    SINGLE-PACKAGE GAS HEATING/ELECTRIC COOLING UNITS Model 582A Sizes 018-060 1-1/2 to 5 Nominal Tons Low NOx Models Available Form No. PDS 582A.18.2 Single-Package Rooftop Units with. • Direct Spark Ignition • Low Sound Levels • AFUE ratings up to 81.1% • 10 SEER AVAILABLE OPTIONS One-piece heating and cooling units with low sound levels, eas ...

  • Bryant 582A - page 2

    2 Low Sound Ratings ensure a quiet indoor and outdoor environ- ment with sound ratings as low as 7.5 bels. (See ARI capacity charts for individual values.) Easy-to-Service Cabinets provide easy single-panel acces- sibility to serviceable components during maintenance and installation. The basepan with integrated drain pan provides easy ground level ...

  • Bryant 582A - page 3

    ARI* CAP ACITIES COOLING CAP ACITIES AND EFFICIENCIES UNIT 582A NOMINAL T ONS ST ANDARD CFM NET COOLING CAP ACITIES (Btuh) SEER† SOUND RA TINGS** (Bels) 018040 1 1 / 2 600 18,000 10.0 7.5 024040 024060 2 800 24,600 10.0 7.5 030040 030060 2 1 / 2 1000 28,800 10.0 7.5 036060 036090 3 1200 34,400 10.0 8.0 042060 042090 3 1 / 2 1400 42,000 10.0 8.0 0 ...

  • Bryant 582A - page 4

    PHYSICAL DA T A UNIT SIZE 582A 018040 024040 024060 030040 030060 036060 036090 042060 042090 NOMINAL CAP ACITY (ton) 1 1 / 2 22 2 1 / 2 2 1 / 2 33 3 1 / 2 3 1 / 2 OPERA TING WEIGHT (lb) 249 280 280 280 280 314 314 355 355 COMPRESSOR(S) – QUANTITY Reciprocating-1 REFRIGERANT (R-22) Quantity (lb) 2.6 3.5 3.5 3.65 3.65 3.75 3.75 5.7 5.7 REFRIGERANT ...

  • Bryant 582A - page 5

    OPTIONS AND ACCESSORIES F ACTORY -INST ALLED OPTIONS Louvered Grille provides hail guard and vandalism protection. A wire grille is standard on all models. See model number no- menclature for louvered grille options. Coil Options include copper/copper and vinyl-coated construc- tion for refrigerant coils. Units are shipped standard with copper tube ...

  • Bryant 582A - page 6

    OPTIONS AND ACCESSORIES (cont) Economizer DAMPER BLADE MANUAL OUTSIDE AIR HOOD REPLACEMENT P ANEL Filter Rack Manual Outdoor Air Damper 6 ...

  • Bryant 582A - page 7

    BASE UNIT DIMENSIONS – 582A018-042 REQ'D CLEARANCES FOR OPERA TION AND SER VICING. in. (mm) Evaporator coil access side .................. 3 6 (914) Power entry side (except for NEC requirements) ......... 3 6 (914) Unit top ........................... 3 6 (914) Side opposite ducts ..................... 3 6 (914) Duct panel ................. ...

  • Bryant 582A - page 8

    BASE UNIT DIMENSIONS – 582A048-060 FLUE HOOD REQ'D CLEARANCES FOR OPERA TION AND SER VICING. in. (mm) Evaporator coil access side .................. 3 6 (914) Power entry side (except for NEC requirements) ......... 3 6 (914) Unit top ........................... 3 6 (914) Side opposite ducts ..................... 3 6 (914) Duct panel ....... ...

  • Bryant 582A - page 9

    ACCESSOR Y DIMENSIONS UNIT SIZE 582A ODS ORDER NUMBER A in. [mm] B in. [mm] C in. [mm] D in. [mm] FLA T CURB 018-042 CPRFCURB006A00 8 [203] 1 1 27 / 32 [301] 30 5 / 8 [778] 28 3 / 4 [730] CPRFCURB007A00 14 [356] 1 1 27 / 32 [301] 30 5 / 8 [778] 28 3 / 4 [730] 048,060 CPRFCURB008A00 8 [203] 15 27 / 32 [402] 42 1 / 8 [1070] 40 1 / 4 [1022] CPRFCURB00 ...

