    HP BladeSystem c3000 Enclosure technology brief, 2nd edition Abstract .............................................................................................................................................. 3 Overview of HP BladeSystem c3000 Enclosure ....................................................................................... 3 Ma ...

  • StarTech.com C3000 - page 2

    HP BladeSystem Power Sizer ....................................................................................................... 31 Summary ............................................................................................................................... ........... 32 Appendix. Fan, power supply, and device bay populati on guideline ...

  • StarTech.com C3000 - page 3

    Abstract The HP BladeSystem c3000 Enclosur e is the next generation in an evolution of the entir e rack- mounted infrastru cture. The c3000 en closure is d esi gned for remote sites, small and medium-sized businesses, and data centers with special power and cooling constraints. This technology brief provides an overview of the HP BladeSystem c3 000 ...

  • StarTech.com C3000 - page 4

    Figure 2. HP BladeSystem c3000 Enclosure – rear view The HP BladeSystem c3000 Enclosure has redundant signal paths between servers and interconnect modules. 1 The NonStop signal midplane in the c3000 enclosure has no active components. Th e enclosure is available with a single-phase power subs ystem that can run on either low-line or high-lin e p ...

  • StarTech.com C3000 - page 5

    Table 1. Components supported by HP Bl adeSystem c-Class enclosures Enclosure c3000 c7000 Model Rack (6U) or Tower Rack (10U) Blade orientation Horizontal (rack) Vertical (tower) Vertical Blades supported 8 HH , 4 FH, 6HH/1FH 16 HH, 8 FH Interconnect bays 4 8 Power supplies 6 at up to 1200 watts each 6 at 2250 watts each Active Cool fans 6 10 Enclo ...

  • StarTech.com C3000 - page 6

    the component. If a component is remove d from a bay, the Onboard Administrator deletes the information about that component. Identifying components To identify a component, the Onboard Administrator reads a Field-Re placeable Unit (FRU) Electrically Erasable Programmable Read-Only Memory (EEPROM) that contains specific factory information about th ...

  • StarTech.com C3000 - page 7

    Figure 3. Management communications betwe en Onboard Administrator and other components in an HP BladeSystem c3000 Enclosure c3000 internal management interfaces The Onboard Administrator has several hardware in terfaces to each bay in the c3000 enclosur e to provide management communications bet ween the On board Administrator and all components i ...

  • StarTech.com C3000 - page 8

    service port that allows users to temporarily conne ct a laptop PC to any of the linked enclosu re Onboard Administrators for loca l diagnostics and debugging. Updating firmware The Onboard Administrator manages firmware updat es for the enclosure’s management devices. Updating firmware, including server BIOS firmwa re, NIC and mezzanine BIOS fir ...

  • StarTech.com C3000 - page 9

    user credentials. Two -factor authentication allows even tighter security for the user management session to the Onboard Administrator. Rather than requiring separate logins to multiple resources (once to each enclosure and/or once to every server management processor), the Onboard A d ministrator allows secure , single point access. Thus, the admi ...

  • StarTech.com C3000 - page 10

    configured, the Insight Display verifie s that there are no installation or configurat ion errors. The Installation Wizard turns off the enclosur e UID when the installation is complete. When an error or alert condition is detected, the Insight Display Health Summary screen displays the total number of error conditions and their location s in the o ...

  • StarTech.com C3000 - page 11

    Figure 6. HP BladeSystem c3000 Onboar d Administrator link module Enclosure link cabling The Onboard Administrator link module contains two enclosure li nk ports to allow any active Onboard Administrator module to access linked enclosures. On a standalone enc losure or upper enclosure in a series of l inked enclosures, the uppe r enclosure link-up ...

  • StarTech.com C3000 - page 12

    Enclosure-based DVD ROM The HP BladeSystem c3000 Enclosure has an optional CD/DVD ROM drive that installs in the front of the enclosure. The Insight Display and Onboard Admi nistrator allow system administrators to connect and disconnect the media device to one or multiple servers at a time. In addition, a browser-based console is available through ...

  • StarTech.com C3000 - page 13

    Figure 7. Optional c3000 K VM Module – K VM menu screen Interconnect options and infrastructure A key component of the c3000 en closure is the I/ O infrastructur e—essentially, a NonStop signal midplane that provides the internal wiring between the server or st orage blades and the interconnect modules. The NonStop signal midplane is an en tire ...

