Goodman Mfg GSZ/VSZ 13 SEER - page 1
GSZ/VSZ 13 SEER S plit System Heat Pump s • Refer to Service Manual RS6200006 for installation, operation, and troubleshooting information. • All safety information must be followed as provided in the Service Manual. • Refer to the appropriate Parts Catalog for part number information. • Models listed on page 3. RT6212006 Rev. 5 August 2010 ...
-
Goodman Mfg GSZ/VSZ 13 SEER - page 2
PRODUCT IDENTIFICA TION 2 The model number is used for positive identification of component parts used in manufacturing. Please use this number when requesting service or parts information. WA RNI NG WARNING HIGH VOLTAGE! Disconnect ALL power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause ...
-
Goodman Mfg GSZ/VSZ 13 SEER - page 3
PRODUCT IDENTIFICA TION 3 The United States Environmental Protection Agency (“EPA”) has issued various regulations re- garding the introduction and disposal of refrigerants introduced into this unit. Failure to follow these regulations may harm the environment and can lead to the imposition of substantial fines. These regulations may vary by ju ...
-
Goodman Mfg GSZ/VSZ 13 SEER - page 4
PRODUCT DESIGN 4 GSZ/VSZ13 models are available in 1 1/2 through 5 ton sizes and use R-410A refrigerant. They are designed for 208/230 volt single phase applications. Select GSZ13 models are available in 208/230 and 460 volt 3-phase applications. These models use R-410A refrigerant. The condenser air is pulled through the condenser coil by a direct ...
-
Goodman Mfg GSZ/VSZ 13 SEER - page 5
PRODUCT DESIGN 5 Mo d el D i m en si o n s - W x D x H G / V SZ 130181A * 26 x 26 x 32 ¼ G / V S Z 130241A * 26 x 26 x 32 ¼ G / V S Z 130241B* 26 x 26 x 32 ½ G / V SZ 130301A * 26 x 26 x 32 ¼ G / V S Z 13036 1A * G SZ 130363A * 2 9 x 2 9 x 3 8 ¼ G / V S Z 130361B* 29 x 29 x 32 ½ G / V SZ 130421A * 29 x 29 x 38 ¼ G / V S Z 13048 1A * G SZ 130 ...
-
Goodman Mfg GSZ/VSZ 13 SEER - page 6
HEA T PUMP SPECIFICA TIONS 6 NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only. Unit specifications are subject to change without notice. ALWAYS refer to the unit's serial ...
-
Goodman Mfg GSZ/VSZ 13 SEER - page 7
HEA T PUMP SPECIFICA TIONS 7 NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only. Unit specifications are subject to change without notice. ALWAYS refer to the unit's serial ...
-
Goodman Mfg GSZ/VSZ 13 SEER - page 8
HEA T PUMP SPECIFICA TIONS 8 NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only. Unit specifications are subject to change without notice. ALWAYS refer to the unit's serial ...
-
Goodman Mfg GSZ/VSZ 13 SEER - page 9
9 COOLING PERFORMANCE DA T A G/VSZ130181A* M O D E L : G /V S Z 130181A * / A R * F 182416 ** EXPA ND ED PER FOR M ANC E D ATA COOL I NG O PE RA T I ON O utdoor Am bien t Te m pe r ature 65 75 85 95 105 1 15 E n te r ing I n doo r We t B u l b Te m pe rature I D B * A i r f l o w 5 96 3 6 7 7 15 9 6 3 6 77 15 96 36 77 1 5 9 6 3 6 7 7 15 9 6 3 6 77 ...
-
Goodman Mfg GSZ/VSZ 13 SEER - page 10
10 COOLING PERFORMANCE DA T A G/VSZ130181A* M O D E L: G /V S Z 130181A * / A R * F 182416* * EXPAN DED PER FORM AN CE DA T A COOL I NG OP E RA T I ON O utdoor Am bi e nt Te m pe r a tur e 65 75 85 95 105 115 E nte r i ng Indoor W e t B ul b Te m pe r at ur e I D B * A i r f l o w 5 96 36 7 7 15 96 3 6 77 15 96 36 77 15 9 6 3 6 7 7 15 96 36 77 15 9 ...
