OH 43229 614-888-0246 Technical Support U.S.A........................... ....................................1-800-222-5877 Outside the U.S.A ..................... ......................614-841-6755 U.K..................................... ........................... +44 (0) 1793 553355 France ......................... ...

Produzent Liebert Kategorie Power Supply

Dokumente, die wir vom Produzenten des Geräts Liebert 700-2200 VA erhalten, können wir in mehrere Gruppen teilen. Unteranderem in:
- technische Zeichnungen Liebert
- Bedienungsanleitungen 700-2200 VA
- Produktkarten Liebert
- Informationsbroschüren
- oder Energieetiketten Liebert 700-2200 VA
Jede von ihnen ist wichtig, jedoch finden wir die wichtigsten Informationen für den Nutzer des Geräts in der Bedienungsanleitung Liebert 700-2200 VA.

Die Dokumentengruppe, die als Bedienungsanleitungen bezeichnet wird, wird ebenfalls in detaillierte Arten geteilt, solche wie: Montageanleitungen Liebert 700-2200 VA, Wartungsanleitungen, Kurzanleitungen oder Benutzeranleitungen Liebert 700-2200 VA. Abhängig vom Bedarf, sollten Sie das Dokument finden, das Sie brauchen. In unserem Service können Sie sich die populärste Bedienungsanleitung des Produkts Liebert 700-2200 VA ansehen.

Ähnliche Bedienungsanleitungen

Die komplette Bedienungsanleitung des Geräts Liebert 700-2200 VA, wie sollte sie aussehen?
Die Bedienungsanleitung, auch bezeichnet als Benutzerhandbuch, oder einfach nur „Anleitung”, ist ein technisches Dokument, das dem Benutzer bei der Nutzung von Liebert 700-2200 VA hilfreich sein soll. Die Bedienungsanleitungen werden in der Regel von technischen Schriftstellern geschrieben, aber in einer Sprache, die für alle Nutzer von Liebert 700-2200 VA verständlich ist.

Eine gänzliche Bedienungsanleitung von Liebert sollte einige Grundelemente enthalten. Ein Teil von ihnen ist nicht so wichtig, wie z.B.: die Titelseite oder Autorenseiten. Die restlichen von ihnen jedoch, sollten Informationen liefern, die für den Nutzer von enormer Wichtigkeit sind.

1. Einführung und Hinweise, wie man sich in einer Bedienungsanleitung von Liebert 700-2200 VA bewegt - Am Anfang jeder Bedienungsanleitung sollten wir Hinweise bezüglich der Nutzungsart eines bestimmten Ratgebers finden. In ihr sollten sich Informationen über die Lokalisierung des Inhaltsverzeichnisses von Liebert 700-2200 VA befinden, FAQ oder über oft auftretende Probleme – also Stellen, die von den Benutzern in jeder Bedienungsanleitung am meisten gesucht werden
2. Inhaltsverzeichnis - Index aller Ratschläge bezüglich Liebert 700-2200 VA, die wir im aktuellen Dokument finden
3. Ratschläge zur Nutzung der Grundfunktionen des Geräts Liebert 700-2200 VA - die uns die ersten Schritte während der Nutzung von Liebert 700-2200 VA erleichtern sollten
4. Troubleshooting - geordneter Tätigkeitslauf, der uns bei der Diagnose und als nächstes bei der Lösung wichtiger Probleme mit Liebert 700-2200 VA hilft
5. FAQ - häufig gestellte Fragen
6. Kontaktdaten Informationen darüber, wo man Kontakt zum Produzenten / Service von Liebert 700-2200 VA im bestimmten Land suchen kann, wenn es nicht gelingt, das Problem selbst zu lösen.

Haben Sie eine Frage bezüglich Liebert 700-2200 VA?

Nutzen Sie das untere Formular

Wenn Sie mit Hilfe der gefundenen Bedienungsanleitung Ihr Problem mit Liebert 700-2200 VA nicht gelöst haben, stellen Sie eine Frage, indem Sie das untere Formular nutzen. Wenn einer der Nutzer ein ähnliches Problem mit Liebert 700-2200 VA hatte, ist es möglich, dass er mit Ihnen die Lösung teilen möchte.

Text vom Bild übertragen

Kommentare (0)