    APC Silcon 240-320kW 400V UPS Installation Guide Copyright 2000 APC Denmark ApS This manual is subject to change without notice and does not represent a commitment on the part of the vendor ...

  • American Power Conversion 240-320kW 400V - page 2

    2 Installation Guide APC Silcon 240-320kW 400V UPS 990-4045a Thank You! Thank you for chosing the APC Silcon Series UPS. Please read this Installation Guide thoroughly prior to installing the system. It provides important information on safe and efficient installation. The installation and use of this product must comply with national, federal, sta ...

  • American Power Conversion 240-320kW 400V - page 3

    990-4045a Installation Guide APC Silcon 240-320kW 400V UPS 3 Contents 1.0 Introduction 5 1.1 Tools and Equipment 5 2.0 Unpacking 6 3.0 Installation 7 3.1 Requirements on Site 7 3.1.1 Cabinet Dimensions 7 3.2 Footprint 8 3.2.1 1600mm Cabinet for 240-320kW UPS 8 3.2.2 825mm Cabinet for Isolation Transformer or Switch Gear 8 3.2.3 1600mm Cabinet for I ...

  • American Power Conversion 240-320kW 400V - page 4

    4 Installation Guide APC Silcon 240-320kW 400V UPS 990-4045a 6.3 Intersystem Synchronization Unit 56 6.4 Remote Display 57 6.4.1 Extension of Remote Display Communication Distance 57 6.4.2 Remote Display Installation 59 6.4.3 Remote Display Use 60 6.5 Isolation Transformer 61 6.5.1 Connecting Isolation Transformer 62 6.5.2 Wiring up UPS with Extern ...

  • American Power Conversion 240-320kW 400V - page 5

    Introduction 990-4045a Installation Guide APC Silcon 240-320kW 400V UPS 5 1.0 Introduction Power regulation varies from country to country, and information given in this installation guide can therefore only be of a general nature. Electricians should therefore always refer to national and local electrical codes prior to installing the UPS system. ...

  • American Power Conversion 240-320kW 400V - page 6

    6 Installation Guide APC Silcon 240-320kW 400V UPS 990-4045a Unpacking 2.0 Unpacking 1. To unpack UPS unit, remove top and bottom screws from side plates of packaging and lift up side plates 2. Verify compliance between type label on reverse side of front door and system ordered. Check input and output voltage 3. Copy type label data to label copy ...

  • American Power Conversion 240-320kW 400V - page 7

    Installation 990-4045a Installation Guide APC Silcon 240-320kW 400V UPS 7 3.0 Installation 3.1 Requirements on Site All system parts are accessible from front or top of UPS. Cable entries are accessible from bottom. A 1-metre free space on all sides should be allowed during installation. After installation of the UPS, leave a free space of 600 mm t ...

  • American Power Conversion 240-320kW 400V - page 8

    8 Installation Guide APC Silcon 240-320kW 400V UPS 990-4045a Installation 3.2 Footprint 3.2.1 1600mm Cabinet for 240-320kW UPS 3.2.2 825mm Cabinet for Isolation Transformer or Switch Gear 3.2.3 1600mm Cabinet for Isolation Transformer Power cable entry com. cable entry Rear Front Rear Power cable entry Front Power cable entry Rear ...

  • American Power Conversion 240-320kW 400V - page 9

    External Connection 990-4045a Installation Guide APC Silcon 240-320kW 400V UPS 9 4.0 External Connection 4.1 Connecting the UPS NOTICE! Check correct phase rotation of mains input voltage!! Max. input/output cables: 3//300 mm 2 . If there is no neutral input Dzn0 or Dyn11 input isolation transformer is required. CAUTION! This UPS unit is an EN 5009 ...

  • American Power Conversion 240-320kW 400V - page 10

    10 Installation Guide APC Silcon 240-320kW 400V UPS 990-4045a External Connection * DIN gL types PVC cables insulated to withstand ambient temperature of max. 30oC ** Must be rated as external PE cable if mains system is not supplying PE CAUTION! At a switch mode load of 100% the neutral must be rated for 200% output phase current. UPS External Inp ...