-
Goodman Mfg GSZ/VSZ 13 SEER - page 11
11 COOLING PERFORMANCE DA T A G/VSZ130241A* M O D E L: G /V S Z 130241A * / A R* F 182416** EX PANDED P ERF O RM ANCE DAT A C O O L IN G O P E R A T IO N O utdoo r Am bi e nt Te m pe r at ur e 65 75 85 95 105 115 E nte r i ng I ndoor Wet B ul b Te m pe r at ur e I D B * A i r f l o w 5 9 6 3 6 77 1 5 9 6 36 77 15 96 3 6 7 7 15 9 6 3 6 7 7 15 96 36 ...
-
Goodman Mfg GSZ/VSZ 13 SEER - page 12
12 COOLING PERFORMANCE DA T A G/VSZ130241A* M O D E L : G /VSZ 13024 1A * / A R * F 1 82416 * * EX PAN DE D PERF OR M ANCE D AT A COOL I NG OP E RA T I ON O utdoor Am bi e nt Te m per a ture 65 75 85 95 105 115 E nte ri ng I ndoor W e t B ul b Te m pe r at ur e I D B * A i r f l o w 5 9 6 3 6 77 1 5 9 6 36 77 15 96 3 6 7 7 15 9 6 3 6 7 7 1 5 96 36 ...
-
Goodman Mfg GSZ/VSZ 13 SEER - page 13
13 COOLING PERFORMANCE DA T A EXPAN DED PE RFORM AN CE DATA MODE L : G/ V S Z130241B*/ AR*F18 2416* * C OOLI NG OPE RA TI ON O ut door Am bie nt Te m pe r atur e 65 75 85 95 105 115 E nte r ing Indoor W e t B ulb Te m pe r atur e ID B Air f l ow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 5 9 63 67 71 M Bh 22 . 5 23.4 25. 6 - 22. 0 ...
-
Goodman Mfg GSZ/VSZ 13 SEER - page 14
14 COOLING PERFORMANCE DA T A G/VSZ130241B* EXPAN DED PE RFORM AN CE DATA MODE L : G/ V S Z 130241B*/ AR*F18 2416* * C OOLI NG OP E RA T I ON O ut door Am bie nt Te m pe r atur e 6 5 75 8 5 9 5 105 11 5 E nte r ing Indoor W e t B ulb Te m pe r atur e ID B Air f l ow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 5 9 63 67 71 M Bh 23.33 ...
-
Goodman Mfg GSZ/VSZ 13 SEER - page 15
15 COOLING PERFORMANCE DA T A G/VSZ130301A* M O D E L : G /V S Z 1303 01A * / A R * F 30 301* * E XPA NDED P E RF ORM AN CE DA T A COOL I NG OP ER A TI ON O utd o or Am bie nt T e m p e r atur e 65 75 85 95 105 115 E n te r i n g I ndo or We t B ul b Te m pe r ature I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 9 6 3 6 77 15 9 6 3 6 7 7 15 96 36 ...
-
Goodman Mfg GSZ/VSZ 13 SEER - page 16
16 COOLING PERFORMANCE DA T A G/VSZ130301A* M O D E L : G /V S Z 13030 1A * / A R * F 303 01* * EXPA ND ED PER FOR M AN CE D ATA C OOL I N G OPE RA TI ON O utdoor Am bi e nt Te m pe r ature 65 75 85 95 105 1 15 E n te r i ng I ndoor We t B ulb Te m pe r ature I D B * A i r f l o w 5 96 36 77 1 5 96 36 77 15 9 6 3 6 77 15 9 6 3 6 7 7 15 9 6 3 6 77 1 ...
