    GPC 13 SEER R-410A Package Air Conditioners with R-410A Copyright © 2008 - 2010 Goodman Manufacturing Company, L.P. RT6322006r6 September 2010 This manual is to be used by qualified, professionally trained HV AC technicians only . Goodman does not assume any responsibility for property damage or personal injury due to improper service procedures o ...

  • Goodmans GPC1324H41A - page 2

    PRODUCT IDENTIFICA TION 2 The model and manufacturing number are used for positive identification of component parts used in manufacturing. Please use these numbers when requesting service or parts information. WARNING WARNING HIGH VOLTAGE! Disconnect ALL power before servicing or installing this unit. Multiple power sources may be present. Failure ...

  • Goodmans GPC1324H41A - page 3

    PRODUCT IDENTIFICA TION 3 The model and manufacturing number are used for positive identification of component parts used in manufacturing. Please use these numbers when requesting service or parts information. The United States Environmental Protection Agency (“EPA”) has issued various regulations re- garding the introduction and disposal of r ...

  • Goodmans GPC1324H41A - page 4

    4 PRODUCT DESIGN GPC Package Cooling Units are designed for outdoor instal- lations only in either residential or light commercial applica- tions. The connecting ductwork (Supply and Return) can be con- nected for either horizontal or vertical airflow. In the vertical application a matching Roof Curb is recommended. A return air filter must be inst ...

  • Goodmans GPC1324H41A - page 5

    PRODUCT DESIGN 5 In installations where the unit is installed above ground level and not serviceable from the ground (Example: Roof Top in- stallations), the installer must provide service platform for ser- vice person with rails or guards in accordance with local codes or ordinances or in their absence with the latest edition of the Uniform Mechan ...

  • Goodmans GPC1324H41A - page 6

    6 PRODUCT DIMENSIONS GPC13[24-60]H41** B A 66” Ch ass i s M o d el A B G P C 132 4 33 3 0½ G P C 133 0 33 3 0½ G P C 133 6 33 3 5½ G P C 134 2 33 3 5½ G P C 134 9 33 3 5½ La rg e GPC 134 8 33 3 8½ G P C 136 0 33 3 8½ D i men s ions i n i nc he s Sm a ll Me d i u m ...

  • Goodmans GPC1324H41A - page 7

    ACCESSORIES 7 GPC13[24-60]H41** P a rt Nu m b e r De s cr i p t i on O T 18- 60 A O ut door T her mosta t Ki t w /Loc kout S t at O T /EHR18-60 Em e r genc y Heat Rel ay Ki t HKR El ectric Heat Ki t PCCP101- 103 Roof C ur b PCP 101- 103 Dow nflow Pl e num Ki t PCP 101- 103R8 Dow nflow Pl e num Ki t w / R - 8 In s ul ati on G PCED101- 103 Dow nflow ...

  • Goodmans GPC1324H41A - page 8

    8 PRODUCT DESIGN ELECTRICAL DA T A (*Blower Only , Heat Mode) All wires and overcurrent protection devices are sized for use with electric heaters only and without refrigeration. If heaters are not installed with above wire size, overheating and fire could occur. See PACKAGE COOLING SPECIFICATIONS section for minimum circuit ampacity and maximum ov ...

  • Goodmans GPC1324H41A - page 9

    BLOWER PERFORMANCE DA T A 9 Dry Coil Data NOTES: 1. Data shown is Dry Coil. Wet Coil Pressure Drop is approximate. 2. 0.1" H 2 O, for 2 row indoor coil; 0.2” H 2 O, for 3 row indoor coil; and 0.3” H 2 O, for 4 row indoor coil. 3. Data shown does not include filter pressure drop, approx. 0.08” H 2 O. 4. Reduce airflow by 2% for 208V opera ...

  • Goodmans GPC1324H41A - page 10

    10 BLOWER PERFORMANCE DA T A 30 40 50 60 70 80 90 110 1 2 0 100 13 0 140 15 0 100 90 80 70 60 50 40 30 20 10 OUT P UT B TU/ H R x 10 0 0 BT U OUTPUT vs TEMPER AT URE RISE CHART TEMPERAT URE RISE 600 C FM 700 900 1000 1100 1200 140 0 160 0 1800 2000 220 0 240 0 C F M FORMULA S BTU OUTPUT = CFM x 1.08 x RISE RISE = BTU OUTPUT 1.0 8 ÷ CF M 800 ...