  • StarTech.com C3000 - page 14

    Figure 8. Diagram of the HP BladeSystem c3000 signal midplane By taking advantage of the similar four-wire differ ential transmit and receive mechanism, the NonStop signal midplane can support either network-semantic protocols (such as Ethernet, Fibre Channel, and InfiniBand) or memory-semantic protocol s (PCIe), using the same si gnal traces. 3 Fi ...

  • StarTech.com C3000 - page 15

    Figure 9. Logically overlaying physical lanes (r ight) onto sets of four traces (l eft) Each device bay connector has a 100-pin signal connector with 64 high-speed signal pins hard-wired from the device bay connector to the interconnect bay s. This configuration result s in 16 lanes (64 ÷ 4) to each interconnect bay, which provides at least tw o l ...

  • StarTech.com C3000 - page 16

    Each interconnect module a lso prov ides external connectors that va ry based on the particular design. In the c3000 enclosur e, pairs of single-wid e inte rconnect modules installe d in adjacent horizontal bays provide redundant connectivity for dual-por t interfaces in each device bay. Adjacent interconnect modules also have high-speed cross- con ...

  • StarTech.com C3000 - page 17

    a Smart Array controller to enable hardware-based RAID config urations. A mezzanine card is not required to connect a half-height server blade to a direct attach storage blade. However, a full-height serv er blade does require a mezzanine card to connect to the direct attach storage blade. The card must be in the Mezzanine 3 connector to al low ful ...

  • StarTech.com C3000 - page 18

    4x DDR single-port mezzanine ca rd will work equally well in Mezzanine 1, Mezzanine 2, or Mezzanine 3 connectors. Both types of mezzanine cards us e a 450-pin connec tor, enabling up to eight lanes of diff erential transmit and receive signals—in other words, up to two x1 connections, up to two x4 connections, or a single x8 connection. Because t ...

  • StarTech.com C3000 - page 19

    Figure 10. HP BladeSystem c3000 interconnect bay numbering For interconnect bay mapping purp oses, it does not matter in whic h device bay a server blade is installed. The mezzanine connect ors always connec t to the same inter connect bays. Becaus e the connections between the device bays and the interc onnect bays are hard-wired through the NonSt ...

  • StarTech.com C3000 - page 20

    interconnects. It connects embedded Ethernet NICs to the internal facing ports on the Ethernet interconnect. Depending on the configuration requirements, additional mezzanine cards and interconnects can b e employed: • Mezzanine 1 and Interconnect Bay 2 • Mezzanine 2 and Interconnect Bays 3 and 4 • Mezzanine 3 and Interconnect Bays 3 and 4 Th ...

  • StarTech.com C3000 - page 21

    signal midplane are allocated to the adjacent devi ce bay. A four-port PCIe x8 mezzanine card installed in connect or 2 PCIe x8 can send x2 signals to interconnect bays 3 and 4. Figure 12 lists the available conf igu rations for half-height devices installed in device bay N (1–8). Figure 12. Port mapping for HP BladeSystem c3000 half-h eight serv ...

  • StarTech.com C3000 - page 22

    Figure 13. HP BladeSystem c3000 dev ice bay crosslinks as i ndicated by the arrows Interconnect bay crosslinks Interconnect bay crosslinks are wired between adjac ent interconnect bay pairs as indic ated by the arrows in the c3000 enclo sure rear view (Figure 1 4). The crosslink connectivity is i dentical in the c3000 Tower enclo sure. These signal ...

  • StarTech.com C3000 - page 23

    HP Thermal Logic technologies include many elements and capabilities: • Active Cool fans • Parallel Redundant Scalable Enclosure Cooling (PARSEC) design • Instant power and thermal monitoring • Pooled power for a variety of power redundancy modes • Dynamic Power Saver mode • Power Regulator • Power Capping • Power Meter Active Cool ...

  • StarTech.com C3000 - page 24

    Figure 15. Ducted fan cross-section and ducte d fan blade compared to traditional server fan HP PARSEC architecture The c3000 enclosure u ses PARSEC architect ure— parallel, redundant, sc alable, enclosure-based cooling. In this context, parallel means that fresh, cool air flows over all the server blades (in the front of the enclosure) and all t ...

  • StarTech.com C3000 - page 25

    Figure 16. HP BladeSystem c3000 self-sea ling enclosure Redundant and scalable BladeSystem c3000 enclos ures ship with four insta lled fans that provide redundancy and support up to four half-height devices in device bays 1, 2, 5, and 6, or two full-height server blades in device bays 1 and 2. Adding two additional fans to the en closure allows pop ...