-
Goodman Mfg GSZ/VSZ 13 SEER - page 17
17 COOLING PERFORMANCE DA T A G/VSZ130361A* M O D E L : G /V S Z130361A * / A R * F 36 42 16 * * EX PANDED P ERF O RM ANCE DAT A C OOL I N G OPE R ATIO N O utdoor Am bi e nt Te m pe r a tur e 65 75 85 95 105 11 5 E nte r i ng In door Wet B ul b Te m pe rature ID B A ir f lo w 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 M ...
-
Goodman Mfg GSZ/VSZ 13 SEER - page 18
18 COOLING PERFORMANCE DA T A G/VSZ130361A* M O D E L: G / VSZ130361A * / A R * F 3 64216 * * EXPA NDED PERFOR M AN CE DA T A C OOL IN G OP E R AT ION O utd oor Am bi e n t Te m pe r atur e 65 75 85 95 105 115 E nte ring I ndoor W e t B ul b Tem pe r atu r e I D B * A i r f l o w 5 9 6 3 6 77 1 5 9 6 36 7 7 1 5 9 6 3 6 77 15 9 6 3 6 7 7 15 96 36 77 ...
-
Goodman Mfg GSZ/VSZ 13 SEER - page 19
19 COOLING PERFORMANCE DA T A G/VSZ130361B* EXPAN DED PE RFORM AN CE DATA M ODEL: G/ V S Z 1303 61B* / AR*F 364216 * * C OOLI NG OPE RA TI ON O ut door Am bie nt Te m pe r atur e 65 75 85 95 105 115 E nte r ing Indoor W et B ulb Te m pe r atur e ID B Air f l ow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 5 9 63 67 71 M Bh 34.3 35.5 ...
-
Goodman Mfg GSZ/VSZ 13 SEER - page 20
20 COOLING PERFORMANCE DA T A G/VSZ130361B* EXPAN DED PE RFORM AN CE DATA M ODEL: G/ V S Z 1303 61B* / AR*F 364216 * * C OOLI NG OP ER ATION O ut door Am bie nt Te m pe r atur e 65 75 85 95 105 115 E nte r ing Indoor W et B ulb Te m pe r atur e ID B Air f l ow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 5 9 63 67 71 M Bh 35.50 36.27 ...
-
Goodman Mfg GSZ/VSZ 13 SEER - page 21
21 COOLING PERFORMANCE DA T A GZ130363A* EXPAN DED PERFORMAN CE DATA M ODEL: GS Z 130363A* / AR*F 3642 16** COOLING OP E RATION O u td oo r Am bie n t Te m pe r atur e 65 75 85 9 5 105 115 E nte r i ng I ndoor Wet B ul b Te m pe r ature ID B Air flow 59 63 67 71 59 63 67 7 1 59 63 67 71 59 63 67 71 59 63 67 71 59 63 6 7 71 M Bh 33.8 3 5.0 38. 4 - 3 ...
-
Goodman Mfg GSZ/VSZ 13 SEER - page 22
22 COOLING PERFORMANCE DA T A GZ130363A* EXPAN DED PERFORMAN CE DATA M ODEL: GS Z 130363A* / AR*F 3642 16** COOLING OP E RATION O u td oo r Am bie n t Te m pe r atur e 65 75 85 9 5 105 115 E nte r i ng I ndoor Wet B ul b Te m pe r ature ID B Air flow 59 63 67 71 59 63 67 7 1 59 63 67 71 59 63 67 71 59 63 67 71 59 63 6 7 71 M Bh 34.98 3 5.75 38.19 4 ...
-
Goodman Mfg GSZ/VSZ 13 SEER - page 23
23 COOLING PERFORMANCE DA T A G/VSZ130421A* M O D E L : G /V SZ 130421A * / A R * F 36421* * EX PANDED PERF ORM ANCE DATA COOL I NG OP ERA T I ON O utdoo r Am bie nt Te m pe r ature 65 75 85 95 105 115 E n t e r in g In d o o r We t B u lb T e m p e r at u r e ID B Air f low 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 M ...