  • Bryant 582A - page 10

    SELECTION PROCEDURE (with example) I DETERMINE COOLING AND HEA TING REQUIRE- MENTS A T DESIGN CONDITIONS: Given: Required Cooling Capacity (TC) .......... 34,000 Btuh Btuh Sensible Heat Capacity (SHC) ....... 25,000 Btuh Btuh Required Heating Capacity ......... 60,000 Btuh Condenser Entering Air T emperature ............9 5 F Indoor-Air T emperatur ...

  • Bryant 582A - page 11

    PERFORMANCE DA T A NET COOLING CAP ACITIES 582A018 TEMP (F) OUTDOOR-AIR ENTERING CONDENSER EV APORA T OR AIR—CFM/BF 525/0.118 Evaporator Air—Ewb (F) 62 67 72 62 67 72 62 67 72 85 TC 15.7 18.5 20.9 16.5 19.2 21.5 17.2 19.8 21.9 SHC 13.5 1 1.6 9.5 14.9 12.7 10.2 16.2 13.6 10.7 kW 1.75 1.80 1.83 1.77 1.81 1.84 1.78 1.82 1.85 95 TC 14.5 17.3 19.9 1 ...

  • Bryant 582A - page 12

    PERFORMANCE DA T A (cont) NET COOLING CAP ACITIES (cont) 582A036 TEMP (F) OUTDOOR-AIR ENTERING CONDENSER EV APORA T OR AIR—CFM/BF 1050/0.095 Evaporator Air—Ewb (F) 62 67 72 62 67 72 62 67 72 85 TC 31.8 35.3 38.7 32.7 36.1 39.5 33.4 36.8 40.1 SHC 29.1 24.2 19.0 31.4 26.0 20.0 33.4 27.6 21.0 kW 3.48 3.57 3.66 3.50 3.59 3.68 3.52 3.61 3.70 95 TC 3 ...

  • Bryant 582A - page 13

    PERFORMANCE DA T A (cont) NET COOLING CAP ACITIES (cont) 582A060 TEMP (F) OUTDOOR-AIR ENTERING CONDENSER EV APORA T OR AIR – CFM/BF 1750/0.039 Evaporator Air – Ewb (F) 62 67 72 62 67 72 62 67 72 85 TC 53.9 61.5 69.3 56.1 63.6 71.1 58.0 65.2 72.4 SHC 48.8 41.4 33.4 53.7 45.2 35.7 58.0 48.8 37.9 kW 6.12 6.33 6.52 6.21 6.38 6.57 6.25 6.42 6.62 95 ...

  • Bryant 582A - page 14

    PERFORMANCE DA T A (cont) DR Y COIL AIR DELIVER Y*—HORIZONT AL AND DOWNFLOW DISCHARGE (Deduct 10% for 208 v) 230 AND 460 VOL T Unit 582A Motor Speed External Static Pressure (in. wg) 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 018 Low W atts 227 212 196 177 165 153 CFM 1082 1016 929 796 668 428 ————— ————— Med W atts ——— ...

  • Bryant 582A - page 15

    PERFORMANCE DA T A (cont) ECONOMIZER/1-IN. FIL TER PRESSURE DROP UNIT 582A PRESSURE DROP (in. wg) 018-042 0.12 048, 060 0.24 WET COIL PRESSURE DROP UNIT 582A AIRFLOW (CFM) PRESSURE DROP (in. wg) 018 500 0.049 600 0.070 700 0.095 024 700 0.077 800 0.100 900 0.127 030 900 0.065 1000 0.080 1 100 0.097 036 1 100 0.084 1200 0.100 1300 0.177 042 1300 0.1 ...

