    TECHNICAL GUIDE AFFINITY SPLIT -SYSTEM HEA T PUMPS 15 SEER – R-410A MODELS: YZE024THRU 060 (2 THRU 5 NOMINAL TONS) Due to continuous pr oduct improvement, spec ifications are subject to change without notice. Visit us on the web at www .york.com Additional rati ng information can be foun d at www .ari.org/aridirectory LISTED ISO 9001 Certified Qu ...

  • York YZE024 THRU 060 - page 2

    2 Johnson Controls Unitary Products 246750-YTG-L-0408 All dimensions are in inches. They are subject to change without notice. Certified dimensions wil l be provided upon request. * Adapter fitting required for 1-1/8” line set. Physical and Electrical Dat a MODEL YZE0241 1 YZE0361 1 YZE0481 1 YZE0601 1 Unit Supply V oltage 208-230V , 1 φ, 60Hz N ...

  • York YZE024 THRU 060 - page 3

    Johnson Controls Unitary Produ cts 3 246750-YTG-L-0408 PROCEDURES: 1. Unit factory charge listed on the unit nameplate includes refri gerant for the condenser , the smallest evaporator and 15 feet of intercon- necting line tubing. 2. V erify the TXV and additional charge requ ired for specific evaporator coil in th e system using the above table. 3 ...

  • York YZE024 THRU 060 - page 4

    4 Johnson Controls Unitary Products 246750-YTG-L-0408 COOLING CAP ACITY - Wi th Air Handler Coils UNIT MODEL AIR HANDLER COIL 1 MODEL COOLING MODEL W ST AGE RA TED CFM NET MBH SENSIBL E SEER EER YZE0241 1 A V24 17 – 1 535 18.6 13.6 15.00 13.00 2 800 24.0 18.6 12.50 A V36 17 – 1 535 18.6 13.6 15.00 13.00 2 800 24.0 18.6 12.50 MV12B 17 FC/MC30B 1 ...

  • York YZE024 THRU 060 - page 5

    Johnson Controls Unitary Produ cts 5 246750-YTG-L-0408 COOLING CAP ACITY - With V a riable Speed Furnaces UNIT MODEL V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING ST AGE RA TED CFM NET MBH SEER EER TOT AL SENSIBLE YZE0241 1 PV8*A12 FC/MC/PC/UC30A 14 1 430 17.3 1 1.5 14.00 12.60 2 750 23.0 18.2 12.00 PV9*A12 FC/MC/PC30A 14 1 625 18.5 14.4 14. ...

  • York YZE024 THRU 060 - page 6

    6 Johnson Controls Unitary Products 246750-YTG-L-0408 YZE0361 1 P(C,V)9*C16 FC/MC/PC/UC48C 21 1 640 24.2 16.2 15.50 12.70 2 1200 35.2 25.1 12.00 PV8*C16 FC/MC/PC/UC48C 21 1 780 25.0 18.9 15.00 12.85 2 1200 34.8 26.8 12.00 PV8*C20 FC/MC/PC/UC48C 21 1 800 25.2 19.1 15.25 12.90 2 1200 35.0 26.8 12.00 P(C,V)9*D20 FC/MC/PC/UC48D 24 1 770 25.0 18.8 15.50 ...

  • York YZE024 THRU 060 - page 7

    Johnson Controls Unitary Produ cts 7 246750-YTG-L-0408 HEA TIN G CAP ACITY - With Air Handler Coils UNIT MODEL AIR HANDLER MODEL COIL 1 MODEL HEA TING ST AGE RA TED CFM NET MBH HSPF COP @ 47 47 OD 17 OD YZE0241 1 A V24 - 1 650 19.0 - - 3.30 2 775 24.0 15.6 8.25 3.36 2 650 23.2 14.6 8.05 3.12 A V36 - 1 650 19.0 - - 3.30 2 775 24.0 15.6 8.25 3.36 2 6 ...

  • York YZE024 THRU 060 - page 8

    8 Johnson Controls Unitary Products 246750-YTG-L-0408 ** Refer to Q uick Selectio n Char t for specific furnace match-up. YZE0601 1 A V60 - 1 1200 37.6 - - 3.26 2 1900 55.0 32 .4 8.05 3.50 2 1200 50.0 29 .8 7.90 3.22 F2FV060 - 1 1200 37.6 - - 3.26 2 1900 54.0 32 .2 8.00 3.50 2 1200 50.0 29 .8 7.90 3.22 MV20D FC/MC60D 1 1200 37. 6 - - 3.26 2 1900 54 ...

