    Building Air-Conditioners Control System Model : LMAP03U Contents Safety precautions ····················································1,2 1 .Parts Include ····························································3 2 .Specifications ...

  • Mitsumi electronic LMAP03U - page 2

    ...

  • Mitsumi electronic LMAP03U - page 3

    1 Safety Precautions • Before instralling this unit,make sure you read all the “ Safety Precautions ” . • This manual describes the installation of LM ADAPTER and wiring to the outdoor unit. • Please read the installation manual of air-conditioning units with regards to the installation method of air-conditioning units. • The “ Safety ...

  • Mitsumi electronic LMAP03U - page 4

    2 CAUTION Do not install the unit where combustible gas may leak. If the gas leaks and accumulates around the unit, an explosion may result. Do not use in any special environment. Using in any place exposed to oil(including machine oil), steam and sulfuric gas may deteriorate the performances significantly or given damage to the component parts. Wh ...

  • Mitsumi electronic LMAP03U - page 5

    3 1. Parts Include 2. Specifications Verify that the following parts are appended to the product. 2-2 Environment Specifications 2-1 External View Name Shape Quantity Main Unit Binding band 1 3 Installation manual 1 · The external interface file (XIF) is necessary for the product. Upon verifying the 16-digit program ID (PID) which is bonded on the ...

  • Mitsumi electronic LMAP03U - page 6

    4 2-3 Connected Air Conditioning Equipment 2-4 L ON W ORKS ® Network Specifications * The proper communication is not obtainable when communication intervals exceed its performance, assure sufficeint intervals. * ACK Service is recommended for the network service. * Detailed specifications for the L ON W ORKS ® network can be found in “ FTT-10A ...

  • Mitsumi electronic LMAP03U - page 7

    3. Installation <Notes> Prepare the following prior to installing the unit. Read and understand the contents of Chapter 1 “ Safety Precautions ” before performing the installation. 3-1 Locally Procured Parts 5 Contents P ower wire and ground wire M-NET transmission wire Screw T o install the main body , prepare f our M4 screws which are s ...

  • Mitsumi electronic LMAP03U - page 8

    6 3-2 Installation Method • LM ADAPTER is not waterproof type. • LM ADAPTER shall be installed in a control panel box (steel : thickness 1 mm (3/64 in) or more). Please prepare the control panel box in consideration with installation space as shown in the Fig. (Install in an area capable of withstanding a 3.4 kg (7 1/2 lb) load.) The unit shall ...

  • Mitsumi electronic LMAP03U - page 9

    7 3-3 Wiring Methods Use wire clamps provided to secure the wires and prevent external force from being conveyed by the wire to the wire connections. * External force could cause deformation or damage to the terminal blocks. Use a small screwdriver to connect diameter 0.2 to 2.5 mm 2 (AWG24 to 12) cable for terminal block (TB21) on the unit. Tighte ...

  • Mitsumi electronic LMAP03U - page 10

    8 P .B. L.B. TB1 PE L1 L2 Main Power Switch 3A Unit Body Unit Body CN31 3 1 3 AC250V 2A T ZNR2 F 1 T2 CN33 DSA1 ZNR1 Unit Body 7 3 1 5 CN71 SWL (Service Switch) (Service LEDL LED) 1 3 4 3 2 1 5 6 CN45 T1 CN65 2 1 CN21 3 1 CN32 1 2 3 4 CNL12 CN605 5 4 3 2 1 LED402 (5VM) LED502 (3150RST) 6 4 3 2 1 M-NET Power Supply CN40 (WDT) LED009 LED201 CN41 (180 ...

  • Mitsumi electronic LMAP03U - page 11

    9 Note: Function switch setting of LM ADAPTER is different according to the management item of the equipment connected with L ON W ORKS ® . Carefully set the system. SW1-1 ON OFF Function s witch of local prohibit local prohibit eff ective local prohibit inv alidity ON OFF LOSSNA Y is operated from L ON W ORKS ® LOSSNA Y interlocks with the indoo ...

  • Mitsumi electronic LMAP03U - page 12

    10 4. System Settings <Notes> This chapter only describes the system settings of this product. For the installation work and electrical work, refer to the last chapter “ 3. Installation ” . Read and understand the contents of Chapter 1 “ Safety Precautions ” before performing the installation. 4-1 If not used together with system cont ...

