Bedienungsanleitung Carrier 38AUQ

36 Seiten 3.39 mb
Download

Zur Seite of 36

Summary
  • Carrier 38AUQ - page 1

    Inst allation, S t art-Up and Service Instructions CONTENTS SA FE TY C ON SI DE RA TI ON S . . . . . . . . . . . . . . . . . . . . . . . 1 INST ALLA TION GUIDELI NES . . . . . . . . . . . . . . . . . . . . . . . 2 IN ST A LLA T IO N . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-14 St ep 1 – Pl an f or U ni t L oc at io n . . . ...

  • Carrier 38AUQ - page 2

    2 INST AL LA TION GUIDELIN E Replacem ent /Retrofit – R22 to Pu ron ® Split system heat pumps are intended to be installed with matching indoor sections only . The 38AUQ heat pump outdoor units are matched only with sa me-size 40RUQ indoor sections. Existing R-22 indoor coils cannot be converted to R-410A heat pump duty . Only the existing refri ...

  • Carrier 38AUQ - page 3

    3 Fig. 1 — 38AUQ*07-12 Unit Dimensions UNIT St andard Weig ht Corne r A Corner B Corner C Corner D Center of Gravity Unit Height lbs. kg. lbs. kg. lbs. kg. lbs. kg. lbs. kg. X Y Z H 38AUQ*07 444 201 134 61 97 44 90 41 123 56 23 [584] 26 [660] 13 [330] 42-3/8 [1076] 38AUQ*08 483 219 162 74 1 10 50 85 39 12 5 57 20 [508] 24 [610] 13 [330] 42-3/8 [1 ...

  • Carrier 38AUQ - page 4

    4 Table 1A — Physical Data — 38AUQ*07-12 Units — 60 Hz English UNIT SIZE 38AUQ *07 *08 *12 NOMINAL CAP ACITY (ton s) 67 . 5 1 0 OPERA TING WEIGHTS (lb) Aluminum-Fin Coils 444 483 575 REFRIGERANT TYPE ‡ R-410A Operating Charge, T ypical (l b) † 18.0 21.0 27.0 Shipping Charge (lb) 10.0 12.0 15.0 COMPRESSOR Qty ...T ype 1...Scroll 1...Scroll ...

  • Carrier 38AUQ - page 5

    5 Table 1B — Physical Data — 38AUQ*07-12 Units — 60 Hz SI UNIT SIZE 38AUQ *07 *08 *12 NOMINAL CAP ACITY (kW) 21.1 26.4 35.1 OPERA TING WEIGHT (kg) Aluminum-Fin Coils 201 219 261 REFRIGERANT TYPE ‡ R-410A Operating Charge, T ypical (kg ) † 8.2 9.5 12.2 Shipping Charge (kg) 4.5 5.9 6.8 COMPRESSOR Qty ...T ype 1...Scroll 1...Scroll 1...Scro ...

  • Carrier 38AUQ - page 6

    6 Fig. 2 — Model Number Nomenclature Fig. 3 — Serial Number Nomenclature 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 38 A U Q A 12 A 0 C 6– 0 A 0 A 0 Model T ype Pa cka g in g 3 8A U= C ar r ie r Condensing Unit R - - - 410A Ref ri geran t 0=S t a n d a r d Ty p e o f C o i l Electrical Options Q = Heat Pump Scroll Compressor A=N o n e C = N ...

  • Carrier 38AUQ - page 7

    7 . INST AL LA TION Jobsite Survey Complete the following checks before installation. 1. Consult local building codes and the NEC (National Electrical Code) ANSI/NFP A 70 for special installation requirements. 2. Determine unit location (from project plans) or select unit location. 3. Check for possible overhead obstructions which may in- terfere w ...

  • Carrier 38AUQ - page 8

    8 Table 2 — 38AUQ*0 7-12 Piping Recomme ndations (Singl e-Circuit Unit) CHECK VER TICAL SEP ARA TION — If there is any vertical separation between the indoor and outdoor units, check to ensure that the separation is within allowable limits. Relocate equipment if necessary . PROVIDE SAFETY RELIEF — If local codes dictate an additional safety r ...

  • Carrier 38AUQ - page 9

    9 Table 5 — Refrigerant Specia lties Part Numbers. INST ALL LIQUID LINE SOLENOID V AL VE — It is recommended that a bi-directional solenoid valve be placed in the main liquid line (see Figs. 5 & 6) between the outdoor unit and the indoor coil. Locate the solenoid valve at the end of the liquid line, near the outdoor unit connections, with f ...