  • York YZE024 THRU 060 - page 9

    Johnson Controls Unitary Produ cts 9 246750-YTG-L-0408 YZE0361 1 P(C,V)9*B12 FC/MC/PC3 5B 17 1 650 2 3.0 - - 3.54 2 1200 33.0 20.8 8.50 3.70 2 650 29.4 19.6 8.35 3.30 PV8*B16 FC/MC/PC35B 17 1 650 23.0 - - 3.54 2 1200 33.0 21.0 8.50 3.70 2 650 29.4 19.6 8.35 3.30 P(C,V)9*C16 FC/MC/PC35C 21 1 650 23.0 - - 3.54 2 1200 33.0 21.0 8.50 3.70 2 650 29.4 19 ...

  • York YZE024 THRU 060 - page 10

    10 Johnson Controls Unitary Products 246750-YTG-L-0408 YZE0481 1 PV8*C20 FC/PC/UC60C 21 1 860 31.2 - - 3.56 2 1610 48.0 27.8 8.35 3.96 2 860 44.5 26.2 8.30 3.66 P(C,V)9*C20 FC /PC/UC60C 21 1 870 31.2 - - 3.56 2 1590 48.0 27.8 8.40 3.96 2 870 44.5 26.2 8.30 3.66 P(C,V)9*D20 FC/MC/PC/UC60D 24 1 855 31.2 - - 3.56 2 1620 48.0 27.8 8.40 3.96 2 855 44.5 ...

  • York YZE024 THRU 060 - page 11

    Johnson Controls Unitary Produ cts 11 246750-YTG-L-0408 ACCESSORIES* TXV Kits - 1 TVM9 series thermal expansion val ves precisely meter refrigerant for optimu m performance. Bonnet Sensor (2SB137 00124) - The bonnet sensor is u sed to sense plenum temperatur e, and is optional with a gas or oi l back-up heat source. Compatible only with 13 SEER and ...

  • York YZE024 THRU 060 - page 12

    12 Johnson Controls Unitary Products 246750-YTG-L-0408 Multipliers for determining th e performance with other indoor sec tions . NOTE: For dry bulb temperatures dif f erent than those listed (bet ween 73-87 F), sensible capacity increa se s by 1060 BTUH per 100 0 CFM per degree above the listed temperatu re and decre ases by 1060 BTUH per 1000 CFM ...

  • York YZE024 THRU 060 - page 13

    Johnson Controls Unitary Produ cts 13 246750-YTG-L-0408 Multipliers for determining the performance with ot her indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity increases by 1060 BTUH per 100 0 CFM per degree above the listed temperature and decre ases by 1060 BTUH per 10 00 CFM per ...

  • York YZE024 THRU 060 - page 14

    14 Johnson Controls Unitary Products 246750-YTG-L-0408 Multipliers for determining th e performance with other indoor sec tions . NOTE: For dry bulb temperatures dif f erent than those listed (bet ween 73-87 F), sensible capacity increa se s by 1060 BTUH per 100 0 CFM per degree above the listed temperatu re and decre ases by 1060 BTUH per 1000 CFM ...

  • York YZE024 THRU 060 - page 15

    Johnson Controls Unitary Produ cts 15 246750-YTG-L-0408 Multipliers for determining the performance with ot her indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity increases by 1060 BTUH per 100 0 CFM per degree above the listed temperature and decre ases by 1060 BTUH per 10 00 CFM per ...

  • York YZE024 THRU 060 - page 16

    16 Johnson Controls Unitary Products 246750-YTG-L-0408 Multipliers for determining th e performance with other indoor sec tions . NOTE: For dry bulb temperatures dif f erent than those listed (bet ween 73-87 F), sensible capacity increa se s by 1060 BTUH per 100 0 CFM per degree above the listed temperatu re and decre ases by 1060 BTUH per 1000 CFM ...

  • York YZE024 THRU 060 - page 17

    Johnson Controls Unitary Produ cts 17 246750-YTG-L-0408 Multipliers for determining the performance with ot her indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity increases by 1060 BTUH per 100 0 CFM per degree above the listed temperature and decre ases by 1060 BTUH per 10 00 CFM per ...