  • Mitsumi electronic LMAP03U - page 13

    11 4-2 If used together with system controller . SW1-2 [ON] SW2-1 [ON] Centralized controller (system controller) M-NET transmission line (Centralized control line) M-NET address 201 to 250 [factory setting 247] (* Setting of position 100 not required.) (Note:1) When connecting LOSSNA Y , register the sequence must be registered fr om the shared sy ...

  • Mitsumi electronic LMAP03U - page 14

    12 4-3 Initialization Settings of L ON W ORKS ® Network (1) System Specifications • Up to 64 FTT-10/FTT-10A transceivers are allowed per network segment. • LPT-10 transceivers may be used on network segments with FTT-10/FTT-10A transceivers, but are subject to additional constraints, particularly on distance. See the LPT-10 Use's Guide fo ...

  • Mitsumi electronic LMAP03U - page 15

    13 5. Confirming Operation 5-1 Flow of Onsite Adjustments …… …… …… T est run by unit and local remote controller Ref er to 5-4 (1) T est run by LM AD APTER Ref er to 5-4 (2) T est run from the L ON W ORKS ® network Refer to 5-4 (3) There are the f ollowing two methods to perf or m a test run from the L ON W ORKS ® networ k. T est run ...

  • Mitsumi electronic LMAP03U - page 16

    14 5-4 T est Run P erform the test r un according to the test procedure of the test run check list. (1) T est run of units by local remote controller * Confirm that all units are r unning nor mally . (2) T est-operation of the indoor unit from LM AD APTER T ur n on SW1-9 of LM ADAPTER. Finally turn OFF SW1-9, and verify that all indoor units are st ...

  • Mitsumi electronic LMAP03U - page 17

    15 6. T roubleshooting (WDT) (5VM) LED009 Item ON Normal state Contents to check Check the Main P ower Switch to the LM AD APTER is not tur ned off, an y connectors (CN605, CN65, CN32, CN33, CN31, CN71) are disconnected and f or a blo wn fuse (F). LED402 ON Check the Main P ower Switch to the LM AD APTER is not tur ned off, an y connectors (CN405, ...

  • Mitsumi electronic LMAP03U - page 18

    16 (1)The LM AD APTER is not completely initialized. (2)Setting on M-NET side is not properly completed. (3)If system controller is used together LM AD APTER is not registered to system controller . T ur n OFF all SW2. After verifying that LED002 is OFF , test the operation again. V er ify that the test operation of the air conditioner is properly ...

  • Mitsumi electronic LMAP03U - page 19

    17 (1)The LM AD APTER is not completely initialized. (2)Setting on M-NET side is not properly completed. (3)If system controller is used together LM AD APTER is not registered to system controller . (4)The independent/combined LOSSNA Y of LM AD APTER is not set. (5)L ON W ORKS ® network transmission wire is not properly connected. (6)The terminati ...

  • Mitsumi electronic LMAP03U - page 20

    18 6600 6601 6607 • If it has been confirmed that a unit with the same M-NET address is transmitting. • When discrimination of the polarity of the M-NET transmission wire. • If there is no response (ACK) from the recipient after a transmission. • If there are two or more units with the same M-NET address at the unit and controller . • Int ...

  • Mitsumi electronic LMAP03U - page 21

    19 Test run check sheet ON OFF ON OFF Operation from L ON W ORKS ® network Confirmation of operating status Error Operation mode Set temperature ON OFF Operation mode Set temperature temperature Intake 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 ...

  • Mitsumi electronic LMAP03U - page 22

    ...

  • Mitsumi electronic LMAP03U - page 23

    ...

  • Mitsumi electronic LMAP03U - page 24

    WT03760X01 HEAD OFFICE MITSUBISHI DENKI BLDG.MARUNOUCHI TOKYO 100-0005 TELEX J24532 CABLE MELCO TOKYO NO TE: This equipment has been tested and f ound to comply with the limits f or a Class B digital de vice, pursuant to P ar t 15 of the FCC Rules. These limits are designed to provide resonable protection against harmful inter- f erence in a reside ...

