Manual de instrucciones Goodman Mfg GSX130421B

44 de páginas 0.7 mb
Descargar

Pasar a la página of 44

Summary
  • Goodman Mfg GSX130421B - page 1

    SS-GSX13 www .goodmanmfg.com 2/14 Supersedes 11/13 GSX1 3 S plit S yStem A ir C onditioner 13 Seer / 1½ t o 5 t onS C oolinG C Ap ACity : 1 8,000 - 60,000 BtU/ h Standard Featur es • R-410Achlorine-freer efrigerant • Energ y-efcientcompressor • Factor y-installedlterdrier • Coppertube/aluminumnc ...

  • Goodman Mfg GSX130421B - page 2

    P roduct S Pecifica tionS 2 www .goodmanmfg.com SS-GSX13 n omenClA tUre Brand Engineering * G Goodman ® Brand or Minor Revision Amana ® Distinctions ® Brand Engineering * Major Revision Product Category Electrical S Split System 1 208-230 V , 1 Phase, 60 Hz 2 220/240 V , 1 Phase, 50 Hz Unit T ype 3 208-230 V , 3 Phase, 60 Hz C Condenser R-22 4 4 ...

  • Goodman Mfg GSX130421B - page 3

    P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 3 S peCifiCA tionS GSX13 0181E* GSX13 0241D* GSX13 0301B* GSX13 0361C* GSX13 0361E* GSX13 0421B* GSX13 0481B* GSX13 0601B* GSX13 0611A* Cap acities Nominal Cooling (BTU/h) 18,000 24,000 30,000 36,000 36,000 42,000 48,000 60,000 60,000 SEER / EER 13 / 11 13 / 11 13 / 11 13 / 11 13 / 11 13 / 11 1 ...

  • Goodman Mfg GSX130421B - page 4

    P roduct S Pecifica tionS 4 www .goodmanmfg.com SS-GSX13 e Xp Anded C oolinG d A tA — GSX1 301 81e* / CApf1 824B6dB Outdoor Ambient Temper a ture 65ºF 75ºF 85ºF 95ºF 105ºF 115ºF Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 70 525 MBh 15.6 16.2 17.7 - 15.3 15.8 17.3 ...

  • Goodman Mfg GSX130421B - page 5

    P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 5 e Xp Anded C oolinG d A tA — GSX1 301 81e* / CApf1 824B6dB ( Cont .) Outdoor Ambient Temper a ture 65ºF 75ºF 85ºF 95ºF 105ºF 115ºF Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 80 525 MBh 16.2 16.5 17.7 18.9 1 ...

  • Goodman Mfg GSX130421B - page 6

    P roduct S Pecifica tionS 6 www .goodmanmfg.com SS-GSX13 e Xp Anded C oolinG d A tA — GSX1 302 4 1d* / CA*f1 82 4*6d* Outdoor Ambient Temper a ture 65ºF 75ºF 85ºF 95ºF 105ºF 115ºF Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 70 700 MBh 20.2 20.9 22.9 - 19.7 20.4 22 ...

  • Goodman Mfg GSX130421B - page 7

    P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 7 e Xp Anded C oolinG d A tA — GSX1 302 4 1d* / CA*f1 82 4*6d* ( Cont .) Outdoor Ambient Temper a ture 65ºF 75ºF 85ºF 95ºF 105ºF 115ºF Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 80 700 MBh 20.9 21.4 22.8 24.4 ...

  • Goodman Mfg GSX130421B - page 8

    P roduct S Pecifica tionS 8 www .goodmanmfg.com SS-GSX13 e Xp Anded C oolinG d A tA — GSX1 30 301B* / CA *f30 30*6d* Outdoor Ambient Temper a ture 65ºF 75ºF 85ºF 95ºF 105ºF 115ºF Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 70 945 MBh 26.2 27.2 29.8 - 25.6 26.6 29. ...

  • Goodman Mfg GSX130421B - page 9

    P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 9 e Xp Anded C oolinG d A tA — GSX1 30 301B* / CA *f30 30*6d* ( Cont .) Outdoor Ambient Temper a ture 65ºF 75ºF 85ºF 95ºF 105ºF 115ºF Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 80 945 MBh 27.2 27.8 29.6 31.7 ...

