    PRODUCT DATA 63-2689-05 Sp yder ® BA C n e t ® Pr ogrammab le Contr oller s PR ODUCT DESCRIPTION The PUB and PVB controllers are par t of the Sp yder f amily . These controllers are BACnet MS/TP netw ork devices designed to control HV AC equipment. These controllers provide man y options and adv anced system f eatures that allow state-of-the-ar t ...

  • Honeywell PUB4024S - page 2

    SP YDER® BACNET® PROGR AMMABLE CONTROLLERS 63-2689—0 5 2 OR DERING INFORMATION When purchasing replacement and moder nizat ion products from your TRADELINE® wholesaler or distributor , refer to the TRADELINE® Catalog or price sheets for complete ordering number . If you hav e additional que stions, need fur ther i nf or mation, or would lik e ...

  • Honeywell PUB4024S - page 3

    SPYDER® BA CNET® PROGR AMMABLE CONTROLLERS 3 63-2689—0 5 BEF ORE INSTALLATION The controller is av ailable in three models (see T able 1). Revie w the power , input, and output specifications on page 2 before installing the controller . — Hardw are driven by T riac output s must hav e a minim um current draw , when energized, of 25 mA and a m ...

  • Honeywell PUB4024S - page 4

    SP YDER® BACNET® PROGR AMMABLE CONTROLLERS 63-2689—0 5 4 Fig. 2. Damper with 90 de gree CW rotation to open. IMPORTANT Mount actuator flush with damper housing or add a spacer between the actuator mounting surface and damper box housing. Before Mounting Actu ator onto Damper Shaft (PVB0000AS, PVB4022AS and PVB6436AS) T ools required: — Philli ...

  • Honeywell PUB4024S - page 5

    SPYDER® BA CNET® PROGR AMMABLE CONTROLLERS 5 63-2689—0 5 IMPORTANT Special prec autions must be taken for dampers that open in a CCW directi on. The actuator is shipped with its rotation direction set to CW to Op en, which applies to the damper direction in ste ps 1 and 2 above . If the damper shaft rota tes in the CCW direction to open, the co ...

  • Honeywell PUB4024S - page 6

    SP YDER® BACNET® PROGR AMMABLE CONTROLLERS 63-2689—0 5 6 P anel Mounting The controller enclosure is cons tructed of a plastic base plate and a plastic factor y-snap-on cover . NO TE: The controller is design ed so that the cover does not need to be removed from the base plate for either mounting or wiring. The controller mounts usin g f our sc ...

  • Honeywell PUB4024S - page 7

    SPYDER® BA CNET® PROGR AMMABLE CONTROLLERS 7 63-2689—0 5 The application en gineer must re view the control job requirements. This includes the seq uences of operation for the controller , and f or the system as a whole. Usually , there are variables that m ust be passed b etween the controller and other Sp yder BACnet controller(s) that are re ...

  • Honeywell PUB4024S - page 8

    SP YDER® BACNET® PROGR AMMABLE CONTROLLERS 63-2689—0 5 8 required and thereby affect tr ansformer sizi ng. The f ollowing ex ample is an I x R line-loss calcula tion f or a 200 ft. (61m) run from the transf or mer to a controller drawing 37 V A and using two 18 A WG (1.0 sq mm) wires. The formula is: Loss = [length of round-tr ip wire run (ft.) ...

  • Honeywell PUB4024S - page 9

    SPYDER® BA CNET® PROGR AMMABLE CONTROLLERS 9 63-2689—0 5 on page 6. The ear th ground ter minal (ter minal 3) must be connected to a verif ied ear th ground for each controller in the group (see Fig. 12 on page 9). — All loads on the co ntrolle r must be powered by the same transf or mer that powers the controller itself . A controller can us ...

  • Honeywell PUB4024S - page 10

    SP YDER® BACNET® PROGR AMMABLE CONTROLLERS 63-2689—0 5 10 Cabling should be selected that meets or e xceeds the BA Cnet Standard which specifies the f ollowing: An MS/TP EIA-485 network shall use sh ielded, twisted-pair cable with characteristic i mpedance between 100 and 130 ohms. Distributed capacitance between conductors shall be less than 1 ...

  • Honeywell PUB4024S - page 11

    SPYDER® BA CNET® PROGR AMMABLE CONTROLLERS 11 63-2689—0 5 Fig. 13. T ermination modules. Wiring Method WARNING Electrical Shock Hazar d. Can cause severe inju ry , death o r property damage. Disconnect power supply before beginning wiring, or making wiring connections, to prevent electrical shock or equipment damage. NO TE: When attaching tw o ...

  • Honeywell PUB4024S - page 12

    SP YDER® BACNET® PROGR AMMABLE CONTROLLERS 63-2689—0 5 12 T able 7. Description of wiring ter minal connections for PUB6438S, PVB6436AS, and PVB6438NS. IMPORTANT If the controller is not connected to a good ear th ground, the controller's inter nal transient protectio n circuitr y is compromised and the function of protect- ing the control ...