  • York YZE024 THRU 060 - page 18

    18 Johnson Controls Unitary Products 246750-YTG-L-0408 Multipliers for determining th e performance with other indoor sec tions . NOTE: For dry bulb temperatures dif f erent than those listed (bet ween 73-87 F), sensible capacity increa se s by 1060 BTUH per 100 0 CFM per degree above the listed temperatu re and decre ases by 1060 BTUH per 1000 CFM ...

  • York YZE024 THRU 060 - page 19

    Johnson Controls Unitary Produ cts 19 246750-YTG-L-0408 Multipliers for determining the performance with ot her indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity increases by 1060 BTUH per 100 0 CFM per degree above the listed temperature and decre ases by 1060 BTUH per 10 00 CFM per ...

  • York YZE024 THRU 060 - page 20

    20 Johnson Controls Unitary Products 246750-YTG-L-0408 Multipliers for determining the perfo rman ce with other indoor section. NOTE: KW RA TING IS FOR OUT DOOR AND INDOOR UNITS. LOW CFM HEA TING PERFORMA NCE DA T A - LOW CFM 1-ST AGE OPERA TION OUTDOOR UNIT MODEL NO. YZE0241 1 INDOOR COIL MODEL NO . FC/MC/PC36B + MV12B AIR TEMP . ENTERING OUTDOOR ...

  • York YZE024 THRU 060 - page 21

    Johnson Controls Unitary Produ cts 21 246750-YTG-L-0408 Multipliers for de termining the performa nce with other i ndoor section. NOTE: KW RA TING IS FOR OU TDOOR AND INDOOR UNITS. HIGH CFM HEA TIN G PERFOR MA NCE DA T A - HIGH CFM 2-ST AGE OPERA TION OUTDOOR UNIT MODEL NO. YZE0241 1 INDOOR COIL MODEL NO. FC/MC/PC36B + MV12B AIR TEMP . ENTERING OUT ...

  • York YZE024 THRU 060 - page 22

    22 Johnson Controls Unitary Products 246750-YTG-L-0408 Multipliers for determining th e performance with other indoor sec tions . NOTE: KW RA TING IS FOR OUT DOOR AND INDOOR UNITS. LOW CFM HEA TING PERFORMA NCE DA T A - LOW CFM 1-ST AGE OPERA TION OUTDOOR UNIT MODEL NO. YZE0361 1 INDOOR COIL MODEL NO . FC/MC/PC48C + MV16C AIR TEMP . ENTERING OUTDOO ...

  • York YZE024 THRU 060 - page 23

    Johnson Controls Unitary Produ cts 23 246750-YTG-L-0408 Multipliers for de termining the performa nce with other i ndoor sections. NOTE: KW RA TING IS FOR OU TDOOR AND INDOOR UNITS. HIGH CFM HEA TIN G PERFOR MA NCE DA T A - HIGH CFM 2-ST AGE OPERA TION OUTDOOR UNIT MODEL NO. YZE0361 1 INDOOR COIL MODEL NO. FC/MC/PC48C + MV16C AIR TEMP . ENTERING OU ...

  • York YZE024 THRU 060 - page 24

    24 Johnson Controls Unitary Products 246750-YTG-L-0408 Multipliers for determining the perfo rman ce with other indoor sections. NOTE: KW RA TING IS FOR OUT DOOR AND INDOOR UNITS. LOW CFM HEA TING PERFORMA NCE DA T A - LOW CFM 1-ST AGE OPERA TION OUTDOOR UNIT MODEL NO. YZE0481 1 INDOOR COIL MODEL NO . FC/MC/PC60D + MV20D AIR TEMP . ENTERING OUTDOOR ...

  • York YZE024 THRU 060 - page 25

    Johnson Controls Unitary Produ cts 25 246750-YTG-L-0408 Multipliers for de termining the performa nce with other i ndoor sections. NOTE: KW RA TING IS FOR OU TDOOR AND INDOOR UNITS. HIGH CFM HEA TIN G PERFOR MA NCE DA T A - HIGH CFM 2-ST AGE OPERA TION OUTDOOR UNIT MODEL NO. YZE0481 1 INDOOR COIL MODEL NO. FC/MC/PC60D + MV20D AIR TEMP . ENTERING OU ...

  • York YZE024 THRU 060 - page 26

    26 Johnson Controls Unitary Products 246750-YTG-L-0408 Multipliers for determining the perfo rman ce with other indoor sections. NOTE: KW RA TING IS FOR OUT DOOR AND INDOOR UNITS. LOW CFM HEA TING PERFORMA NCE DA T A - LOW CFM 1-ST AGE OPERA TION OUTDOOR UNIT MODEL NO. YZE0601 1 INDOOR COIL MODEL NO. MC61D + MV20D AIR TEMP . ENTERING OUTDOOR UNIT A ...