  • Goodman Mfg GSX130421B - page 10

    P roduct S Pecifica tionS 10 www .goodmanmfg.com SS-GSX13 Outdoor Ambient Temper a ture 65ºF 75ºF 85ºF 95ºF 105ºF 115ºF Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 70 1350 MBh 32.8 34.0 37.2 - 32.0 33.2 36.4 - 31.3 32.4 35.5 - 30.5 31.6 34.6 - 29.0 30.0 32.9 - 26.8 ...

  • Goodman Mfg GSX130421B - page 11

    P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 11 Outdoor Ambient Temper a ture 65ºF 75ºF 85ºF 95ºF 105ºF 115ºF Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 80 1350 MBh 33.93 34.67 37.04 39.59 33.14 33.86 36.18 38.67 32.35 33.06 35.32 37.75 31.56 32.25 34.46 ...

  • Goodman Mfg GSX130421B - page 12

    P roduct S Pecifica tionS 12 www .goodmanmfg.com SS-GSX13 e Xp Anded C oolinG d A tA — GSX1 30 36 1e* / CA *f3 6 3 6*6d* Outdoor Ambient Temper a ture 65 75 85 95 105 115 Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 70 1350 MBh 32.9 34.1 37.4 - 32.2 33.3 36.5 - 31.4 32.5 ...

  • Goodman Mfg GSX130421B - page 13

    P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 13 e Xp Anded C oolinG d A tA — GSX1 30 36 1e* / CA *f3 6 3 6*6d* ( Cont .)    65ºF 75ºF 85ºF 95ºF 105ºF 115ºF  ? ...

  • Goodman Mfg GSX130421B - page 14

    P roduct S Pecifica tionS 14 www .goodmanmfg.com SS-GSX13 e Xp Anded C oolinG d A tA — GSX1 30421B* / CA *f3 642*6B* Outdoor Ambient Temper a ture 65ºF 75ºF 85ºF 95ºF 105ºF 115ºF Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 70 1225 MBh 36.0 37.3 40.9 - 35.2 36.4 39 ...

  • Goodman Mfg GSX130421B - page 15

    P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 15 e Xp Anded C oolinG d A tA — GSX1 30421B* / CA *f3 642*6B* ( Cont .) Outdoor Ambient Temper a ture 65ºF 75ºF 85ºF 95ºF 105ºF 115ºF Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 80 1225 MBh 37.3 38.1 40.7 43.5 ...

  • Goodman Mfg GSX130421B - page 16

    P roduct S Pecifica tionS 16 www .goodmanmfg.com SS-GSX13 e Xp Anded C oolinG d A tA — GSX1 30481B* / CA *f4860*6B* Outdoor Ambient Temper a ture 65ºF 75ºF 85ºF 95ºF 105ºF 115ºF Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 70 1400 MBh 40.4 41.9 45.9 - 39.5 40.9 44. ...

  • Goodman Mfg GSX130421B - page 17

    P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 17 e Xp Anded C oolinG d A tA — GSX1 30481B* / CA *f4860*6B* ( Cont .) Outdoor Ambient Temper a ture 65ºF 75ºF 85ºF 95ºF 105ºF 115ºF Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 80 1400 MBh 41.8 42.7 45.6 48.8 ...

  • Goodman Mfg GSX130421B - page 18

    P roduct S Pecifica tionS 18 www .goodmanmfg.com SS-GSX13 e Xp Anded C oolinG d A tA — GSX1 30601B* / CA *f496 1*6A * Outdoor Ambient Temper a ture 65ºF 75ºF 85ºF 95ºF 105ºF 115ºF Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 70 1500 MBh 50.1 51.9 56.8 - 48.9 50.7 5 ...

  • Goodman Mfg GSX130421B - page 19

    P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 19 e Xp Anded C oolinG d A tA — GSX1 30601B* / CA *f496 1*6A* ( Cont .) Outdoor Ambient Temper a ture 65ºF 75ºF 85ºF 95ºF 105ºF 115ºF Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 80 1500 MBh 51.8 52.9 56.6 60.5 ...

  • Goodman Mfg GSX130421B - page 20

    P roduct S Pecifica tionS 20 www .goodmanmfg.com SS-GSX13 e Xp Anded C oolinG d A tA — GSX1 306 1 1*/CA *f496 1*6d*+eep Outdoor Ambient Temper a ture 65 75 85 95 105 115 Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 70 1500 MBh 53.8 55.7 61.0 - 52.5 54.4 59.6 - 51.3 53.1 ...