  • Bryant 582A - page 16

    TYPICAL PIPING AND WIRING V ertical Discharge *NEC – National Electrical Code Horizontal Discharge 16 INDOOR THERMOST A T DISCONNECT PER NEC* FROM POWER SOURCE RETURN AIR T OP CO VER FROM GAS LINE *NEC - NA TIONAL ELECTRICAL CODE Horizontal Discharge ...

  • Bryant 582A - page 17

    17 APPLICATION DATA 1. CONDENSATE TRAP —A 2-in. condensate trap must be field supplied. 2. DUCTWORK —Secure downflo w discharge ductwork to roof curb . For horizontal discharge applications , attach ductwork to unit with flanges. 3. T O CONVERT A UNIT TO DOWNFLO W DISCHARGE — Units are equipped with f actor y-installed inser ts in the down ...

  • Bryant 582A - page 18

    TYPICAL WIRING SCHEMA TIC, 582A018-060; 208/230-1-60 LEGEND BR — Blower Relay C— Contactor CAP — Capacitor COMP — Compressor Motor CR — Combustion Relay EQUIP — Equipment FS — Flame Sensor FU — Fuse GND — Ground GVR — Gas V alve Relay HS — Hall Effect Sensor HV — High Voltage T ransformer TRAN I— Ignitor IDM — Induced-Dr ...

  • Bryant 582A - page 19

    TYPICAL WIRING SCHEMA TIC, 582A030-060; 208/230-3-60 LEGEND AHA — Adjustable Heat Anticipator BR — Blower Relay C— Contactor CAP — Capacitor COMP — Compressor Motor CR — Combustion Relay CS — Centrifugal Switch EQUIP — Equipment FS — Fusible Link FU — Fuse GND — Ground GV — Gas V alve GVR — Gas V alve Relay HS — Hall Eff ...

  • Bryant 582A - page 20

    TYPICAL WIRING SCHEMA TIC, 582A036-060; 460-3-60 LEGEND AHA — Adjustable Heat Anticipator BR — Blower Relay C— Contactor CAP — Capacitor COMP — Compressor Motor CR — Combustion Relay CS — Centrifugal Switch EQUIP — Equipment FS — Fusible Link FU — Fuse GND — Ground GV — Gas V alve GVR — Gas V alve Relay HS — Hall Effect ...

  • Bryant 582A - page 21

    ELECTRICAL DA T A UNIT SIZE 582A V -PH-Hz VOL T AGE RANGE COMPRESSOR COND F AN MOTOR INDOOR F AN MOTOR POWER SUPPL Y Min Max RLA LRA FLA FLA MCA MOCP* 018 208/230-1-60 187 253 9.0 45.0 0.8 1.8 13.9 20 024 208/230-1-60 187 253 12.8 61.0 0.8 2.0 18.8 30 030 208/230-1-60 187 253 14.4 73.0 0.8 2.0 20.8 30 036 042 208/230-1-60 187 253 18.6 105.0 1.6 3.8 ...

  • Bryant 582A - page 22

    CONTROLS OPERA TING SEQUENCE Heating — When the thermostat calls for heating, terminal “W” is energized, starting the induced-draft motor . When the hall- effect sensor on the induced-draft motor senses that it has reached the required speed, the burner ignition sequence be- gins. The indoor (evaporator) fan motor (IFM) is energized 45 second ...

  • Bryant 582A - page 23

    GUIDE SPECIFICA TIONS P ACKAGED HEA TING/COOLING UNITS CONST ANT VOLUME APPLICA TION HV AC GUIDE SPECIFICA TIONS SIZE RANGE: 1 1 / 2 TO 5 TONS, NOMINAL COOLING 40,000 T O 130,000 BTUH, NOMINAL HEA TING INPUT BRY ANT MODEL NUMBER: 582A P ART 1 — GENERAL SYSTEM DESCRIPTION Outdoor rooftop mounted or ground level installed, gas heating/electric cool ...