  • American Power Conversion 240-320kW 400V - page 11

    External Connection 990-4045a Installation Guide APC Silcon 240-320kW 400V UPS 11 4.2 System Integration Interface System Integration Interface (SII) is the control link between UPS and system main switches as shown in above diagram. The purpose of the SII is to ensure correct operation of switches without losing system output power. Auxiliary cont ...

  • American Power Conversion 240-320kW 400V - page 12

    12 Installation Guide APC Silcon 240-320kW 400V UPS 990-4045a External Connection 4.2.1 Connections Blue Brown ...

  • American Power Conversion 240-320kW 400V - page 13

    External Connection 990-4045a Installation Guide APC Silcon 240-320kW 400V UPS 13 Terminal Blocks: X003/X004 (Anxiliary Contacts) When switching Q001, Q002, Q010, Battery Breaker 1 or Battery Breaker 2 from “ON or 1” to “OFF or 0”, the anxiliary contact has to be open BEFORE the corresponding main contacts are opened. When switching Q001, Q ...

  • American Power Conversion 240-320kW 400V - page 14

    14 Installation Guide APC Silcon 240-320kW 400V UPS 990-4045a External Connection The built-in parallel board connects two or more UPS systems in parallel, either to obtain increased system reliability or to obtain higher output power. The parallel board also ensures correct load-sharing between paralled systems. To prepare the UPS for parallel/red ...

  • American Power Conversion 240-320kW 400V - page 15

    External Connection 990-4045a Installation Guide APC Silcon 240-320kW 400V UPS 15 External Control Cables External multicore cable is equipped with 15-pin SUB-D plug at either end. Connect pin 1 to pin 1, and pin 2 to pin 2 etc. up to pin 15 - with the exception of pin 8, which is not to be connected. Shield is connected to plug cover at both ends. ...

  • American Power Conversion 240-320kW 400V - page 16

    16 Installation Guide APC Silcon 240-320kW 400V UPS 990-4045a External Connection 4.4 Relay Board Relays All relays are “fail safe”: In alarm modes, relay coil will be de-energized. Maximum load: 8.0A – 250VAC Minimum load: 0.05A – 6VAC 1 2 3 0.3A – 60VDC 0.05A – 6VDC ...

  • American Power Conversion 240-320kW 400V - page 17

    External Connection 990-4045a Installation Guide APC Silcon 240-320kW 400V UPS 17 4.4.1 Relay Board/Relay Functions NOTICE If alarm mode “ Communication to controller lost ” is active, ALL relays will indicate failure Relay Number Message Alarm-trigging Events 1 ## (X002) Mains outside limits Mains voltage RMS outside limits Mains wave form (fa ...

  • American Power Conversion 240-320kW 400V - page 18

    18 Installation Guide APC Silcon 240-320kW 400V UPS 990-4045a External Connection ## Delay programmable in configuration stack : “ Common fault delay ” . Settings 0,10,20,30 seconds. Maximum cable size: 2mm 2 See section 5.2: System configuration NOTICE! Alarm Trigging Events 1-2-3-9-10-11-13 activates the corresponding alarm relay after the de ...

  • American Power Conversion 240-320kW 400V - page 19

    External Connection 990-4045a Installation Guide APC Silcon 240-320kW 400V UPS 19 4.5 Communication Interface Board The 3-port ComInterface is used to establish an interaction between UPS and e.g. a computer system. Main purpose: To ensure a controlled computer shut-down in case of a mains supply failure. 4.5.1 Connections . . ...

  • American Power Conversion 240-320kW 400V - page 20

    20 Installation Guide APC Silcon 240-320kW 400V UPS 990-4045a External Connection 4.6 Connecting of APC Silcon Tripel Chassis The enclosed Triple Chassis must be connected to the serial port on the Communication Interface Board, and to the 24V supply (cables included). Terminal locations shown below. 240/320kW APC Silcon Triple Chassis Front view o ...

  • American Power Conversion 240-320kW 400V - page 21

    External Connection 990-4045a Installation Guide APC Silcon 240-320kW 400V UPS 21 4.7 APC Silcon Triple Chassis The APC Silcon Triple Chassis is an American Power Conversion (APC) external management peripheral that allows you to use monitoring and control management peripherals with your APC Silcon series UPS. The retrofit model is for use with Si ...