  • Goodman Mfg GSX130421B - page 21

    P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 21 e Xp Anded C oolinG d A tA — GSX1 306 1 1*/CA *f496 1*6d*+eep ( Cont .) Outdoor Ambient Temper a ture 65 75 85 95 105 115 Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 80 1500 MBh 55.6 56.9 60.7 64.9 54.3 55.5 59.3 ...

  • Goodman Mfg GSX130421B - page 22

    P roduct S Pecifica tionS 22 www .goodmanmfg.com SS-GSX13 Ahri r A tinGS See Notes on P age 38. Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0181E* ACNF18XX16D* 16,800 12,800 13.00 10.80 600 5039733 ACNF24XX16D* 17,000 13,000 13.00 10.80 600 5039734 ARPT18B14A* 17,400 13,30 ...

  • Goodman Mfg GSX130421B - page 23

    P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 23 Ahri r A tinGS ( Cont .) See Notes on P age 38. Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0181E* CAPT3131*4A* A*EH800603B*A* 18,000 13,700 14.00 11.50 650 6944836 CAPT3131*4A* AMEH960403B XA* 18,000 13,700 14.00 1 ...

  • Goodman Mfg GSX130421B - page 24

    P roduct S Pecifica tionS 24 www .goodmanmfg.com SS-GSX13 Ahri r A tinGS ( Cont .) See Notes on P age 38. Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0241D* CA*F1824*6D* A*VC950453BXB* 23,000 16,900 14.00 11.60 800 6497537 CA*F1824*6D* G*VC950453BXB* 23,000 16,900 14.00 11 ...

  • Goodman Mfg GSX130421B - page 25

    P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 25 Ahri r A tinGS ( Cont .) See Notes on P age 38. Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0301B* ACNF30XX16D* 27,600 20,800 13.00 11.00 890 4689680 ARPT30B14A* 27,000 20,400 13.00 11.00 900 5383473 ARUF30B14A* 27, ...

  • Goodman Mfg GSX130421B - page 26

    P roduct S Pecifica tionS 26 www .goodmanmfg.com SS-GSX13 Ahri r A tinGS ( Cont .) See Notes on P age 38. Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0301B* CA*F3131*6D*+MBVC1200**-1A* 28,400 21,400 14.00 11.50 950 4385559 CA*F3636*6D*+EEP 28,400 21,400 13.00 11.00 1,000 5 ...

  • Goodman Mfg GSX130421B - page 27

    P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 27 Ahri r A tinGS ( Cont .) See Notes on P age 38. Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0301B* CAPT3743*4A*+MBVC1600**-1A* 28,200 21,200 14.00 11.50 1,000 5611307 CHPF2430B6C* GME950403B XA* 28,400 21,400 14.00 ...

  • Goodman Mfg GSX130421B - page 28

    P roduct S Pecifica tionS 28 www .goodmanmfg.com SS-GSX13 Ahri r A tinGS ( Cont .) See Notes on P age 38. Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0361E* CA*F3642*6D* G*VC950905CXB* 34,000 26,400 14.00 11.50 1,165 5696692 CA*F3642*6D* A*VC950714CXB* 34,000 26,400 14.00 ...

  • Goodman Mfg GSX130421B - page 29

    P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 29 Ahri r A tinGS ( Cont .) See Notes on P age 38. Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0361E* CAPT3743*4A* A*VM961005DXB* 34,000 26,400 13.50 11.50 1,170 6494238 CAPT3743*4A* GME950805CXA* 33,400 26,000 13.50 1 ...

  • Goodman Mfg GSX130421B - page 30

    P roduct S Pecifica tionS 30 www .goodmanmfg.com SS-GSX13 Ahri r A tinGS ( Cont .) See Notes on P age 38. Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0421B* CA*F3642*6D*+EEP 40,000 30,600 13.00 11.00 1,400 4946292 CA*F3642*6D*+EEP+TXV 40,000 30,600 13.00 11.00 1,400 556191 ...

  • Goodman Mfg GSX130421B - page 31

    P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 31 Ahri r A tinGS ( Cont .) See Notes on P age 38. Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0421B* CHPF3642D6C* G*VC950905CXB* 40,000 30,600 13.50 11.30 1,400 5621024 CHPF3642D6C*+EEP 40,000 30,600 13.00 11.00 1,400 ...