  • Carrier 38AUQ - page 10

    10 MAKE PIPING CONNECTIONS — Piping connections at the 38AUQ unit are ball valves with stub tube ex tensions. Do not open the unit service valves until all interconnecting tube brazing as been completed. The stub tube connections include ¼-in SAE service fittings with Schrader valve cores (see Fig. 7). Before making any brazed connections to the ...

  • Carrier 38AUQ - page 11

    11 Field power wires are connected to the unit at line-side pres- sure lugs on compressor contac tor C and TB1 (see wiring dia- gram label for control box component arrangement) or at facto- ry-installed option non-fused disc on nect switch. Max wire size is #4 A WG (copper only). NOTE: TEST LEADS - Unit may be equipped with short leads (pigtails) ...

  • Carrier 38AUQ - page 12

    12 Fig. 10 — Convenience Outlet Location Non-powered type: This type requires the field installation of a general-purpose 125-volt 15-A circuit powered from a source elsewhere in the building. Observe national and local codes when selecting wire size, fuse or breaker requirements and disconnect switch size and loca tion. Route 125-v power supply ...

  • Carrier 38AUQ - page 13

    13 Press the gasket over the screw heads. Slip the backing plate over the screw heads at the keyhole slots and align with the gasket; tighten the two screws until snug (do not over-tighten). Mount the weatherproof cover to the backing plate as shown in Fig. 12. Remove two slot fillers in the bottom of the cover to permit service tool cords to exit ...

  • Carrier 38AUQ - page 14

    14 Table 8 — Electrical Data — 38AUQ*07-12 60 Hz Units LEGEND UNIT SIZE 38AUQ F ACTOR Y - INST ALLED OPTION NOMINAL V O LTA G E VOL T AGE RANGE ‡ COMPRESSOR F AN MOTORS POWER SUPPL Y V -Ph-Hz MIN MAX RLA LRA FLA (ea) QTY MCA MOCP *07 NONE OR DISCONNECT 208/230- 3-60 187 253 19.0 123 1.5 2 26.8 45 CONVENIENCE OUTLET 31.6 50 NONE OR DISCONNECT ...

  • Carrier 38AUQ - page 15

    15 PRE-ST AR T -UP System Check 1. Check all indoor section and other equipment auxiliary components. Consult the manufacturer ’ s instructions regarding any other equip m ent connected to the con- densing unit. If the unit ha s field-installed accessories, be sure all are properly installed and correctly wired. If used, the airflow switch mu st ...

  • Carrier 38AUQ - page 16

    16 Advanced Scroll T emperatur e Protection (ASTP) A label located above the terminal box identifies Copeland Scroll compressor models that contain this technology . See Fig. 14. Advanced Scroll T emperature Protection (ASTP) is a form of internal discharge temperature protection, that unloads the scroll compressor when the internal temperature rea ...

  • Carrier 38AUQ - page 17

    17 Fig. 16 — 38AUQ*07 Charging Chart Fig. 17 — 38AUQ*08 Charging Chart Fig. 18 — 38AUQ*12 Charging Chart ...

  • Carrier 38AUQ - page 18

    18 Fig. 19 — 38AUQ Wiring Di agram (208/230-3-60 shown) ...

  • Carrier 38AUQ - page 19

    19 OPERA TING SEQUENCE Base Unit Controls — Indoor (Supply) Fan The indoor fan contactor (IFC) is remotely located at the fan coil or fan section. If the thermostat fan operation is selected as Continuous, the IFC is energi zed and the indoor (supply) fan motor runs continuously . If the thermostat fan operation is selected as Automatic, the IFC ...

  • Carrier 38AUQ - page 20

    20 ROUTINE SYSTEM MAINTENANCE These items should be part of a routine maintenance program, to be checked every month or two, until a specific schedule for each can be identified for this installation: Quarterly Inspection (and 30 days after initial start) Indoor section • Coil cleanliness checked. • Return air filter replacement • Belt tensio ...

  • Carrier 38AUQ - page 21

    21 Liquid Line Filter Drier The factory-provided reversible filter drier is specifically de- signed to operate with Puron®. Replace the filter drier with factory-authorized components only with a filter drier with desiccant made from 100% molecular sieve grade XH-11. Fil- ter drier must be replac ed whenever the refrigerant system is opened. When ...

  • Carrier 38AUQ - page 22

    22 Heat Pump Controls Compressor Pr otection Compressor Over current The compressor has internal limbered motor protection. Compressor Overtemperature The compressor has an intern al protector to protect it against excessively high discharge gas temperatures. High Pressur e Switch The system is provided with a high p ressure switch mount- ed on the ...