  • American Power Conversion 240-320kW 400V - page 22

    22 Installation Guide APC Silcon 240-320kW 400V UPS 990-4045a External Connection 4.7.2.3 LEDs The APC Silcon Triple Chassis status LED provides important information concerning operation of the chassis. Refer to the table below for a description of the conditions indicated by the LED. 4.7.2.4 Optional Power Input With the Optional Power input, you ...

  • American Power Conversion 240-320kW 400V - page 23

    External Connection 990-4045a Installation Guide APC Silcon 240-320kW 400V UPS 23 4.7.3.1 Order of Management Peripheral Cards Because UPS signals are passed between management peripherals, you must install management peripheral cards in the correct order for them to work together properly. The card slots are numbered 1 to 3, from left to right, as ...

  • American Power Conversion 240-320kW 400V - page 24

    24 Installation Guide APC Silcon 240-320kW 400V UPS 990-4045a External Connection To add card slots, you can daisy-chain the APC Silcon Triple Chassis with the standard Triple Chassis (AP9604) management peripheral, installing the APC Silcon Triple Chassis closer to the UPS. 4.7.4 Powering the APC Silcon Triple Chassis The APC Silcon Triple Chassis ...

  • American Power Conversion 240-320kW 400V - page 25

    External Connection 990-4045a Installation Guide APC Silcon 240-320kW 400V UPS 25 4.7.5 Troubleshooting The following table shows the solution to common problems with the operation of the Triple Chassis 4.7.5.1 If Problems Persist For problems not covered in the troubleshooting chart or for persistent problems, follow this procedure: 1) Note the se ...

  • American Power Conversion 240-320kW 400V - page 26

    26 Installation Guide APC Silcon 240-320kW 400V UPS 990-4045a External Connection 4) Pack the APC Silcon Triple Chassis carefully in its original packaging, if possible. Do not use polystyrene beads for packing. Damage sustained in transit is not covered under the warranty. Enclose a letter in the package with your name, address, RMA number, a copy ...

  • American Power Conversion 240-320kW 400V - page 27

    External Connection 990-4045a Installation Guide APC Silcon 240-320kW 400V UPS 27 UPS Shut Down RS-232 Input or Advanced Mode RS-232 Data RX In Line Fail RS-232 Output or Advanced Mode RS-232 Data TX Out Unregulated +24 VDC Output Normally Open Line Fail Signal Normally Open Low Battery Signal Normally Closed Line Fail Signal Common Chassis ...

  • American Power Conversion 240-320kW 400V - page 28

    28 Installation Guide APC Silcon 240-320kW 400V UPS 990-4045a External Connection 4.7.6.2 Power, Physical, and Environmental Specifications. Item Specification Power Turn on voltage: > 22 VDC Turn off voltage: < 16 VDC Current draw (normal operation): 90 mADC Current draw (voltage < 16 VDC ): < 1 mADC Physical Size (H xW x D): 1.75 x 17 ...

  • American Power Conversion 240-320kW 400V - page 29

    External Connection 990-4045a Installation Guide APC Silcon 240-320kW 400V UPS 29 4.8 APC Silcon Battery Cabinets Installation and use of this product must comply with all national, federal, state, municipal or local codes. If you need assistance, please have your UPS model and serial number ready and call APC, see “How to Contact APC” in this ...

  • American Power Conversion 240-320kW 400V - page 30

    30 Installation Guide APC Silcon 240-320kW 400V UPS 990-4045a External Connection 4.8.0.6 Installation of Batteries See Installation Guide for Battery Cabinet for: • Preparing Batteries and UPS • Dimensions and Weight • Connecting Batteries WARNING! Before proceding, ensure that power supplies have been disconnected from UPS for a minimum of ...

  • American Power Conversion 240-320kW 400V - page 31

    External Connection 990-4045a Installation Guide APC Silcon 240-320kW 400V UPS 31 4.9 Battery Breaker Box/Fuse-box Battery Breaker Box/Fuse-box provides overcurrent and short-circuit protection for UPS installations with external batteries. CAUTION! Batteries connected to a UPS out of service for a period exceeding 8 days may be damaged. Refer to S ...

  • American Power Conversion 240-320kW 400V - page 32

    32 Installation Guide APC Silcon 240-320kW 400V UPS 990-4045a External Connection 4.9.1 Battery Breaker Box UPS Ampere Rating [A] Connection Cable [mm2] Max. short- circuit current [kA] Dimensions HxWxD [mm] Weight [kg] 240 kW 320 kW 400 500 2//95 2//150 40 40 1035x835x300 1035x835x300 100 100 ...