  • Goodmans GPC1324H41A - page 11

    P ACKAGE COOLING SPECIFICA TIONS 11 GPC13[24-30]H41AA IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters. (1) Maximum Overcurrent Protection D ...

  • Goodmans GPC1324H41A - page 12

    P ACKAGE COOLING SPECIFICA TIONS 12 IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters. (1) Maximum Overcurrent Protection Device: MUST use Ti ...

  • Goodmans GPC1324H41A - page 13

    P ACKAGE COOLING SPECIFICA TIONS 13 GPC13[48-60]H41BA IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters. (1) Maximum Overcurrent Protection D ...

  • Goodmans GPC1324H41A - page 14

    14 COOLING PERFORMANCE DA T A GPC1324H41AA MOD E L: GP C1 324 H4 1A* EX PAN DE D P ER F O R MANC E D ATA C OOLI NG OP ER AT I ON De si g n S u b coo li n g , 1 2± 3 ° F @ th e l i q u i d a cce ss f i tti n g co n n ect i o n A H R I 95 t e st co n d i t i o n s . Des i g n S u p e r h e at 8± 3 ° F @ t h e co m p re s s or s uc tio n a c ce ss ...

  • Goodmans GPC1324H41A - page 15

    15 COOLING PERFORMANCE DA T A GPC1324H41AA MOD EL : GP C1 324 H4 1A* EX PAN DE D P ER F O R MANC E D ATA C OOL I NG OP ER ATI ON De si g n S u b coo li n g , 1 2± 3 ° F @ th e l i qu i d a cce ss fi tti ng co n n ect i o n A H R I 95 t e st co n d i ti o n s . Des i g n S u p e r h e at 8± 3 ° F @ th e co m p re s s or suc ti on ac c ess f i tt ...

  • Goodmans GPC1324H41A - page 16

    16 COOLING PERFORMANCE DA T A GPC1330H41AA MOD E L : G P C 1330H 4 1A* EX PAN DE D P ER F O R M AN C E D ATA C OOL ING OPER AT ION D es ign S ub c oo l ing , 1 2 ± 3 ° F @ t he li qu id ac c e s s f it t ing c o nn e c tio n A H R I 9 5 t es t c o nd itio ns. De s ig n Su p erh e a t 8 ± 3 °F @ t h e c omp r e s s o r s uc t io n a c ce ss f it ...

  • Goodmans GPC1324H41A - page 17

    17 COOLING PERFORMANCE DA T A GPC1330H41AA MOD E L : G P C 1330H 4 1A* EX PAN DE D P ER F O R M ANC E D ATA C OOL ING OPER AT ION D es ign S u bc oo l in g, 1 2 ± 3 ° F @ th e liqu id ac c e s s f it t ing c o nn e c tio n A H R I 9 5 t es t c on dit io n s. D e s ig n Sup e rh ea t 8 ±3 °F @ t h e c omp r e s s o r s uc t io n a c ce ss f it t ...

  • Goodmans GPC1324H41A - page 18

    18 COOLING PERFORMANCE DA T A GPC1336H41AA MOD E L : G P C 1336H41A * EX PAN DE D P ER F O R MANC E D ATA C OOLI NG OP ER AT I ON De si g n S u b coo li n g , 1 2± 3 ° F @ th e l i q u i d a cce ss f i tti n g co n n ect i o n A HR I 95 t e st co n d i t i o n s . Des i g n S u p e r h e at 8± 3 ° F @ t h e co m p re s s or s uc tio n a c c e s ...

  • Goodmans GPC1324H41A - page 19

    19 COOLING PERFORMANCE DA T A GPC1336H41AA MOD E L : G P C 1336H41A * EX PAN DE D P ER F O R MANC E D AT A C OOLI NG OP ER AT I ON De si g n S u b coo li n g , 1 2± 3 ° F @ th e l i qu i d a cce ss fi tti ng co n n ect i o n A H R I 95 t e st co n d i ti o n s . Des i g n S u p e r h e at 8± 3 ° F @ th e co m p re s s or suc ti on ac c ess f i ...

  • Goodmans GPC1324H41A - page 20

    20 COOLING PERFORMANCE DA T A GPC1342H41AA MOD E L : G P C 1342H41A * EX PAN DE D P ER F O R M AN C E D ATA C OOL I NG OP ER ATI ON De si g n S u b coo li n g , 1 2± 3 ° F @ th e l i q u i d a cce ss f i tti n g co n n ect i o n A H R I 95 t e st co n d i t i o n s . Des i g n S u p e r h e at 8± 3 ° F @ t h e co m p re s s or s uc tio n a c ce ...