  • Carrier 38AUQ - page 23

    23 Fig. 21 — Defrost Co ntrol Board (DFB) Location Fig. 22 — Defrost Control Board (DFB) Arrangement Reversing valve contr ol The DFB has two outputs for unit reversing valve control. Op- eration of the reversi ng valves is based on internal logic; this application does not use an “O” or “B” signal to determine re- versing valve positio ...

  • Carrier 38AUQ - page 24

    24 Defrost Thermostats These are temperature switches that monitor the surf ace tem- perature of the outdoor coil circuits. These switches are mount- ed on the liquid tube exiting the outdoor coil heating circuits. These switches close on temperature drop at 30°F (-1°C) and reset open on temperature rise at 80°F (27°C). Indoor Fan Off Delay The ...

  • Carrier 38AUQ - page 25

    25 Fig. 24 — 38AUQ*07 Exterior Fig. 25 — 38A UQ*07 Interior Fans Service V alves LOC HPS High Flow Access Ports Outdoor Coil Defrost Thermostat (DFT) ...

  • Carrier 38AUQ - page 26

    26 Fig. 26 — 38AUQ*08 Exterior Fig.27 — 38AUQ*08 Interior Fans Service V alves LOC HPS High Flow Access Ports Outdoor Coil Defrost Thermostat (DFT) ...

  • Carrier 38AUQ - page 27

    27 Fig. 28 — 38AUQ*12 Exterior Fig. 29 — 38A UQ*12 Interior Fans Service V alves LOC HPS High Flow Access Ports Outdoor Coil Defrost Thermostat (DFT) ...

  • Carrier 38AUQ - page 28

    28 COMFOR T ALER T DIAGNOSTIC MODULE The Comfort Alert Diagnostic Module (CADM) monitors and analyzes data from the Copeland Scroll ® three-phase compres- sor and the thermostat demand. The CADM also provides a 3-minute anti-recycle time delay to compressor cycling. The CADM detects causes for electrical and syste m related failures. Flashing LEDs ...

  • Carrier 38AUQ - page 29

    29 Table 14 — LED Status Codes Status LED St atus LED Description St atus L ED T roubleshootin g Information Green “POWER” Module has power Supply voltage is present at module terminals Red “TRIP” LED On Solid Thermostat demand signal Y is present, but the compressor is not running. 1. Compressor protector is open 2. Condensing unit power ...

  • Carrier 38AUQ - page 30

    30 Table 15 — CADM Troubleshooting Lubrication F AN MOT ORS have sealed bear ings. No provisions are made for lubrication. COMPRESSOR has its own oil supply . Loss of oil due to a leak in the system should be the only reason for adding oil after the system has been in operation. Out door Coil Maintenance and Cleaning Recommendation Routine cleani ...

  • Carrier 38AUQ - page 31

    31 Clean coil as follows: 1. T urn off unit power , tag disconnect. 2. Remove top panel screws on outdoor coil end of unit. 3. Remove coil corner post. T o hold top panel open, place coil corner post between top panel and center post. 4. Remove screws securing coil to compressor plate and compressor acce ss panel. 5. Use a water hose or other suita ...

  • Carrier 38AUQ - page 32

    32 TROUBLESHOOTING PROBLEM CAUSE REMEDY Compressor and Outdoor Fan Will Not St art. Power failure. Call power company . Fuse blown or circuit breaker tr ipped. Replace fuse or reset circuit breaker . Determine root cause. Defective thermostat, contactor , transforme r , control relay , or capa citor . Replace component. Insufficient line voltage. D ...

  • Carrier 38AUQ - page 33

    33 APPENDIX A AIR CONDITIONER AND HEA T PUMP WITH PURON ® — QUICK REFERENCE GUIDE •P u r o n ® (R-410A) refrigerant operates at 50 percent to 70 percent higher pressures than R-22. Be sure that servicing equipment and re placement components are designed to operate with Puron ® . •P u r o n ® refrigerant cylinders are rose colored. • Re ...

  • Carrier 38AUQ - page 34

    Copyright 2009 Ca rrier Corp • 7310 W . Morris S t. • Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 09/09 Catalog No: 38AUQ-01SI Manufacturer reserves the right to change, at any time, spec ifica tions and designs without notice and without obligations. Replaces: New 34 APPENDIX C MOTORMASTER SENSOR LOCA TIONS Fig. 31 Motor master Sens ...

  • Carrier 38AUQ - page 35

    CL-1 III. ST ART UP ST ART -UP CHECKLIST I. PRELIMINAR Y INFORMA TION OUTDOOR: MODEL NO. SERIAL NO. INDOOR: AIR HANDLER MANUF ACTURER MODEL NO. SERIAL NO. ADDITIONAL ACCESSORIES II. PRE-ST ART -UP OUTDOOR UNIT IS THERE ANY SHIPPING DAMAGE? (Y/N) IF SO, WHERE: WILL THIS DAMAGE PREVENT UNIT ST AR T -UP? (Y/N) CHECK POWER SUPPL Y . DOES IT AGREE WIT H ...