  • American Power Conversion 240-320kW 400V - page 33

    External Connection 990-4045a Installation Guide APC Silcon 240-320kW 400V UPS 33 4.9.2 APC Battery Breaker Box Connection Diagram X009 LED signal from UPS “ OK to operate corresponding MCCB ” X010 MCCB position signals for UPS X011 Trip for emergency stop (220-240V AC) Battery 1 Battery 2 Battery 1 Battery 2 UPS UPS Main cables are connected d ...

  • American Power Conversion 240-320kW 400V - page 34

    34 Installation Guide APC Silcon 240-320kW 400V UPS 990-4045a External Connection 4.9.3 UPS with External Battery in Battery Breaker Box/Fuse-box Configuration ...

  • American Power Conversion 240-320kW 400V - page 35

    Programming Parameters 990-4045a Installation Guide APC Silcon 240-320kW 400V UPS 35 5.0 Programming Parameters Below table shows operating parameters programmable from keyboard. Only qualified users should re-set programming parameters. 5.1 Parameters * Factory settings in bold ** Only for systems with Battery Monitor active *** Do not leave syste ...

  • American Power Conversion 240-320kW 400V - page 36

    36 Installation Guide APC Silcon 240-320kW 400V UPS 990-4045a Programming Parameters 5.1.1 Programming Keys NOTICE! Display accuracy is + 1%, + digit. Scrolls up through list Scrolls down through list Stores parameters/ enter parameter stack Silences the audible alarm Chooses parameters Displays time Exits a mode Accesses alarm stack ...

  • American Power Conversion 240-320kW 400V - page 37

    Programming Parameters 990-4045a Installation Guide APC Silcon 240-320kW 400V UPS 37 5.1.2 Programming Example - Switch to Bypass Operation Return to normal operation Follow same procedure to program other parameters. 5.2 System Configuration System configuration parameters are vital for correct system operation and are password- protected. NOTICE! ...

  • American Power Conversion 240-320kW 400V - page 38

    38 Installation Guide APC Silcon 240-320kW 400V UPS 990-4045a Programming Parameters System Configuration Parameters (password protected) * Bold text refers to factory standard setting **Advanced Battery Monitor Parameter Setting* Comments Isolation Transformer Input YES, NO YES if optional input isolation transformer is available IsolationTransfor ...

  • American Power Conversion 240-320kW 400V - page 39

    Programming Parameters 990-4045a Installation Guide APC Silcon 240-320kW 400V UPS 39 5.2.1 Programming Example - Change Charge Voltage to 446 NOTICE! Change charge voltages, battery warning limit, shut down voltage and high battery temperature limit by entering the actual value. See example above. ...

  • American Power Conversion 240-320kW 400V - page 40

    40 Installation Guide APC Silcon 240-320kW 400V UPS 990-4045a Programming Parameters 5.2.2 Programming Example - Change to Output Isolation Transformer available NOTICE! Change parameters by pressing the key once or several times. See example above. ...

  • American Power Conversion 240-320kW 400V - page 41

    Programming Parameters 990-4045a Installation Guide APC Silcon 240-320kW 400V UPS 41 5.3 Programming Parameters for Advanced Parallel Operation To use the advanced parallel functions, the following parameters must be programmed: 1. “Station number” 2. “Highest station address” 3. “Advanced power management” 4. “APM test mode active” ...

  • American Power Conversion 240-320kW 400V - page 42

    42 Installation Guide APC Silcon 240-320kW 400V UPS 990-4045a Programming Parameters 5.3.2 Programming example Example with four systems in parallel with separate batteries. • Programme the station addresses 1-4: 1 for UPS 1, 2 for UPS 2, 3 for UPS 3, and 4 for UPS 4. • All UPS systems have to be programmed to “Highest station address”:4. ? ...

  • American Power Conversion 240-320kW 400V - page 43

    Options/Accessories 990-4045a Installation Guide APC Silcon 240-320kW 400V UPS 43 6.0 Options/Accessories Please contact your local APC representative for information on options/accessories available in your region. See “How to Contact APC” in this guide. 6.1 Service Bypass Panel for Single Operation UPS External System Input Fuse [A] Max. Pros ...

