    TECHNICAL GUIDE SPLIT -SYSTEM HEA T PUMPS 14.5 SEER – R-410A MODELS: YHJF18 THRU 60 (1.5 THRU 5 NOMINAL TONS, 1 PHASE) Due to continuous prod uct improvemen t, specifications are subject to chan ge without notice. Vi si t us on the web at ww w .york.com Additional rating informa tion can be found at www .ahridirectory.org W ARRANTY S tandard 5-ye ...

  • York YHJF18 THRU 60 - page 2

    510667-YTG-B-0509 2 Johnson Controls Unitary Products All dimensions are in inche s. They are su bject to change with- out notice. Certified dimensions will be provi ded upon request. Physical and Electrica l Data MODEL YHJF18 S41S1 YHJF24 S41S1 YHJF30 S41S1 YHJF36 S41S1 YHJF42 S41S1 YHJF48 S41S1 YHJF60 S41S1 Unit Supply V oltage 208-230V , 1 ? ...

  • York YHJF18 THRU 60 - page 3

    510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 3 PROCEDURES: 1. Unit factory charge listed on the u nit nameplate includes re friger ant for the condenser, the smallest evaporator and 15 feet of interconnecting line tub ing. 2. V erify the TXV and additional charge required for specific evaporator coil in the system u sing the above table. 3. ...

  • York YHJF18 THRU 60 - page 4

    510667-YTG-B-0509 4 Johnson Controls Unitary Products — = Not applicable. COOLING CAP ACITY - With Air Handler Coils UNIT MODEL AIR HANDLER COIL MODEL 1 ST AGE COOLING MODEL W RA TED CFM NET MBH SEER EER TOT AL SENS. 14.5 SEER HP WITH MV - V ARIABLE SPEED YHJF18S41S1 MV12B 17 FC/MC35B – 600 18.0 13.0 15.00 12.50 MV12B 17 FC/MC43B – 600 18.0 1 ...

  • York YHJF18 THRU 60 - page 5

    510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 5 COOLING CAP ACITY - With High Efficiency Motor Furnaces UNIT MODEL FURNACE MODEL COIL MODEL 1 WS T A G E COOLING RA TED CFM Net MBH SEER EER TOT AL SENS. 14.5 SEER HP WITH V ARIABLE SPEED FURNACES 2 YHJF18S41S1 T*(8,L)X*A12 FC/MC/PC32A 14 – 590 18.0 13.0 15.00 12.50 Y*(8,L)C*A12 FC/MC/PC32A 1 ...

  • York YHJF18 THRU 60 - page 6

    510667-YTG-B-0509 6 Johnson Controls Unitary Products YHJF36S41S1 T*(8,L)X*A12 FC/MC/PC37A 14 – 1290 35.8 27.4 14.50 12.00 T*(8,L)X*B12 FC/MC/PC43B 17 – 1300 35.8 27.4 14.50 12.00 T*(8,L)X*C16 FC/MC/PC43C 21 – 1 175 35.4 26.4 15.00 12.50 T*(8,L)X*C20 FC/MC/PC43C 21 – 1250 36.0 27.4 15.00 12.50 T*9X*B12 FC/MC/PC43B 17 – 1270 35.8 27.4 14.5 ...

  • York YHJF18 THRU 60 - page 7

    510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 7 CP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heat ing output durin g a normal annual usage period for hea ting divided by th e total electric power input during the same period. — = Not Applicable. HEA TING PERFORMANCE - W ...

  • York YHJF18 THRU 60 - page 8

    510667-YTG-B-0509 8 Johnson Controls Unitary Products HEA TING CAP ACIT Y - With High Efficiency Motor Fu rnaces MODEL FURNACE MODEL COIL 1 MODEL ARI HEA TING 2 47  F1 7  FH S P F MBH COP KW MBH COP KW STD 14.5 SEER HP WITH V ARIABLE SPEED FUR NACES 3 YHJF18S41S1 T*(8,L)X*A12 FC/MC/PC32A 17. 9 3.84 1.37 10.8 2.54 1 .25 9.00 Y*(8,L)C*A12 F C/M ...