  • Carrier 38AUQ - page 36

    Copyright 2009 Carr ier Corp • 7310 W . Morris S t. • Indianapolis, IN 46231 Printed in U.S.A. E dition Date: 1 1 / 09 Catalog No: 38AUQ-01SI Manufacturer reserves the right to change, at any time, spec ifications and designs without notice and without obligations. Pg CL -2 Replac es: New - - - - - - - - - - - - - - - - - - - - - - - - - - - - ...

Produzent Carrier Kategorie Heat Pump

Dokumente, die wir vom Produzenten des Geräts Carrier 38AUQ erhalten, können wir in mehrere Gruppen teilen. Unteranderem in:
- technische Zeichnungen Carrier
- Bedienungsanleitungen 38AUQ
- Produktkarten Carrier
- Informationsbroschüren
- oder Energieetiketten Carrier 38AUQ
Jede von ihnen ist wichtig, jedoch finden wir die wichtigsten Informationen für den Nutzer des Geräts in der Bedienungsanleitung Carrier 38AUQ.

Die Dokumentengruppe, die als Bedienungsanleitungen bezeichnet wird, wird ebenfalls in detaillierte Arten geteilt, solche wie: Montageanleitungen Carrier 38AUQ, Wartungsanleitungen, Kurzanleitungen oder Benutzeranleitungen Carrier 38AUQ. Abhängig vom Bedarf, sollten Sie das Dokument finden, das Sie brauchen. In unserem Service können Sie sich die populärste Bedienungsanleitung des Produkts Carrier 38AUQ ansehen.

Ähnliche Bedienungsanleitungen

Die komplette Bedienungsanleitung des Geräts Carrier 38AUQ, wie sollte sie aussehen?
Die Bedienungsanleitung, auch bezeichnet als Benutzerhandbuch, oder einfach nur „Anleitung”, ist ein technisches Dokument, das dem Benutzer bei der Nutzung von Carrier 38AUQ hilfreich sein soll. Die Bedienungsanleitungen werden in der Regel von technischen Schriftstellern geschrieben, aber in einer Sprache, die für alle Nutzer von Carrier 38AUQ verständlich ist.

Eine gänzliche Bedienungsanleitung von Carrier sollte einige Grundelemente enthalten. Ein Teil von ihnen ist nicht so wichtig, wie z.B.: die Titelseite oder Autorenseiten. Die restlichen von ihnen jedoch, sollten Informationen liefern, die für den Nutzer von enormer Wichtigkeit sind.

1. Einführung und Hinweise, wie man sich in einer Bedienungsanleitung von Carrier 38AUQ bewegt - Am Anfang jeder Bedienungsanleitung sollten wir Hinweise bezüglich der Nutzungsart eines bestimmten Ratgebers finden. In ihr sollten sich Informationen über die Lokalisierung des Inhaltsverzeichnisses von Carrier 38AUQ befinden, FAQ oder über oft auftretende Probleme – also Stellen, die von den Benutzern in jeder Bedienungsanleitung am meisten gesucht werden
2. Inhaltsverzeichnis - Index aller Ratschläge bezüglich Carrier 38AUQ, die wir im aktuellen Dokument finden
3. Ratschläge zur Nutzung der Grundfunktionen des Geräts Carrier 38AUQ - die uns die ersten Schritte während der Nutzung von Carrier 38AUQ erleichtern sollten
4. Troubleshooting - geordneter Tätigkeitslauf, der uns bei der Diagnose und als nächstes bei der Lösung wichtiger Probleme mit Carrier 38AUQ hilft
5. FAQ - häufig gestellte Fragen
6. Kontaktdaten Informationen darüber, wo man Kontakt zum Produzenten / Service von Carrier 38AUQ im bestimmten Land suchen kann, wenn es nicht gelingt, das Problem selbst zu lösen.

Haben Sie eine Frage bezüglich Carrier 38AUQ?

Nutzen Sie das untere Formular

Wenn Sie mit Hilfe der gefundenen Bedienungsanleitung Ihr Problem mit Carrier 38AUQ nicht gelöst haben, stellen Sie eine Frage, indem Sie das untere Formular nutzen. Wenn einer der Nutzer ein ähnliches Problem mit Carrier 38AUQ hatte, ist es möglich, dass er mit Ihnen die Lösung teilen möchte.

Text vom Bild übertragen

Kommentare (0)