  • Honeywell PUB4024S - page 13

    SPYDER® BA CNET® PROGR AMMABLE CONTROLLERS 13 63-2689—0 5 • T ypical controller wiri ng f or 4 to 20 mA heating, cooling, and model ML6161 floati ng motor control (see Fig . 21 on page 18). • T ypical controller wir ing for a pneumatic transducer , model RP7517B (see Fig. 22 on page 19). Fig. 16. Controller wiring diagram (model PVB6438NS s ...

  • Honeywell PUB4024S - page 14

    SP YDER® BACNET® PROGR AMMABLE CONTROLLERS 63-2689—0 5 14 Fig. 17. Controller wiring dia gram (model PVB6436AS shown) for typical V A V application with staged reheat. (For note 2, refer to Fig. 14.) AO-1 DI-1 UI-3 UI-2 UI-1 COM COM 24 V AC 24 V AC COM + - DO-1 DO-2 DO-3 OCCUP ANCY SENSOR (CONT ACTS CLOSED EQU ALS OCCUPIED) WINDOWS CONT ACTS (C ...

  • Honeywell PUB4024S - page 15

    SPYDER® BA CNET® PROGR AMMABLE CONTROLLERS 15 63-2689—0 5 Fig. 18. Contr oller wiring di agram (mod el PUB6438S shown) f or typica l PWM re heat and PWM peripheral heat v alve actuator . (For note 2, ref er to Fig. 14.) NO TE: Make sure to set the Co nfiguration DIP Switch as shown in Fig. 18. Switc h es 1 through 3 set the tim- ing of the ML79 ...

  • Honeywell PUB4024S - page 16

    SP YDER® BACNET® PROGR AMMABLE CONTROLLERS 63-2689—0 5 16 Fig. 19. Controller wiring diag ram (model PUB6438S s hown) f or typical AHU application. (For note 2, refer to Fig. 14.) 2 AO-1 DI-1 UI-2 UI-1 UI-5 24 V AC 24 V AC COM + - DO-1 DO-2 DO-3 DO-4 DO-8 UI-3 COM COM COM COM DISCHARGE AIR TEMP COM COM UI-6 OUTDOOR ENTHALPY RETURN ENTHALPY 20 V ...

  • Honeywell PUB4024S - page 17

    SPYDER® BA CNET® PROGR AMMABLE CONTROLLERS 17 63-2689—0 5 Fig. 20. Contr oller wiring di agram (model PUB6438S shown) with 4 to 20 mA enthalpy senso rs and digital inputs. (For note 2, refer to Fig. 14.) AO-1 DI-1 UI-2 UI-1 UI-5 COM 2 1 3 TO ASSURE PR OPER ELECTRICAL CONT ACT , WIRES MUST BE TWISTED TOGETHER BEFORE INSER TION INTO THE TERMINAL ...

  • Honeywell PUB4024S - page 18

    SP YDER® BACNET® PROGR AMMABLE CONTROLLERS 63-2689—0 5 18 Fig. 21. Co ntroller wiring diagram (model PUB6438S shown) with 4 to 20 mA he at ing, cool ing, and model ML6161 damper actuator . (For note 2, ref er to Fig. 14.) COM COM DO4 COM UI-6 FA N SERIES 70 V AL VE ACTU A TOR 24 VA C IN- PUT COM TWO - OR THREE-W A Y CHILLER W A TER VAL VE SERIE ...

  • Honeywell PUB4024S - page 19

    SPYDER® BA CNET® PROGR AMMABLE CONTROLLERS 19 63-2689—0 5 Fig. 22. Controller wiring diagram (model PUB6438S shown) f or RP7517B pneumatic transducer . CH E CKO U T Step 1. Check Instal lation and Wiring Inspect all wiring conn ections at the controller ter minals, and verify compliance with i nstallation wiring diagrams. If an y wir ing change ...

  • Honeywell PUB4024S - page 20

    SP YDER® BACNET® PROGR AMMABLE CONTROLLERS 63-2689—0 5 20 T able 8. Status LED St ates. B ACNET STATUS LED: The LED on the front of the contro ller , between the BACnet MS/TP terminal s and MA C Address DIP Switches, provides a visual indication of the BA C net MS/TP communication status. When the controller receives po wer , the LED appears in ...

  • Honeywell PUB4024S - page 21

    SPYDER® BA CNET® PROGR AMMABLE CONTROLLERS 21 63-2689—0 5 2. Once the ter minal bloc k is raised 1/4 in. (6.35 mm) from its alignment pins, grasp the ter minal bloc k at its center (f or long ter minal blocks g rasp it at each end) and pull it straight up. Contr oller Replacement (PVB0000AS, PVB4022AS and PVB6436AS) F or PVB0000AS, PVB4022AS an ...