  • American Power Conversion 240-320kW 400V - page 44

    44 Installation Guide APC Silcon 240-320kW 400V UPS 990-4045a Options/Accessories 6.1.1 Wiring up UPS with SBP in TN-C-S Network 6.1.2 Wiring up UPS with SBP in TN-S Network ...

  • American Power Conversion 240-320kW 400V - page 45

    Options/Accessories 990-4045a Installation Guide APC Silcon 240-320kW 400V UPS 45 6.1.3 Operating The External Service Bypass Switch Action 1. Press on the ke yboard 2. Press or on the ke yboard until 3. Press on the ke yboard 4. Press on the ke yboard 5. Check lamp indication on the Service Bypass Panel 6. T urn the external bypass s witch (Q003) ...

  • American Power Conversion 240-320kW 400V - page 46

    46 Installation Guide APC Silcon 240-320kW 400V UPS 990-4045a Options/Accessories 6.1.3.1 Switching from External Bypass to Normal UPS Operation Action 1. T urn the input s witch (Q002) to position ” 0 “ 2. Open the UPS front door and press the green "ON ” key 3. Press on the ke yboard 4. Press or on the ke yboard until 5. Press on the k ...

  • American Power Conversion 240-320kW 400V - page 47

    Options/Accessories 990-4045a Installation Guide APC Silcon 240-320kW 400V UPS 47 6.2 Service Bypass Panel for Parallel Redundant Operation Service Bypass Panel (SBP) Mains Supply System Output Control cables Q003 Q004 Q001b Q001a Q002b Q002a APC Silcon 400V UPS X020 X021 X020 X021 APC Silcon 400V UPS Battery Battery Breaker/ Fuse Box ...

  • American Power Conversion 240-320kW 400V - page 48

    48 Installation Guide APC Silcon 240-320kW 400V UPS 990-4045a Options/Accessories 6.2.1 Two Parallel Systems with Service Bypass Panel ...

  • American Power Conversion 240-320kW 400V - page 49

    Options/Accessories 990-4045a Installation Guide APC Silcon 240-320kW 400V UPS 49 6.2.2 Parallel/Redundant Operation with Service Bypass Panel and External Battery via MCCB ...

  • American Power Conversion 240-320kW 400V - page 50

    50 Installation Guide APC Silcon 240-320kW 400V UPS 990-4045a Options/Accessories 6.2.3 Operating External Service Bypass Switch for Parallel Systems 6.2.3.1 Bypassing Parallel UPS Systems CAUTION! Batteries connected to a UPS out of service for a period exceeding 8 days may be damaged. H002a ...

  • American Power Conversion 240-320kW 400V - page 51

    Options/Accessories 990-4045a Installation Guide APC Silcon 240-320kW 400V UPS 51 Step 1-4 can be carried out with any of the parallel systems, ho we ver this will switch all systems into bypass operation. 1. Press on the keyboard 2. Press or on the keyboard until 3. Press on the keyboard 4. Press on the keyboard All systems will transf er to bypas ...

  • American Power Conversion 240-320kW 400V - page 52

    52 Installation Guide APC Silcon 240-320kW 400V UPS 990-4045a Options/Accessories 6.2.3.2 Switching Parallel System from External Bypass into Normal UPS Operation H002a ...

  • American Power Conversion 240-320kW 400V - page 53

    Options/Accessories 990-4045a Installation Guide APC Silcon 240-320kW 400V UPS 53 Action 1. Check that output s witch (Q004) is in position “ 0 ” 2. Check that all output s witches (Q002) are in position “ 0 ” 3. T ur n input switches (Q001) to position “ 1 ” 4. Open the UPS front door and press the green “ ON ” push-botton 5. Press ...

  • American Power Conversion 240-320kW 400V - page 54

    54 Installation Guide APC Silcon 240-320kW 400V UPS 990-4045a Options/Accessories 6.2.4 Isolating One UPS for Service/Maintenance In a redundant system, one UPS may be isolated for service/maintenance without affecting other UPSs. 1. Check that remaining UPS(s) is capable of carrying the load in the event that one UPS is isolated 2. Switch off syst ...