Produzent Mitsumi electronic Kategorie Network Card

Dokumente, die wir vom Produzenten des Geräts Mitsumi electronic LMAP03U erhalten, können wir in mehrere Gruppen teilen. Unteranderem in:
- technische Zeichnungen Mitsumi electronic
- Bedienungsanleitungen LMAP03U
- Produktkarten Mitsumi electronic
- Informationsbroschüren
- oder Energieetiketten Mitsumi electronic LMAP03U
Jede von ihnen ist wichtig, jedoch finden wir die wichtigsten Informationen für den Nutzer des Geräts in der Bedienungsanleitung Mitsumi electronic LMAP03U.

Die Dokumentengruppe, die als Bedienungsanleitungen bezeichnet wird, wird ebenfalls in detaillierte Arten geteilt, solche wie: Montageanleitungen Mitsumi electronic LMAP03U, Wartungsanleitungen, Kurzanleitungen oder Benutzeranleitungen Mitsumi electronic LMAP03U. Abhängig vom Bedarf, sollten Sie das Dokument finden, das Sie brauchen. In unserem Service können Sie sich die populärste Bedienungsanleitung des Produkts Mitsumi electronic LMAP03U ansehen.

Ähnliche Bedienungsanleitungen

Die komplette Bedienungsanleitung des Geräts Mitsumi electronic LMAP03U, wie sollte sie aussehen?
Die Bedienungsanleitung, auch bezeichnet als Benutzerhandbuch, oder einfach nur „Anleitung”, ist ein technisches Dokument, das dem Benutzer bei der Nutzung von Mitsumi electronic LMAP03U hilfreich sein soll. Die Bedienungsanleitungen werden in der Regel von technischen Schriftstellern geschrieben, aber in einer Sprache, die für alle Nutzer von Mitsumi electronic LMAP03U verständlich ist.

Eine gänzliche Bedienungsanleitung von Mitsumi electronic sollte einige Grundelemente enthalten. Ein Teil von ihnen ist nicht so wichtig, wie z.B.: die Titelseite oder Autorenseiten. Die restlichen von ihnen jedoch, sollten Informationen liefern, die für den Nutzer von enormer Wichtigkeit sind.

1. Einführung und Hinweise, wie man sich in einer Bedienungsanleitung von Mitsumi electronic LMAP03U bewegt - Am Anfang jeder Bedienungsanleitung sollten wir Hinweise bezüglich der Nutzungsart eines bestimmten Ratgebers finden. In ihr sollten sich Informationen über die Lokalisierung des Inhaltsverzeichnisses von Mitsumi electronic LMAP03U befinden, FAQ oder über oft auftretende Probleme – also Stellen, die von den Benutzern in jeder Bedienungsanleitung am meisten gesucht werden
2. Inhaltsverzeichnis - Index aller Ratschläge bezüglich Mitsumi electronic LMAP03U, die wir im aktuellen Dokument finden
3. Ratschläge zur Nutzung der Grundfunktionen des Geräts Mitsumi electronic LMAP03U - die uns die ersten Schritte während der Nutzung von Mitsumi electronic LMAP03U erleichtern sollten
4. Troubleshooting - geordneter Tätigkeitslauf, der uns bei der Diagnose und als nächstes bei der Lösung wichtiger Probleme mit Mitsumi electronic LMAP03U hilft
5. FAQ - häufig gestellte Fragen
6. Kontaktdaten Informationen darüber, wo man Kontakt zum Produzenten / Service von Mitsumi electronic LMAP03U im bestimmten Land suchen kann, wenn es nicht gelingt, das Problem selbst zu lösen.

Haben Sie eine Frage bezüglich Mitsumi electronic LMAP03U?

Nutzen Sie das untere Formular

Wenn Sie mit Hilfe der gefundenen Bedienungsanleitung Ihr Problem mit Mitsumi electronic LMAP03U nicht gelöst haben, stellen Sie eine Frage, indem Sie das untere Formular nutzen. Wenn einer der Nutzer ein ähnliches Problem mit Mitsumi electronic LMAP03U hatte, ist es möglich, dass er mit Ihnen die Lösung teilen möchte.

Text vom Bild übertragen

Kommentare (0)