-
Goodman Mfg GSZ/VSZ 13 SEER - page 24
24 COOLING PERFORMANCE DA T A G/VSZ130421A* M O D E L : G /VSZ 130421 A * / A R * F 36421* * EXP ANDED PERF ORM ANCE DAT A CO OLI N G OPE RA T I ON O utdoo r Am bie nt Te m pe r atur e 65 7 5 85 95 105 115 E n t e r in g In d o o r We t B u lb T e m p e r at u r e I D B * A i r f l o w 5 9 6 3 6 7 7 1 5 9 6 36 77 15 9 6 3 6 77 1 5 9 6 3 6 7 7 1 5 9 ...
-
Goodman Mfg GSZ/VSZ 13 SEER - page 25
25 COOLING PERFORMANCE DA T A G/VSZ130481A* M O D E L : G /V S Z 130481A * /A R * F 48601** EXPAND ED PER F O RM ANC E DATA COOL I NG OP ERA T I ON O utdoor Am bi e nt Te m pe rat ur e 65 75 85 95 105 115 E nte r i ng I ndoor Wet B ul b Te m p e r at ur e I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 9 6 3 6 77 15 9 6 3 6 7 7 15 96 3 6 77 15 96 3 ...
-
Goodman Mfg GSZ/VSZ 13 SEER - page 26
26 COOLING PERFORMANCE DA T A G/VSZ130481A* M O D E L : G /V S Z 130481A * /A R * F 48601* * EXPAND ED PER F O RM ANC E DATA COOL I NG OP ERA T I ON O utdoor Am bi e nt Te m pe r at ur e 65 75 85 95 105 115 E nte r i ng I ndoor Wet B ul b Te m p e r at ur e I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 9 6 3 6 77 15 9 6 3 6 7 7 15 96 36 77 15 96 ...
-
Goodman Mfg GSZ/VSZ 13 SEER - page 27
27 COOLING PERFORMANCE DA T A GSZ130483A* EXPAN DED PERFORMAN CE DATA M ODEL: GS Z 130483A* / AR*F 4860 16** COOLING OP E RATION O u td oo r Am bie n t Te m pe r atur e 65 75 85 9 5 105 115 E nte r i ng I ndoor Wet B ul b Te m pe r ature ID B Air flow 59 63 67 71 59 63 67 7 1 59 63 67 71 59 63 67 71 59 63 67 71 59 63 6 7 71 M Bh 45.1 4 6.7 51. 2 - ...
-
Goodman Mfg GSZ/VSZ 13 SEER - page 28
28 COOLING PERFORMANCE DA T A GSZ130483A* EXPAN DED PERFORMAN CE DATA M ODEL: GS Z 130483A* / AR*F 4860 16** C OOLING O P E RA TION O u td oo r Am bie n t Te m pe r atur e 65 75 85 95 105 11 5 E nte r i ng I ndoor Wet B ul b Te m pe r ature ID B Air flow 59 63 67 71 59 63 67 7 1 59 63 67 71 59 63 67 71 59 63 67 71 59 63 6 7 71 M Bh 46.66 4 7.67 50. ...
-
Goodman Mfg GSZ/VSZ 13 SEER - page 29
29 COOLING PERFORMANCE DA T A GSZ130484A* EXPAN DED PERFORMAN CE DATA M ODEL: GS Z 130484A* / AR*F 4860 16** COOLING OP E RATION O u td oo r Am bie n t Te m pe r atur e 65 75 85 9 5 105 115 E nte r i ng I ndoor Wet B ul b Te m pe r ature ID B Air flow 59 63 67 71 59 63 67 7 1 59 63 67 71 59 63 67 71 59 63 67 71 59 63 6 7 71 M Bh 45.1 4 6.7 51. 2 - ...
-
Goodman Mfg GSZ/VSZ 13 SEER - page 30
30 COOLING PERFORMANCE DA T A GSZ130484A* EXPAN DED PERFORMAN CE DATA M ODEL: GS Z 130484A* / AR*F 4860 16** C OOLING O P E RA TION O u td oo r Am bie n t Te m pe r atur e 65 75 85 95 105 11 5 E nte r i ng I ndoor Wet B ul b Te m pe r ature ID B Air flow 59 63 67 71 59 63 67 7 1 59 63 67 71 59 63 67 71 59 63 67 71 59 63 6 7 71 M Bh 46.66 4 7.67 50. ...