  • American Power Conversion 240-320kW 400V - page 55

    Options/Accessories 990-4045a Installation Guide APC Silcon 240-320kW 400V UPS 55 6.2.5 Switching Back to Normal Parallel/Redundant Operation 1. Turn input switch (Q001) and output switch (Q002) to position “ 1 ” 2. Charge capacitor, connect battery and start up UPS UPS will automatically switch to normal operation and start load-sharing with o ...

  • American Power Conversion 240-320kW 400V - page 56

    56 Installation Guide APC Silcon 240-320kW 400V UPS 990-4045a Options/Accessories 6.3 Intersystem Synchronization Unit Intersystem Synchronization Unit System (ISU System) The ISU system consists of inter-connected ISUs. One ISU system may consist of up to 5 ISUs, regardles of ISU configuration. The ISU system synchronizes the voltage of parallel o ...

  • American Power Conversion 240-320kW 400V - page 57

    Options/Accessories 990-4045a Installation Guide APC Silcon 240-320kW 400V UPS 57 6.4 Remote Display With the remote display unit data may be displayed at distances of up to 25 m from UPS. For extended communication distance, see section below. Remote display may easily be connected to UPS via one of the two serial communication ports on the commun ...

  • American Power Conversion 240-320kW 400V - page 58

    58 Installation Guide APC Silcon 240-320kW 400V UPS 990-4045a Options/Accessories 6.4.1.1 Connections Without Converter Connect a 25-pin female Sub-D and a 9-pin male Sub-D connector with a 3-wire shielded cable, as shown in the table below. Connect shield at one end only. Pin Connection for Interconnection Cable (without converter): 6.4.1.2 Connec ...

  • American Power Conversion 240-320kW 400V - page 59

    Options/Accessories 990-4045a Installation Guide APC Silcon 240-320kW 400V UPS 59 6.4.2 Remote Display Installation 6.4.2.1 Connecting RS232C and Mains Adapter 6.4.2.2 Remote Display Power Supply The remote display is supplied by normal AC power with no battery back-up. For UPS data transmission to remote display to remain unaffected during power f ...

  • American Power Conversion 240-320kW 400V - page 60

    60 Installation Guide APC Silcon 240-320kW 400V UPS 990-4045a Options/Accessories 6.4.3 Remote Display Use The remote display is an inactive unit unable to influence the operation of the UPS: Some of the alarms visible on the internal display are also available on the remote display (See the Alarm section in the APC Silcon User Guide). 6.4.3.1 Init ...

  • American Power Conversion 240-320kW 400V - page 61

    Options/Accessories 990-4045a Installation Guide APC Silcon 240-320kW 400V UPS 61 6.5 Isolation Transformer UPS Height [mm] Width [mm] Depth [mm] Weight [kg] 240kW 320kW 1800 1800 800 1600 800 800 1240 1470 NOTICE! APC isolation transformers are available in various configuration. Contact your local APC representative for further information. See ? ...

  • American Power Conversion 240-320kW 400V - page 62

    62 Installation Guide APC Silcon 240-320kW 400V UPS 990-4045a Options/Accessories 6.5.1 Connecting Isolation Transformer *DIN gL types PVC cables insulated to withstand a maximum ambient temperature of 30 o C UPS External Input Fuses* FM [A] 380-415V External Input Cable [mm2] 380-415V External PE Cable [mm2] External Output Cable [mm2] External Te ...

  • American Power Conversion 240-320kW 400V - page 63

    Options/Accessories 990-4045a Installation Guide APC Silcon 240-320kW 400V UPS 63 NOTICE! If an MCCB is used in stead of external input fuses, the MCCB load capacity must be 8xIn (nominal current) for minimum 10 ms. NOTICE! Check correct phase rotation of mains input voltage! Maximum input/output cables: 3//300 mm 2 . If input neutral is not availa ...

  • American Power Conversion 240-320kW 400V - page 64

    64 Installation Guide APC Silcon 240-320kW 400V UPS 990-4045a Options/Accessories *DIN gL types PVC cables insulated to withstand a maximum ambient temperature of 30 o C Isolation Transformer External Input Fuses* FM [A] 380-415V External Input Cable [mm2] 380-415V External PE Cable [mm2] External Output Cable [mm2] External Temp. Signal Cable Max. ...