  • Honeywell PUB4024S - page 22

    SP YDER® BACNET® PROGR AMMABLE CONTROLLERS 63-2689—0 5 22 ...

  • Honeywell PUB4024S - page 23

    SPYDER® BA CNET® PROGR AMMABLE CONTROLLERS 23 63-2689—0 5 ...

  • Honeywell PUB4024S - page 24

    SP YDER® BACNET® PROGR AMMABLE CONTROLLERS Automation and Control Solu tions Honeywell International Inc. 1985 Douglas Drive North Golden Valley, MN 55422 customer.honeywell.com ® U .S. Registere d T rademark © 2012 Hone ywell International Inc. 63-2689—05 M.S. Re v . 01-12 Printe d in United States BA Cnet ® is a registered tradema rk of AS ...

Produzent Honeywell Kategorie Universal Remote

Dokumente, die wir vom Produzenten des Geräts Honeywell PUB4024S erhalten, können wir in mehrere Gruppen teilen. Unteranderem in:
- technische Zeichnungen Honeywell
- Bedienungsanleitungen PUB4024S
- Produktkarten Honeywell
- Informationsbroschüren
- oder Energieetiketten Honeywell PUB4024S
Jede von ihnen ist wichtig, jedoch finden wir die wichtigsten Informationen für den Nutzer des Geräts in der Bedienungsanleitung Honeywell PUB4024S.

Die Dokumentengruppe, die als Bedienungsanleitungen bezeichnet wird, wird ebenfalls in detaillierte Arten geteilt, solche wie: Montageanleitungen Honeywell PUB4024S, Wartungsanleitungen, Kurzanleitungen oder Benutzeranleitungen Honeywell PUB4024S. Abhängig vom Bedarf, sollten Sie das Dokument finden, das Sie brauchen. In unserem Service können Sie sich die populärste Bedienungsanleitung des Produkts Honeywell PUB4024S ansehen.

Ähnliche Bedienungsanleitungen

Die komplette Bedienungsanleitung des Geräts Honeywell PUB4024S, wie sollte sie aussehen?
Die Bedienungsanleitung, auch bezeichnet als Benutzerhandbuch, oder einfach nur „Anleitung”, ist ein technisches Dokument, das dem Benutzer bei der Nutzung von Honeywell PUB4024S hilfreich sein soll. Die Bedienungsanleitungen werden in der Regel von technischen Schriftstellern geschrieben, aber in einer Sprache, die für alle Nutzer von Honeywell PUB4024S verständlich ist.

Eine gänzliche Bedienungsanleitung von Honeywell sollte einige Grundelemente enthalten. Ein Teil von ihnen ist nicht so wichtig, wie z.B.: die Titelseite oder Autorenseiten. Die restlichen von ihnen jedoch, sollten Informationen liefern, die für den Nutzer von enormer Wichtigkeit sind.

1. Einführung und Hinweise, wie man sich in einer Bedienungsanleitung von Honeywell PUB4024S bewegt - Am Anfang jeder Bedienungsanleitung sollten wir Hinweise bezüglich der Nutzungsart eines bestimmten Ratgebers finden. In ihr sollten sich Informationen über die Lokalisierung des Inhaltsverzeichnisses von Honeywell PUB4024S befinden, FAQ oder über oft auftretende Probleme – also Stellen, die von den Benutzern in jeder Bedienungsanleitung am meisten gesucht werden
2. Inhaltsverzeichnis - Index aller Ratschläge bezüglich Honeywell PUB4024S, die wir im aktuellen Dokument finden
3. Ratschläge zur Nutzung der Grundfunktionen des Geräts Honeywell PUB4024S - die uns die ersten Schritte während der Nutzung von Honeywell PUB4024S erleichtern sollten
4. Troubleshooting - geordneter Tätigkeitslauf, der uns bei der Diagnose und als nächstes bei der Lösung wichtiger Probleme mit Honeywell PUB4024S hilft
5. FAQ - häufig gestellte Fragen
6. Kontaktdaten Informationen darüber, wo man Kontakt zum Produzenten / Service von Honeywell PUB4024S im bestimmten Land suchen kann, wenn es nicht gelingt, das Problem selbst zu lösen.

Haben Sie eine Frage bezüglich Honeywell PUB4024S?

Nutzen Sie das untere Formular

Wenn Sie mit Hilfe der gefundenen Bedienungsanleitung Ihr Problem mit Honeywell PUB4024S nicht gelöst haben, stellen Sie eine Frage, indem Sie das untere Formular nutzen. Wenn einer der Nutzer ein ähnliches Problem mit Honeywell PUB4024S hatte, ist es möglich, dass er mit Ihnen die Lösung teilen möchte.

Text vom Bild übertragen

Kommentare (0)