-
Goodman Mfg GSZ/VSZ 13 SEER - page 31
31 COOLING PERFORMANCE DA T A G/VSZ130601A* M O D E L : G /V S Z 130601A * / A R* F 48601** EXPAN DED PER F O RM AN CE DA T A C OOL I N G OP E R ATI ON O utdoor Am bi e nt Te m pe rat ur e 65 75 85 95 105 115 E nte r i ng I ndoor We t B ul b Te m p e r at ur e ID B A ir f low 59 63 6 7 71 59 63 67 71 5 9 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 ...
-
Goodman Mfg GSZ/VSZ 13 SEER - page 32
32 COOLING PERFORMANCE DA T A G/VSZ130601A* EX PANDED P ERF O RM ANCE DAT A C OOL I N G OP E R AT I ON M ODEL: GS Z 130601A * / AR*F 48601** O utdoor Am bi e n t Te m pe rat ur e 65 75 85 95 105 115 E nt e r i ng Indoor Wet B ulb Te m pe rature ID B A ir flo w 59 63 67 71 59 63 67 71 59 63 67 71 5 9 63 67 71 59 63 67 7 1 59 63 67 71 M Bh 55.9 57.9 ...
-
Goodman Mfg GSZ/VSZ 13 SEER - page 33
33 COOLING PERFORMANCE DA T A GSZ130603A* EXPAN DED PERFORMAN CE DATA M ODEL: GS Z 130603A* /AR*F 4860 16** COOLING OP E RATION O u td oo r Am bie n t Te m pe r atur e 65 75 85 9 5 105 115 E nte r i ng I ndoor Wet B ul b Te m pe r ature ID B Air flow 59 63 67 71 59 63 67 7 1 59 63 67 71 59 63 67 71 59 63 67 71 59 63 6 7 71 M Bh 55.9 5 7.9 63. 4 - 5 ...
-
Goodman Mfg GSZ/VSZ 13 SEER - page 34
34 COOLING PERFORMANCE DA T A GSZ130603A* EXPAN DED PERFORMAN CE DATA M ODEL: GS Z 130603A* /AR*F 4860 16** C OOLING O P E RA TION O u td oo r Am bie n t Te m pe r atur e 65 75 85 95 105 11 5 E nte r i ng I ndoor Wet B ul b Te m pe r ature ID B Air flow 59 63 67 71 59 63 67 7 1 59 63 67 71 59 63 67 71 59 63 67 71 59 63 6 7 71 M Bh 57.81 5 9.07 63.1 ...
-
Goodman Mfg GSZ/VSZ 13 SEER - page 35
35 COOLING PERFORMANCE DA T A GSZ130604A* EXPAN DED PERFORMAN CE DATA M ODEL: GS Z 130604A* /AR*F 4860 16** COOLING OP E RATION O u td oo r Am bie n t Te m pe r atur e 65 75 85 9 5 105 115 E nte r i ng I ndoor Wet B ul b Te m pe r ature ID B Air flow 59 63 67 71 59 63 67 7 1 59 63 67 71 59 63 67 71 59 63 67 71 59 63 6 7 71 M Bh 55.9 5 7.9 63. 4 - 5 ...
-
Goodman Mfg GSZ/VSZ 13 SEER - page 36
36 COOLING PERFORMANCE DA T A GSZ130604A* EXPAN DED PERFORMAN CE DATA M ODEL: GS Z 130604A* /AR*F 4860 16** COOLING OP E RATION O u td oo r Am bie n t Te m pe r atur e 65 75 85 9 5 105 115 E nte r i ng I ndoor Wet B ul b Te m pe r ature ID B Air flow 59 63 67 71 59 63 67 7 1 59 63 67 71 59 63 67 71 59 63 67 71 59 63 6 7 71 M Bh 57.81 5 9.07 63.11 6 ...