  • American Power Conversion 240-320kW 400V - page 65

    Options/Accessories 990-4045a Installation Guide APC Silcon 240-320kW 400V UPS 65 6.5.2 Wiring up UPS with External Yyn0 Isolation Transformer at Output WARNING! Isolation transformer provides galvanic isolation between mains supply and load. Load will loose galvanic isolation if isolation transformer is bypassed NOTICE! Refer to local legal regula ...

  • American Power Conversion 240-320kW 400V - page 66

    66 Installation Guide APC Silcon 240-320kW 400V UPS 990-4045a Options/Accessories 6.5.3 Wiring up UPS with External Yyn0 Isolation Transformer at Input WARNING! Isolation transformer provides galvanic isolation between mains supply and load. Load will loose galvanic isolation if isolation transformer is bypassed. NOTICE! Refer to local legal regula ...

  • American Power Conversion 240-320kW 400V - page 67

    Options/Accessories 990-4045a Installation Guide APC Silcon 240-320kW 400V UPS 67 6.5.4 Wiring up UPS with External Optional Dzn0 Isolation Transformer at Input WARNING! Isolation transformer provides galvanic isolation between mains supply and load. Load will loose galvanic isolation if isolation transformer is bypassed. NOTICE! Refer to local leg ...

  • American Power Conversion 240-320kW 400V - page 68

    68 Installation Guide APC Silcon 240-320kW 400V UPS 990-4045a Options/Accessories 6.5.5 Wiring up UPS with External Optional Dzn0 Isolation Transformer at Output WARNING! Isolation transformer provides galvanic isolation between mains supply and load. Do not bypass isolation transformer in order to avoid damaging circulation currents and to prevent ...

  • American Power Conversion 240-320kW 400V - page 69

    Options/Accessories 990-4045a Installation Guide APC Silcon 240-320kW 400V UPS 69 6.5.6 Wiring up UPS with External Optional Dyn11 Isolation Transformer at Input WARNING! Isolation transformer provides galvanic isolation between mains supply and load. Do not bypass isolation transformer in order to avoid damaging circulation currents and to prevent ...

  • American Power Conversion 240-320kW 400V - page 70

    70 Installation Guide APC Silcon 240-320kW 400V UPS 990-4045a System Specifications 7.0 System Specifications 7.1 Technical Data 7.2 Dimensions / Weight Voltage 3x380/400/415V Input Voltage tolerance Normal operation Bypass operation + 15% + 10% (standard) + 4, 6, 8% (programmable) Frequency 50Hz/60Hz + 6 standard + 0.5-8% (programmable) Input powe ...

  • American Power Conversion 240-320kW 400V - page 71

    Warranty 990-4045a Installation Guide APC Silcon 240-320kW 400V UPS 71 8.0 Warranty 8.1 APC Silcon Series Limited Factory Warranty APC warrants that the unit, when properly installed and commissioned by APC or APC authorized service personnel, shall be free from defects in materials and workmanship for a period of (1) year from the date of installa ...

  • American Power Conversion 240-320kW 400V - page 72

    72 Installation Guide APC Silcon 240-320kW 400V UPS 990-4045a Appendix 9.0 Appendix 9.1 Table 1. Installation Planning Data Main Input Breaker Field Wiring* Battery Bank** UPS Module Service Bypass Panel Field Wiring Output Breaker * ** Internal Batteries available for 40kW units and smaller * * Q1 Q2 Q3 * Not supplied by APC Installation Planning ...

  • American Power Conversion 240-320kW 400V - page 73

    Appendix 990-4045a Installation Guide APC Silcon 240-320kW 400V UPS 73 Notes: 1. Nominal input current based on rated load. 2. Maximum input current based on rated load + full battery recharge. Full battery recharge assumed to increase input current with 10%. 3. Nominal power consumption (column 1c) based on nominal input current (1e) and the corre ...

  • American Power Conversion 240-320kW 400V - page 74

    74 Installation Guide APC Silcon 240-320kW 400V UPS 990-4045a How to Contact APC 10.0 How to Contact APC APC Corporate 132 Fairgrounds Road West Kingston, RI 02892 USA Telephone: +1 401 789-5735 Fax: +1 401 789-3710 Pre-sales Technical Support +1 877-474-5266 Post-sales Technical Support +1 877-287-7835 APC Denmark Silcon Allé DK-6000 Kolding Denm ...