  • Bryant 582A - page 24

    GUIDE SPECIFICA TIONS (cont) K. Electrical Requirements: All unit power wiring shall enter the unit cabinet at a single location. L. Motors: 1. Compressor motors shall be of the refrigerant-cooled type with line-break thermal and current overload protection. 2. All fan motors shall have permanently lubricated bear- ings, and inherent, automatic res ...

Produzent Bryant Kategorie Heating System

Dokumente, die wir vom Produzenten des Geräts Bryant 582A erhalten, können wir in mehrere Gruppen teilen. Unteranderem in:
- technische Zeichnungen Bryant
- Bedienungsanleitungen 582A
- Produktkarten Bryant
- Informationsbroschüren
- oder Energieetiketten Bryant 582A
Jede von ihnen ist wichtig, jedoch finden wir die wichtigsten Informationen für den Nutzer des Geräts in der Bedienungsanleitung Bryant 582A.

Die Dokumentengruppe, die als Bedienungsanleitungen bezeichnet wird, wird ebenfalls in detaillierte Arten geteilt, solche wie: Montageanleitungen Bryant 582A, Wartungsanleitungen, Kurzanleitungen oder Benutzeranleitungen Bryant 582A. Abhängig vom Bedarf, sollten Sie das Dokument finden, das Sie brauchen. In unserem Service können Sie sich die populärste Bedienungsanleitung des Produkts Bryant 582A ansehen.

Ähnliche Bedienungsanleitungen

Die komplette Bedienungsanleitung des Geräts Bryant 582A, wie sollte sie aussehen?
Die Bedienungsanleitung, auch bezeichnet als Benutzerhandbuch, oder einfach nur „Anleitung”, ist ein technisches Dokument, das dem Benutzer bei der Nutzung von Bryant 582A hilfreich sein soll. Die Bedienungsanleitungen werden in der Regel von technischen Schriftstellern geschrieben, aber in einer Sprache, die für alle Nutzer von Bryant 582A verständlich ist.

Eine gänzliche Bedienungsanleitung von Bryant sollte einige Grundelemente enthalten. Ein Teil von ihnen ist nicht so wichtig, wie z.B.: die Titelseite oder Autorenseiten. Die restlichen von ihnen jedoch, sollten Informationen liefern, die für den Nutzer von enormer Wichtigkeit sind.

1. Einführung und Hinweise, wie man sich in einer Bedienungsanleitung von Bryant 582A bewegt - Am Anfang jeder Bedienungsanleitung sollten wir Hinweise bezüglich der Nutzungsart eines bestimmten Ratgebers finden. In ihr sollten sich Informationen über die Lokalisierung des Inhaltsverzeichnisses von Bryant 582A befinden, FAQ oder über oft auftretende Probleme – also Stellen, die von den Benutzern in jeder Bedienungsanleitung am meisten gesucht werden
2. Inhaltsverzeichnis - Index aller Ratschläge bezüglich Bryant 582A, die wir im aktuellen Dokument finden
3. Ratschläge zur Nutzung der Grundfunktionen des Geräts Bryant 582A - die uns die ersten Schritte während der Nutzung von Bryant 582A erleichtern sollten
4. Troubleshooting - geordneter Tätigkeitslauf, der uns bei der Diagnose und als nächstes bei der Lösung wichtiger Probleme mit Bryant 582A hilft
5. FAQ - häufig gestellte Fragen
6. Kontaktdaten Informationen darüber, wo man Kontakt zum Produzenten / Service von Bryant 582A im bestimmten Land suchen kann, wenn es nicht gelingt, das Problem selbst zu lösen.

Haben Sie eine Frage bezüglich Bryant 582A?

Nutzen Sie das untere Formular

Wenn Sie mit Hilfe der gefundenen Bedienungsanleitung Ihr Problem mit Bryant 582A nicht gelöst haben, stellen Sie eine Frage, indem Sie das untere Formular nutzen. Wenn einer der Nutzer ein ähnliches Problem mit Bryant 582A hatte, ist es möglich, dass er mit Ihnen die Lösung teilen möchte.

Text vom Bild übertragen

Kommentare (0)