  • York YHJF18 THRU 60 - page 9

    510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 9 CP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heat ing output durin g a normal annual usage period for hea ting divided by th e total electric power input during the same period. — = Not Applicable. YHJF36S41S1 T*(8,L)X*A12 F ...

  • York YHJF18 THRU 60 - page 10

    510667-YTG-B-0509 10 Johnson Controls Unitary Products CP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heat ing output during a normal annual usage period for heating divided by the total electric power input during the same period. — = Not Applicable. ACCESSORIES Refer to Price Ma ...

  • York YHJF18 THRU 60 - page 11

    510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 11 SOUND LEVEL - TYPICAL OCT A VE BAND SPE CTRUM (without tone adjustment) * Rated in accordance with ARI 270-200 8 S tandards. TYPICAL INST ALLA TION TYPICAL FIELD WIRING Size T est Condition 63 125 250 500 1000 2000 4000 8000 dBA SQI RSS Sound Power Calibration 1091 402 82.8 85.4 85.9 85.3 88.1 ...

  • York YHJF18 THRU 60 - page 12

    510667-YTG-B-0509 12 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73- 87 F), sensible capacity incr eases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decr eases by 1060 BTUH per 1000 CFM per ...

  • York YHJF18 THRU 60 - page 13

    510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 13 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73-87 F), se nsible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decrease s by 1060 BTUH per 1000 CFM per d ...

  • York YHJF18 THRU 60 - page 14

    510667-YTG-B-0509 14 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73- 87 F), sensible capacity incr eases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decr eases by 1060 BTUH per 1000 CFM per ...

  • York YHJF18 THRU 60 - page 15

    510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 15 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73-87 F), se nsible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decrease s by 1060 BTUH per 1000 CFM per d ...

  • York YHJF18 THRU 60 - page 16

    510667-YTG-B-0509 16 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73- 87 F), sensible capacity incr eases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decr eases by 1060 BTUH per 1000 CFM per ...

  • York YHJF18 THRU 60 - page 17

    510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 17 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73-87 F), se nsible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decrease s by 1060 BTUH per 1000 CFM per d ...

  • York YHJF18 THRU 60 - page 18

    510667-YTG-B-0509 18 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73- 87 F), sensible capacity incr eases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decr eases by 1060 BTUH per 1000 CFM per ...

  • York YHJF18 THRU 60 - page 19

    510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 19 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73-87 F), se nsible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decrease s by 1060 BTUH per 1000 CFM per d ...

  • York YHJF18 THRU 60 - page 20

    510667-YTG-B-0509 20 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. HEA TING PE RFORMANCE DA T A CONDENSING UNIT MO DEL NO YHJF18S41S1 EV APORA TOR COIL MODEL NO AHX30 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 450 600 750 MBTUH KW C.O.P . MBTUH KW C.O.P . MBT ...

  • York YHJF18 THRU 60 - page 21

    510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 21 Multipliers for determining the perform ance with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO YHJF24S41S1 EV APORA TOR COIL MODEL NO AHX30 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 600 800 1000 MBTUH KW C.O.P . MBTUH KW C.O.P . MBTU ...

  • York YHJF18 THRU 60 - page 22

    510667-YTG-B-0509 22 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. HEA TING PE RFORMANCE DA T A CONDENSING UNIT MO DEL NO YHJF30S41S1 EV APORA TOR COIL MODEL NO AHX36 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 800 1000 1200 MBTUH KW C.O.P . MBTUH KW C.O.P . M ...

  • York YHJF18 THRU 60 - page 23

    510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 23 Multipliers for determining the perform ance with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO YHJF36S41S1 EV APORA TOR COIL MODEL NO AHX36 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 1000 1200 1400 MBTUH KW C.O.P . MBTUH KW C.O.P . MB ...

  • York YHJF18 THRU 60 - page 24

    510667-YTG-B-0509 24 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. HEA TING PE RFORMANCE DA T A CONDENSING UNIT MO DEL NO YHJF42S41S1 EV APORA TOR COIL MODEL NO AHX60 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 1200 1400 1600 MBTUH KW C.O.P . MBTUH KW C.O.P . ...