  • Goodmans GPC1324H41A - page 21

    21 COOLING PERFORMANCE DA T A GPC1342H41AA MOD E L : G P C 1342H41A * EX PAN DE D P ER F O R MANC E D AT A C OOLI NG OP ER AT I ON De si g n S u b coo li n g , 1 2± 3 ° F @ th e l i qu i d a cce ss fi tti ng co n n ect i o n A H R I 95 t e st co n d i ti o n s . Des i g n S u p e r h e at 8± 3 ° F @ th e co m p re s s or suc ti on ac c ess f i ...

  • Goodmans GPC1324H41A - page 22

    22 COOLING PERFORMANCE DA T A GPC1348H41BA MOD E L: GP C 1348H41** EX PAN DE D P ER F O R MANC E D ATA C OOLI NG OP ER AT I ON De si g n S u b coo li n g , 1 2± 3 ° F @ th e l i q u i d a cce ss f i tti n g co n n ect i o n A H R I 95 t e st co n d i t i o n s . Des i g n S u p e r h e at 8± 3 ° F @ t h e co m p re s s or s uc tio n a c ce ss f ...

  • Goodmans GPC1324H41A - page 23

    23 COOLING PERFORMANCE DA T A GPC1348H41BA MOD E L: GP C 1348H41** EX PAN DE D P ER FO R MANC E D ATA C OOL ING OP ER AT ION De si g n S u b coo li n g , 1 2± 3 ° F @ th e l i qu i d a cce ss fi tti ng co n n ect i o n A H R I 95 t e st co n d i ti o n s . Des i g n S u p e r h e at 8± 3 ° F @ th e co m p re s s or suc ti on ac c ess f i tting ...

  • Goodmans GPC1324H41A - page 24

    24 COOLING PERFORMANCE DA T A GPC1360H41BA MOD E L: GP C 1360H41** EX PAN DE D P ER F O R MANC E D ATA C OOLI NG OP ER AT I ON De si g n S u b coo li n g , 1 2± 3 ° F @ th e l i q u i d a cce ss f i tti n g co n n ect i o n A H R I 95 t e st co n d i t i o n s . Des i g n S u p e r h e at 8± 3 ° F @ t h e co m p re s s or s uc tio n a c ce ss f ...

  • Goodmans GPC1324H41A - page 25

    25 COOLING PERFORMANCE DA T A GPC1360H41BA MOD E L: GP C 1360H41** EX PAN DE D P ER FO R MANC E D ATA C OOL ING OP ER AT ION De si g n S u b coo li n g , 1 2± 3 ° F @ th e l i qu i d a cce ss fi tti ng co n n ect i o n A H R I 95 t e st co n d i ti o n s . Des i g n S u p e r h e at 8± 3 ° F @ th e co m p re s s or suc ti on ac c ess f i tting ...

  • Goodmans GPC1324H41A - page 26

    26 COOLING PERFORMANCE DA T A PERFORMANCE TEST All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoo r air cubic feet per minute (CFM) as listed in the Performance Data Sheets: If conditions vary from this, results will change as follows: 1. As indoor dry bulb temperatures incr ...

  • Goodmans GPC1324H41A - page 27

    WIRING DIAGRAMS 27 WARN I NG HIGH V OLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT . MULTI PLE PO WER S OUR CES MA Y BE PRESENT . F AILURE TO DO SO MAY CAUSE PROPERTY DAM AGE, PERSONAL INJURY OR DEATH. Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. NOTE #4 FC NOTE # ...

  • Goodmans GPC1324H41A - page 28

    28 WIRING DIAGRAMS Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. WARN I NG HIGH V OLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT . MULTI PLE PO WER S OUR CES MA Y BE PRESENT . F AILURE TO DO SO MAY CAUSE PROPERTY DAM AGE, PERSONAL INJURY OR DEATH. GPC1360H41BA 2 3 ...

  • Goodmans GPC1324H41A - page 29

    29 GPC1324H41AB GPC1330H41AB GPC1336H41AB GPC 13 SEER R-410A 5 mm Package Air Conditioners GPC Package Cooling Units are designed for outdoor instal- lations only in either residential or light commercial applica- tions. The connecting ductwork (Supply and Return) can be con- nected for either horizontal or vertical airflow. In the vertical applica ...