  • Goodman Mfg GSX130421B - page 32

    P roduct S Pecifica tionS 32 www .goodmanmfg.com SS-GSX13 Ahri r A tinGS ( Cont .) See Notes on P age 38. Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0481B* CA*F4860*6D*+TXV A*VM960604CXB* 46,000 35,200 14.00 11.30 1,550 5621064 CA*F4860*6D*+TXV A*VM960805CXB* 46,000 35,20 ...

  • Goodman Mfg GSX130421B - page 33

    P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 33 Ahri r A tinGS ( Cont .) See Notes on P age 38. Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0481B* CHPF4860D6D*+TXV A*EH801005C*A* 46,000 35,200 13.50 11.30 1,570 6944925 CHPF4860D6D*+TXV AMEH960805CXA* 45,500 34,80 ...

  • Goodman Mfg GSX130421B - page 34

    P roduct S Pecifica tionS 34 www .goodmanmfg.com SS-GSX13 Ahri r A tinGS ( Cont .) See Notes on P age 38. Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0601B* CAPT4961*4A* A*VC950915D XB* 55,000 39,000 13.00 11.00 1,660 5621088 CAPT4961*4A* G*VM961005DXB* 54,500 38,500 13.00 ...

  • Goodman Mfg GSX130421B - page 35

    P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 35 Ahri r A tinGS ( Cont .) Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0611A* ARPT48D14A* 54,500 37,400 13.00 11.00 1,500 5586528 ARPT60D14A* 55,000 37,600 13.00 11.00 1,500 5586693 ARUF48D14A* 54,500 37,400 13.00 11. ...

  • Goodman Mfg GSX130421B - page 36

    P roduct S Pecifica tionS 36 www .goodmanmfg.com SS-GSX13 Ahri r A tinGS ( Cont .) See Notes on P age 38. Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0611A* CA*F4961*6D*+TXV G*VC80805C*B* 56,500 38,500 14.00 11.50 1,520 5586612 CA*F4961*6D*+TXV G*VC81005C*B* 56,500 38,500 ...

  • Goodman Mfg GSX130421B - page 37

    P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 37 Ahri r A tinGS ( Cont .) See Notes on P age 38. Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0611A* CAPT4961*4A* G*VC950905CXB* 56,500 38,500 13.50 11.00 1,460 5621112 CAPT4961*4A* A*VC950905D XB* 56,500 38,500 14.00 ...

  • Goodman Mfg GSX130421B - page 38

    P roduct S Pecifica tionS 38 www .goodmanmfg.com SS-GSX13 Ahri r A tinGS ( Cont .) Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0611A* CSCF4860N6D*+TXV GME951005DXA* 55,000 37,600 13.50 11.00 1,500 5589957 CSCF4860N6D*+TXV A*VC950905CXB* 55,000 37,600 13.50 11.00 1,475 5621 ...

  • Goodman Mfg GSX130421B - page 39

    P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 39 d imenSionS H W D Model Dimensions W” D” H” GSX130181E* 23 23 25¾ GSX130241D* 23 23 25¾ GSX130301B* 26 26 27½ GSX130361C* 29 29 28¾ GSX130361E* 26 26 27½ GSX130421B* 29 29 36¼ GSX130481B* 29 29 36¼ GSX130601B* 29 29 40 GSX130611A* 35½ 35½ 38¼ ...

  • Goodman Mfg GSX130421B - page 40

    P roduct S Pecifica tionS 40 www .goodmanmfg.com SS-GSX13 W irinG d iAGrAm — GSX1 3 01 81e USE N.E.C. CLASS 2 WIRE COMP ALTERNA TE DOUBLE POLE CONTACTO R ONL Y IO T1 M A I N R A U X 5 S SR SA 2 1 RCCF SC T2 C L1 L2 (IF USED) C H C F M A I N A U X C C 0140R00258-B BL Y C LVJB COL OR C ODE BK ------- -------- BLACK BL --------- ------ BLUE BL/PK -- ...

  • Goodman Mfg GSX130421B - page 41

    P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 41 W irinG d iAGrAm — GSX1 3 0(3 0-60)1B/C/e*     ref er to the wiring diagram or the unit for the most up-t o-date wiring. ⚠ W ARNING High V oltage:  ? ...