-
Goodman Mfg GSZ/VSZ 13 SEER - page 37
37 SPLIT SYSTEM HEA TING PERFORMANCE *Note: Shaded area is AHRI Rating Conditions at 47° outdoor ambient temberature Hi g h pressure i s measure d a t th e li qu id serv i ce va l ve (t h e sma ll er va l ve ) . AMPS = O u td oor un it amps ( com p.+ f an ) L ow pres su re i s me asu re d a t th e gauge p or t connec ti on. KW = T o t a l sys t em ...
-
Goodman Mfg GSZ/VSZ 13 SEER - page 38
38 SPLIT SYSTEM HEA TING PERFORMANCE *Note: Shaded area is AHRI Rating Conditions at 47° outdoor ambient temberature Hi g h pressure i s measure d a t th e li qu id serv i ce va l ve (t h e sma ll er va l ve ) . AMPS = O u td oor un it amps ( com p. + f an ) L ow pres su re i s me asu re d a t th e gauge p or t connec ti on. KW = T o t a l sys t e ...
-
Goodman Mfg GSZ/VSZ 13 SEER - page 39
39 SPLIT SYSTEM HEA TING PERFORMANCE *Note: Shaded area is AHRI Rating Conditions at 47° outdoor ambient temberature Hi g h pressure i s measure d a t th e li qu id serv i ce va l ve (t h e sma ll er va l ve ) . AMPS = O u td oor un it amps ( com p. + f an ) L ow pres su re i s me asu re d a t th e gauge p or t connec ti on. KW = T o t a l sys t e ...
-
Goodman Mfg GSZ/VSZ 13 SEER - page 40
40 SPLIT SYSTEM HEA TING PERFORMANCE EXPA N DED PER FOR M A N CE DA T A M ODEL: GS Z 130483A* / A R*F486016 ** H E A T IN G OP E RAT IO N O utd oor Am bie nt Te m pe r atur e 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 - 5 - 10 M Bh 55.3 52.4 49.3 46.1 44. 0 42.6 39.6 36.5 33.6 31.1 28.6 27.0 26.0 23.3 20.7 18.0 15.4 12.6 D T 32.0 30. 3 28.5 26.7 ...
-
Goodman Mfg GSZ/VSZ 13 SEER - page 41
41 PERFORMANCE DA T A PERFORMANCE TEST All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoo r air cubic feet per minute (CFM) as listed in the Performance Data Sheets: If conditions vary from this, results will change as follows: 1. As indoor dry bulb temperatures increase, a ...
-
Goodman Mfg GSZ/VSZ 13 SEER - page 42
HIGH VOL T AGE! DISCONNECT ALL POWER BEFORE SERVICI NG OR INST A LLIN G THIS UNIT . MUL T IPL E POWER SO URCES M A Y BE P RESENT . F AI LURE TO DO SO MA Y CAUS E PROP ERTY DAMAGE, PERSONAL INJURY OR DEA TH. WIRING DIAGRAMS 42 Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring. G/VSZ130[18-60]1 ...
-
Goodman Mfg GSZ/VSZ 13 SEER - page 43
HI GH VO L T AG E! DISC ONNECT ALL POWE R BEFORE SERVICI NG O R INS T A LLING THIS UNIT . MUL T IPL E POWER SOUR CES MA Y BE PR ESENT . F AILURE T O DO SO MA Y CAUS E PROP ERTY DAMAG E, PERSONAL I NJURY OR DE A TH . WIRING DIAGRAMS 43 Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring. GSZ130[ ...
¿Tienes una pregunta acerca de Goodman Mfg GSZ/VSZ 13 SEER?
Utiliza el formulario que se encuentra abajo
Si con la ayuda del manual de instrucciones encontrado no has podido solucionar tu problema con Goodman Mfg GSZ/VSZ 13 SEER, haz una pregunta utilizando el formulario que se encuentra abajo. Si alguno de los usuarios ha tenido un problema parecido con Goodman Mfg GSZ/VSZ 13 SEER probablemente compartirá una forma de solucionarlo.