  • York YZE024 THRU 060 - page 27

    Johnson Controls Unitary Produ cts 27 246750-YTG-L-0408 Multipliers for de termining the performa nce with other i ndoor sections. NOTE: KW RA TING IS FOR OU TDOOR AND INDOOR UNITS. HIGH CFM HEA TIN G PERFOR MA NCE DA T A - HIGH CFM 2-ST AGE OPERA TION OUTDOOR UNIT MODEL NO. YZE0601 1 INDOOR COIL MODEL NO. MC61D + MV20D AIR TEMP . ENTERING OUTDOOR ...

  • York YZE024 THRU 060 - page 28

    Subject to change without notice. Printe d in U.S.A. 246750-YTG-L-0408 Copyright © 2008 by Johnson Controls, Inc. All rights reserved. Supersedes: 246750-YTG-K-0108 Johnson Controls Unit ary Products 5005 Y ork Drive Norman, OK 73069 NOTES ...

Fabricante York Categoría Heat Pump

Los documentos del dispositivo York YZE024 THRU 060 que obtenemos del fabricante se pueden dividir en varios grupos. Entre ellos están::
- dibujos técnicos York
- manuales de instrucciones YZE024 THRU 060
- hojas de producto York
- folletos informativos
- o etiquetas energéticas York YZE024 THRU 060
Todos son importantes, pero lo más importante desde el punto de vista del usuario de un dispositivo lo encontraremos en el manual de instrucciones York YZE024 THRU 060.

Un conjunto de documentos determinado como manual de instrucciones se divide también en tipos más detallados, tales como: instrucciones de montaje York YZE024 THRU 060, instrucciones de servicio, instrucciones cortas o instrucciones de usuario York YZE024 THRU 060. Dependiendo de la situación debes buscar el documento que necesitas. En nuestra página puedes consultar el manual de instrucciones más popular del producto York YZE024 THRU 060.

Manuales de instrucciones parecidos

El manual de instrucciones del dispositivo York YZE024 THRU 060, ¿cómo debería ser?
El manual de instrucciones, también determinado como el manual de usuario o simplemente instrucciones, es un documento técnico que tiene como objetivo ayudar a los usuarios a utilizar York YZE024 THRU 060. Las instrucciones normalmente las realiza un escritor técnico pero en un lenguaje comprensible para todos los usuarios de York YZE024 THRU 060.

El manual de instrucciones completo de York debe contener unos elementos básicos. Una parte de ellos es menos importante, como por ejemplo: la portada / la página principal o las páginas de autor. Sin embargo, lo demás debe facilitarnos la información más importante desde el punto de vista del usuario.

1. Introducción y pistas sobre cómo orientarse con el manual York YZE024 THRU 060 - Al principio de cada manual se deben encontrar las indicaciones acerca de la manera de usar un manual de instrucciones. Debe contener información sobre dónde encontrar el índice York YZE024 THRU 060, preguntas frecuentes o problemas más comunes – son los apartados más buscados por los usuarios de cada manual de instrucciones.
2. Índice - listados de todos los consejos acerca de York YZE024 THRU 060 que encontraremos en el documento
3. Consejos de uso de las funciones básicas del dispositivo York YZE024 THRU 060 - que deben facilitarnos los primeros pasos durante el uso de York YZE024 THRU 060
4. Troubleshooting - una secuencia sistematizada de acciones que nos ayudará a diagnosticar los problemas más importantes con York YZE024 THRU 060
5. FAQ - las preguntas frecuentes
6. Datos de contacto Información acerca de cómo encontrar los datos de contacto del fabricante / servicio de York YZE024 THRU 060 en cada país si no somos capaces de solucionar el problema por nuestra cuenta.

¿Tienes una pregunta acerca de York YZE024 THRU 060?

Utiliza el formulario que se encuentra abajo

Si con la ayuda del manual de instrucciones encontrado no has podido solucionar tu problema con York YZE024 THRU 060, haz una pregunta utilizando el formulario que se encuentra abajo. Si alguno de los usuarios ha tenido un problema parecido con York YZE024 THRU 060 probablemente compartirá una forma de solucionarlo.

Copia el texto de la imagen

Comentarios (0)