  • Goodmans GPC1324H41A - page 30

    30 PRODUCT DESIGN Location and Clearances NOTE: To ensure proper condensate drainage, unit must be installed in a level position. 36" 36" 10" UNIT WALL 36" Outside Slab Installation - Horizontal (H) Minimum clearances are required to avoid air recirculation and keep the unit operating at peak efficiency. 36" 36" 24&quo ...

  • Goodmans GPC1324H41A - page 31

    P ACKAGE COOLING SPECIFICA TIONS 31 MODELS WITH 5MM COILS GPC13[24-36]H41AB IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters. (1) Maximum Ov ...

  • Goodmans GPC1324H41A - page 32

    P ACKAGE COOLING SPECIFICA TIONS 32 MODELS WITH 5MM COILS GPC1342H41AB GPC1349H41AA GPC1360H41BB IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric he ...

  • Goodmans GPC1324H41A - page 33

    33 COOLING PERFORMANCE DA T A 5MM COILS GPC1324H41AB MOD E L : GPC 1324H 41A * EX PAN DE D P ER FO R M ANC E D AT A C OOL ING OP ER AT IO N Ou t doo r A m bi en t Te mpera ture 65 75 8 5 95 10 5 115 E nt e ri n g In d o o r W et B u lb T em p e r at ur e I D B * A i r f l o w 5 96 36 77 15 9 6 36 77 15 96 36 7 7 15 9 6 3 6 7 7 1 5 96 36 77 15 9 6 3 ...

  • Goodmans GPC1324H41A - page 34

    34 COOLING PERFORMANCE DA T A 5MM COILS GPC1324H41AB MOD E L : GP C 1324H41 A * EX PAN DE D P ER F O R MANC E D ATA CO O LI N G O PE RA TI O N O ut d o or A m b i en t T em per atu r e 65 75 8 5 95 10 5 115 E nte ri ng I nd oor Wet Bul b T e m pe r a ture I D B * A i r f l o w 5 96 36 77 15 9 6 36 77 15 96 36 7 7 15 9 6 3 6 7 7 1 5 96 36 77 15 9 6 ...

  • Goodmans GPC1324H41A - page 35

    35 COOLING PERFORMANCE DA T A 5MM COILS GPC1330H41AB MOD EL: GPC 1330H41A * EX PAN DE D P E R F O R M ANC E D ATA C OOL ING OP ER AT I ON Ou t doo r A m bi e nt Te mpera ture 65 75 8 5 9 5 10 5 115 E nt e ri n g In d oo r W e t B ulb T e m per a tu re I D B * A i r f l o w 5 96 36 77 15 9 6 36 77 15 96 36 7 7 15 9 6 3 6 7 7 1 5 96 36 77 15 9 6 36 7 ...

  • Goodmans GPC1324H41A - page 36

    36 COOLING PERFORMANCE DA T A 5MM COILS GPC1330H41AB MOD EL: GPC 1330H41A * EX PAN DE D P E R F O R M ANC E D AT A C OOL I NG OP E R AT ION Ou t doo r A m bi e nt Te mpera ture 65 75 8 5 9 5 10 5 115 E nt eri ng Ind oo r W e t B ulb T e m per a tu re I D B * A i r f l o w 5 96 36 77 15 9 6 36 77 15 96 36 7 7 15 9 6 3 6 7 7 1 5 96 36 77 15 9 6 36 77 ...

  • Goodmans GPC1324H41A - page 37

    37 COOLING PERFORMANCE DA T A 5MM COILS GPC1336H41AB MOD E L: GPC 1336H 41A * EX PA N DE D P ER F O R M AN C E D AT A C OOL ING OP ER AT I ON Ou t doo r A mbi e nt Te m pera ture 65 75 8 5 95 10 5 115 E nt eri ng Ind oo r W et B ulb T e m per atu re I D B * A i r f l o w 5 9 6 36 77 15 9 6 3 6 7 7 15 96 36 7 7 1 5 9 6 3 6 7 7 1 5 96 36 77 15 9 6 36 ...

  • Goodmans GPC1324H41A - page 38

    38 COOLING PERFORMANCE DA T A 5MM COILS GPC1336H41AB MOD E L: GP C 1336H41A * EX PA N DE D P ER F O R M AN C E D ATA C OOLI NG OP ER ATI ON O ut d o o r A m b i ent T em p er atu r e 65 75 8 5 95 10 5 115 E n ter i n g Ind oo r W e t Bu lb T em p e r at u re I D B * A i r f l o w 5 96 36 77 15 9 6 36 77 15 96 36 7 7 15 9 6 3 6 7 7 1 5 96 36 77 15 9 ...