  • Goodman Mfg GSX130421B - page 42

    P roduct S Pecifica tionS 42 www .goodmanmfg.com SS-GSX13     ref er to the wiring diagram or the unit for the most up-t o-date wiring. ⚠ W ARNING High V oltage:      ? ...

  • Goodman Mfg GSX130421B - page 43

    P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 43 W irinG d iAGrAm — GSX1 3 06 1 1*     ref er to the wiring diagram or the unit for the most up-t o-date wiring. ⚠ W ARNING High V oltage:   ? ...

  • Goodman Mfg GSX130421B - page 44

    P roduct S Pecifica tionS 44 www .goodmanmfg.com SS-GSX13 Goodman Manufacturing Company , L.P ., reserves the right to discontinue, or change at any time, specica tions or designs without notice or without incurring obligations. © 2014 • Goodman Manufacturing Company , L.P . • Houston, T exas • Printed in the USA. A CCeSSorieS Model De sc ...

Fabricante Goodman Mfg Categoría Air Conditioner

Los documentos del dispositivo Goodman Mfg GSX130421B que obtenemos del fabricante se pueden dividir en varios grupos. Entre ellos están::
- dibujos técnicos Goodman Mfg
- manuales de instrucciones GSX130421B
- hojas de producto Goodman Mfg
- folletos informativos
- o etiquetas energéticas Goodman Mfg GSX130421B
Todos son importantes, pero lo más importante desde el punto de vista del usuario de un dispositivo lo encontraremos en el manual de instrucciones Goodman Mfg GSX130421B.

Un conjunto de documentos determinado como manual de instrucciones se divide también en tipos más detallados, tales como: instrucciones de montaje Goodman Mfg GSX130421B, instrucciones de servicio, instrucciones cortas o instrucciones de usuario Goodman Mfg GSX130421B. Dependiendo de la situación debes buscar el documento que necesitas. En nuestra página puedes consultar el manual de instrucciones más popular del producto Goodman Mfg GSX130421B.

El manual de instrucciones del dispositivo Goodman Mfg GSX130421B, ¿cómo debería ser?
El manual de instrucciones, también determinado como el manual de usuario o simplemente instrucciones, es un documento técnico que tiene como objetivo ayudar a los usuarios a utilizar Goodman Mfg GSX130421B. Las instrucciones normalmente las realiza un escritor técnico pero en un lenguaje comprensible para todos los usuarios de Goodman Mfg GSX130421B.

El manual de instrucciones completo de Goodman Mfg debe contener unos elementos básicos. Una parte de ellos es menos importante, como por ejemplo: la portada / la página principal o las páginas de autor. Sin embargo, lo demás debe facilitarnos la información más importante desde el punto de vista del usuario.

1. Introducción y pistas sobre cómo orientarse con el manual Goodman Mfg GSX130421B - Al principio de cada manual se deben encontrar las indicaciones acerca de la manera de usar un manual de instrucciones. Debe contener información sobre dónde encontrar el índice Goodman Mfg GSX130421B, preguntas frecuentes o problemas más comunes – son los apartados más buscados por los usuarios de cada manual de instrucciones.
2. Índice - listados de todos los consejos acerca de Goodman Mfg GSX130421B que encontraremos en el documento
3. Consejos de uso de las funciones básicas del dispositivo Goodman Mfg GSX130421B - que deben facilitarnos los primeros pasos durante el uso de Goodman Mfg GSX130421B
4. Troubleshooting - una secuencia sistematizada de acciones que nos ayudará a diagnosticar los problemas más importantes con Goodman Mfg GSX130421B
5. FAQ - las preguntas frecuentes
6. Datos de contacto Información acerca de cómo encontrar los datos de contacto del fabricante / servicio de Goodman Mfg GSX130421B en cada país si no somos capaces de solucionar el problema por nuestra cuenta.

¿Tienes una pregunta acerca de Goodman Mfg GSX130421B?

Utiliza el formulario que se encuentra abajo

Si con la ayuda del manual de instrucciones encontrado no has podido solucionar tu problema con Goodman Mfg GSX130421B, haz una pregunta utilizando el formulario que se encuentra abajo. Si alguno de los usuarios ha tenido un problema parecido con Goodman Mfg GSX130421B probablemente compartirá una forma de solucionarlo.

Copia el texto de la imagen

Comentarios (0)