Produzent American Power Conversion Kategorie Power Supply

Dokumente, die wir vom Produzenten des Geräts American Power Conversion 240-320kW 400V erhalten, können wir in mehrere Gruppen teilen. Unteranderem in:
- technische Zeichnungen American Power Conversion
- Bedienungsanleitungen 240-320kW 400V
- Produktkarten American Power Conversion
- Informationsbroschüren
- oder Energieetiketten American Power Conversion 240-320kW 400V
Jede von ihnen ist wichtig, jedoch finden wir die wichtigsten Informationen für den Nutzer des Geräts in der Bedienungsanleitung American Power Conversion 240-320kW 400V.

Die Dokumentengruppe, die als Bedienungsanleitungen bezeichnet wird, wird ebenfalls in detaillierte Arten geteilt, solche wie: Montageanleitungen American Power Conversion 240-320kW 400V, Wartungsanleitungen, Kurzanleitungen oder Benutzeranleitungen American Power Conversion 240-320kW 400V. Abhängig vom Bedarf, sollten Sie das Dokument finden, das Sie brauchen. In unserem Service können Sie sich die populärste Bedienungsanleitung des Produkts American Power Conversion 240-320kW 400V ansehen.

Die komplette Bedienungsanleitung des Geräts American Power Conversion 240-320kW 400V, wie sollte sie aussehen?
Die Bedienungsanleitung, auch bezeichnet als Benutzerhandbuch, oder einfach nur „Anleitung”, ist ein technisches Dokument, das dem Benutzer bei der Nutzung von American Power Conversion 240-320kW 400V hilfreich sein soll. Die Bedienungsanleitungen werden in der Regel von technischen Schriftstellern geschrieben, aber in einer Sprache, die für alle Nutzer von American Power Conversion 240-320kW 400V verständlich ist.

Eine gänzliche Bedienungsanleitung von American Power Conversion sollte einige Grundelemente enthalten. Ein Teil von ihnen ist nicht so wichtig, wie z.B.: die Titelseite oder Autorenseiten. Die restlichen von ihnen jedoch, sollten Informationen liefern, die für den Nutzer von enormer Wichtigkeit sind.

1. Einführung und Hinweise, wie man sich in einer Bedienungsanleitung von American Power Conversion 240-320kW 400V bewegt - Am Anfang jeder Bedienungsanleitung sollten wir Hinweise bezüglich der Nutzungsart eines bestimmten Ratgebers finden. In ihr sollten sich Informationen über die Lokalisierung des Inhaltsverzeichnisses von American Power Conversion 240-320kW 400V befinden, FAQ oder über oft auftretende Probleme – also Stellen, die von den Benutzern in jeder Bedienungsanleitung am meisten gesucht werden
2. Inhaltsverzeichnis - Index aller Ratschläge bezüglich American Power Conversion 240-320kW 400V, die wir im aktuellen Dokument finden
3. Ratschläge zur Nutzung der Grundfunktionen des Geräts American Power Conversion 240-320kW 400V - die uns die ersten Schritte während der Nutzung von American Power Conversion 240-320kW 400V erleichtern sollten
4. Troubleshooting - geordneter Tätigkeitslauf, der uns bei der Diagnose und als nächstes bei der Lösung wichtiger Probleme mit American Power Conversion 240-320kW 400V hilft
5. FAQ - häufig gestellte Fragen
6. Kontaktdaten Informationen darüber, wo man Kontakt zum Produzenten / Service von American Power Conversion 240-320kW 400V im bestimmten Land suchen kann, wenn es nicht gelingt, das Problem selbst zu lösen.

Haben Sie eine Frage bezüglich American Power Conversion 240-320kW 400V?

Nutzen Sie das untere Formular

Wenn Sie mit Hilfe der gefundenen Bedienungsanleitung Ihr Problem mit American Power Conversion 240-320kW 400V nicht gelöst haben, stellen Sie eine Frage, indem Sie das untere Formular nutzen. Wenn einer der Nutzer ein ähnliches Problem mit American Power Conversion 240-320kW 400V hatte, ist es möglich, dass er mit Ihnen die Lösung teilen möchte.

Text vom Bild übertragen

Kommentare (0)