  • Goodmans GPC1324H41A - page 39

    39 COOLING PERFORMANCE DA T A 5MM COILS GPC1342H41AB MOD E L: GP C 1342H41A * EX PA N DE D P ER FO R MANC E D ATA C OOL ING OP ER AT ION O ut d o o r A m b i ent T em p er atu r e 65 75 8 5 95 10 5 115 E n ter i ng In d o o r W e t Bu lb T em p er a t u r e I D B * A i r f l o w 5 96 36 77 15 9 6 36 77 15 96 36 7 7 15 9 6 3 6 7 7 1 5 96 36 77 15 9 ...

  • Goodmans GPC1324H41A - page 40

    40 COOLING PERFORMANCE DA T A 5MM COILS GPC1342H41AB MOD EL: GP C 1342H41A * EX PAN DE D P ER F O R MAN C E D ATA C O OL ING OP ER AT I ON Ou t doo r A mbi e nt Tempe r a ture 65 75 8 5 95 10 5 115 E nte r i ng I nd oor W e t Bul b T e m pe r a tur e I D B * A i r f l o w 5 96 36 77 15 9 6 36 77 15 96 36 7 7 15 9 6 3 6 7 7 1 5 96 36 77 15 9 6 36 77 ...

  • Goodmans GPC1324H41A - page 41

    41 COOLING PERFORMANCE DA T A 5MM COILS GPC1349H41AA MOD EL: GP C 1349H41A * E XP A ND E D PE RF O RM A N CE DA T A C OO LIN G OP E R ATION O ut d o o r A m b i en t T em p er at u r e 65 75 8 5 95 10 5 115 E nte r i ng I nd oor We t Bul b T e m pe r a ture I D B * A i r f l o w 5 96 36 77 15 9 6 36 77 15 96 36 7 7 15 9 6 3 6 7 7 1 5 96 36 77 15 9 ...

  • Goodmans GPC1324H41A - page 42

    42 COOLING PERFORMANCE DA T A 5MM COILS GPC1349H41AA MOD E L: GP C 1349H41A * EX PA N DE D P ER F O R M AN C E D ATA C OOLI NG OP ER ATI ON O ut d o o r A m b i ent T em p er atu r e 65 75 8 5 95 10 5 115 E n ter i n g Ind oo r W e t Bu lb T em p e r at u re I D B * A i r f l o w 5 96 36 77 15 9 6 36 77 15 96 36 7 7 15 9 6 3 6 7 7 1 5 96 36 77 15 9 ...

  • Goodmans GPC1324H41A - page 43

    43 COOLING PERFORMANCE DA T A GPC1360H41BB 5MM COILS MOD E L: GP C 1360H41B* EX PAN DE D P ER F O R M AN C E D ATA C OOLI NG OP ER AT I ON O ut d o o r A m b i ent T em p er atu r e 65 75 8 5 95 10 5 115 E n ter i ng In d o o r W e t Bu lb T em p er a t u r e I D B * A i r f l o w 5 96 36 77 15 9 6 36 77 15 96 36 7 7 15 9 6 3 6 7 7 1 5 96 36 77 15 ...

  • Goodmans GPC1324H41A - page 44

    44 COOLING PERFORMANCE DA T A GPC1360H41BB 5MM COILS MOD E L: GP C 1360H41B* EX PAN DE D P ER F O R M AN C E D ATA C OOLI NG OP ER ATI ON O ut d o o r A m b i ent T em p er atu r e 65 75 8 5 95 10 5 115 E n ter i ng In d o o r W e t B u lb T em p er at ur e I D B * A i r f l o w 5 96 36 77 15 9 6 36 77 15 96 36 7 7 15 9 6 3 6 7 7 1 5 96 36 77 15 9 ...

  • Goodmans GPC1324H41A - page 45

    45 COOLING PERFORMANCE DA T A PERFORMANCE TEST All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoo r air cubic feet per minute (CFM) as listed in the Performance Data Sheets: If conditions vary from this, results will change as follows: 1. As indoor dry bulb temperatures incr ...

  • Goodmans GPC1324H41A - page 46

    46 WIRING DIAGRAMS Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. WARN I NG HIGH V OLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT . MULTI PLE PO WER S OUR CES MA Y BE PRESENT . F AILURE TO DO SO MAY CAUSE PROPERTY DAM AGE, PERSONAL INJURY OR DEATH. GPC13[24-42]H41AB ...