  • York YHJF18 THRU 60 - page 25

    510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 25 Multipliers for determining the perform ance with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO YHJF48S41S1 EV APORA TOR COIL MODEL NO F6FP060 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 1400 1600 1800 MBTUH KW C.O.P . MBTUH KW C.O.P . ...

  • York YHJF18 THRU 60 - page 26

    Subject to change without notice. Publishe d in U.S.A. 510667-YTG-B-0509 Copyright © 2009 by Johnson Controls, Inc. All ri ghts reserved. Supersedes: 510667-YTG-A-0409 Johnson Controls Unitary Product s 5005 Y ork Drive Norman, OK 73069 Multipliers for determining the perfo rman ce with other indoor sections. HEA TING PE RFORMANCE DA T A CONDENSIN ...

Fabricante York Categoría Heat Pump

Los documentos del dispositivo York YHJF18 THRU 60 que obtenemos del fabricante se pueden dividir en varios grupos. Entre ellos están::
- dibujos técnicos York
- manuales de instrucciones YHJF18 THRU 60
- hojas de producto York
- folletos informativos
- o etiquetas energéticas York YHJF18 THRU 60
Todos son importantes, pero lo más importante desde el punto de vista del usuario de un dispositivo lo encontraremos en el manual de instrucciones York YHJF18 THRU 60.

Un conjunto de documentos determinado como manual de instrucciones se divide también en tipos más detallados, tales como: instrucciones de montaje York YHJF18 THRU 60, instrucciones de servicio, instrucciones cortas o instrucciones de usuario York YHJF18 THRU 60. Dependiendo de la situación debes buscar el documento que necesitas. En nuestra página puedes consultar el manual de instrucciones más popular del producto York YHJF18 THRU 60.

Manuales de instrucciones parecidos

El manual de instrucciones del dispositivo York YHJF18 THRU 60, ¿cómo debería ser?
El manual de instrucciones, también determinado como el manual de usuario o simplemente instrucciones, es un documento técnico que tiene como objetivo ayudar a los usuarios a utilizar York YHJF18 THRU 60. Las instrucciones normalmente las realiza un escritor técnico pero en un lenguaje comprensible para todos los usuarios de York YHJF18 THRU 60.

El manual de instrucciones completo de York debe contener unos elementos básicos. Una parte de ellos es menos importante, como por ejemplo: la portada / la página principal o las páginas de autor. Sin embargo, lo demás debe facilitarnos la información más importante desde el punto de vista del usuario.

1. Introducción y pistas sobre cómo orientarse con el manual York YHJF18 THRU 60 - Al principio de cada manual se deben encontrar las indicaciones acerca de la manera de usar un manual de instrucciones. Debe contener información sobre dónde encontrar el índice York YHJF18 THRU 60, preguntas frecuentes o problemas más comunes – son los apartados más buscados por los usuarios de cada manual de instrucciones.
2. Índice - listados de todos los consejos acerca de York YHJF18 THRU 60 que encontraremos en el documento
3. Consejos de uso de las funciones básicas del dispositivo York YHJF18 THRU 60 - que deben facilitarnos los primeros pasos durante el uso de York YHJF18 THRU 60
4. Troubleshooting - una secuencia sistematizada de acciones que nos ayudará a diagnosticar los problemas más importantes con York YHJF18 THRU 60
5. FAQ - las preguntas frecuentes
6. Datos de contacto Información acerca de cómo encontrar los datos de contacto del fabricante / servicio de York YHJF18 THRU 60 en cada país si no somos capaces de solucionar el problema por nuestra cuenta.

¿Tienes una pregunta acerca de York YHJF18 THRU 60?

Utiliza el formulario que se encuentra abajo

Si con la ayuda del manual de instrucciones encontrado no has podido solucionar tu problema con York YHJF18 THRU 60, haz una pregunta utilizando el formulario que se encuentra abajo. Si alguno de los usuarios ha tenido un problema parecido con York YHJF18 THRU 60 probablemente compartirá una forma de solucionarlo.

Copia el texto de la imagen

Comentarios (0)