  • Goodmans GPC1324H41A - page 47

    WIRING DIAGRAMS 47 WARN I NG HIGH V OLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT . MULTI PLE PO WER S OUR CES MA Y BE PRESENT . F AILURE TO DO SO MAY CAUSE PROPERTY DAM AGE, PERSONAL INJURY OR DEATH. Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. GPC1360H41BB 2 3 ...

Produzent Goodmans Kategorie Air Conditioner

Dokumente, die wir vom Produzenten des Geräts Goodmans GPC1324H41A erhalten, können wir in mehrere Gruppen teilen. Unteranderem in:
- technische Zeichnungen Goodmans
- Bedienungsanleitungen GPC1324H41A
- Produktkarten Goodmans
- Informationsbroschüren
- oder Energieetiketten Goodmans GPC1324H41A
Jede von ihnen ist wichtig, jedoch finden wir die wichtigsten Informationen für den Nutzer des Geräts in der Bedienungsanleitung Goodmans GPC1324H41A.

Die Dokumentengruppe, die als Bedienungsanleitungen bezeichnet wird, wird ebenfalls in detaillierte Arten geteilt, solche wie: Montageanleitungen Goodmans GPC1324H41A, Wartungsanleitungen, Kurzanleitungen oder Benutzeranleitungen Goodmans GPC1324H41A. Abhängig vom Bedarf, sollten Sie das Dokument finden, das Sie brauchen. In unserem Service können Sie sich die populärste Bedienungsanleitung des Produkts Goodmans GPC1324H41A ansehen.

Ähnliche Bedienungsanleitungen

Die komplette Bedienungsanleitung des Geräts Goodmans GPC1324H41A, wie sollte sie aussehen?
Die Bedienungsanleitung, auch bezeichnet als Benutzerhandbuch, oder einfach nur „Anleitung”, ist ein technisches Dokument, das dem Benutzer bei der Nutzung von Goodmans GPC1324H41A hilfreich sein soll. Die Bedienungsanleitungen werden in der Regel von technischen Schriftstellern geschrieben, aber in einer Sprache, die für alle Nutzer von Goodmans GPC1324H41A verständlich ist.

Eine gänzliche Bedienungsanleitung von Goodmans sollte einige Grundelemente enthalten. Ein Teil von ihnen ist nicht so wichtig, wie z.B.: die Titelseite oder Autorenseiten. Die restlichen von ihnen jedoch, sollten Informationen liefern, die für den Nutzer von enormer Wichtigkeit sind.

1. Einführung und Hinweise, wie man sich in einer Bedienungsanleitung von Goodmans GPC1324H41A bewegt - Am Anfang jeder Bedienungsanleitung sollten wir Hinweise bezüglich der Nutzungsart eines bestimmten Ratgebers finden. In ihr sollten sich Informationen über die Lokalisierung des Inhaltsverzeichnisses von Goodmans GPC1324H41A befinden, FAQ oder über oft auftretende Probleme – also Stellen, die von den Benutzern in jeder Bedienungsanleitung am meisten gesucht werden
2. Inhaltsverzeichnis - Index aller Ratschläge bezüglich Goodmans GPC1324H41A, die wir im aktuellen Dokument finden
3. Ratschläge zur Nutzung der Grundfunktionen des Geräts Goodmans GPC1324H41A - die uns die ersten Schritte während der Nutzung von Goodmans GPC1324H41A erleichtern sollten
4. Troubleshooting - geordneter Tätigkeitslauf, der uns bei der Diagnose und als nächstes bei der Lösung wichtiger Probleme mit Goodmans GPC1324H41A hilft
5. FAQ - häufig gestellte Fragen
6. Kontaktdaten Informationen darüber, wo man Kontakt zum Produzenten / Service von Goodmans GPC1324H41A im bestimmten Land suchen kann, wenn es nicht gelingt, das Problem selbst zu lösen.

Haben Sie eine Frage bezüglich Goodmans GPC1324H41A?

Nutzen Sie das untere Formular

Wenn Sie mit Hilfe der gefundenen Bedienungsanleitung Ihr Problem mit Goodmans GPC1324H41A nicht gelöst haben, stellen Sie eine Frage, indem Sie das untere Formular nutzen. Wenn einer der Nutzer ein ähnliches Problem mit Goodmans GPC1324H41A hatte, ist es möglich, dass er mit Ihnen die Lösung teilen möchte.

Text vom Bild übertragen

Kommentare (0)