  • StarTech.com C3000 - page 26

    Figure 17. The c3000 enclosure fan bay an d de vice bay population guidelines Thermal Logic for the server blade Precise ducting on HP server blades manages airflow and temperature based on the unique thermal requirements of all the crit ical components. The airflo w is tightly ducted to ensure that no air bypasses the server blade and to obtain th ...

  • StarTech.com C3000 - page 27

    Figure 18. Processor heat sink using fully du cted design (left) and a traditional heat sink in a 1U rack-mount server (right) Instant Thermal Monitoring provides a real-time vi ew of heat, power, and cooling data. The Onboard Administrator retrieves thermal informati on from a ll server blades, storage blades, and interconnect modules in the enclo ...

  • StarTech.com C3000 - page 28

    Figure 19. HP BladeSystem c3000 Encl osure supports up to six power supplies High efficiency HP c3000 power supplie s provide gr eater than 90 percent efficiency in AC to DC conversion. These power supplie s use the ProLiant univ ersal form factor so they can also be used in other ProLiant servers. Each power s upply ships wi th a standard power di ...

  • StarTech.com C3000 - page 29

    Figure 20. Remote site solution includes a c3000 enclo sure with UPS and local KVM in a small 14U rack NOTE The rack-mountable HP R5500 UPS (5000VA/4500W) supports four power supplies in the power supply redundant (N+1) power mode. Pooled power configuration an d power redundancy options All the power in the enclosure is provid ed as a si ngle powe ...

  • StarTech.com C3000 - page 30

    Figure 21. Redundant HP BladeSystem c3000 power supplies c onnected to an HP R5500 UPS Connecting to PDUs with AC redundancy to each rack In an N+N AC redundancy configuration, the tota l power available in the power pool equals the amount from the A or B side, whichever contains fe wer power supplies. In this configuration, N power supplies are us ...

  • StarTech.com C3000 - page 31

    NOTE In redundant environments using Dynamic P ower Saver mode, a minimum of two power supplies are always active. The maximum load for any power supply is 50 percent. Once the 50 percent load is reached, another two power supplies are activated to ensure redundancy at all times. HP Power Regulator for ProLiant HP Power Regulator for ProLiant and B ...

  • StarTech.com C3000 - page 32

    type, application utilization, and ambient temperatur e. The BladeSystem Power Sizer is available at the following URL: http://www.hp.com/go/blad esystem/powercalculator . Summary The HP BladeSystem c3000 Enclosure is the next generation of a new modular computing architect ure that consolidates and simplifies in fras tructur e, re duces op eration ...

  • StarTech.com C3000 - page 33

    Appendix. Fan, power supply, and device bay population guidelines Figure A-1. Fan population guidelines for HP BladeSystem c 3000 Enclosure. For co rrect operation, fans a nd server blades must be installed in the correct fan bays . The Onboard Administrator will ensure that fans and server/storage blades are correctly placed before allowing system ...

  • StarTech.com C3000 - page 34

    Figure A-2. Power supply population guidelines for HP BladeSystem c3000 Enclosure Table A-1. Power supply placement for HP BladeSystem c3000 Enclosure Number of power supplies Power supply bays used 2 1 and 4 4 1, 2, 4, and 5 6 All power supply bays filled Table A-2. Power supply redundancy options fo r HP BladeSystem c3000 Enclosure Number of powe ...

  • StarTech.com C3000 - page 35

    Figure A-3. Full-height server blade device bay numbering for HP BladeSystem c3000 Enclosure. Full--height servers should be populated from bottom to top (rack) or left to right (tower) when viewing from the front of the enclosure. With four fans, only the bottom or left two de vice bays can be used; with six fans, all device bays can be used. Figu ...

  • StarTech.com C3000 - page 36

    CAUTION To prevent improper cooling or thermal damage, do not operate the server blade or the enclosure unless all device bays are populated with either a component or a blank. Figure A-5. The c3000 enclosure is divided by sheet metal panels into two full-height zones. Zone 1 and Zone 2 are divided in half by a removable shelf to acco mmod ate a ma ...

  • StarTech.com C3000 - page 37

    37 CAUTION If a full-height server blade is installed in devi ce bay 1/5 and half-height server blades are installed in devic e bays 2 or 6, removing the full-height server blade leaves server blades installed in device bays 2 and 6 unsupported. This might cause damage to the server blades and the enclosure connectors. Removing the full-height divi ...

  • StarTech.com C3000 - page 38

    For more information For additional information, refer to the resources listed below. Resource description Web address General HP BladeSystem information http://www.hp.com/go/bladesystem/ HP BladeSystem c-Class documentation http://h71028.www7.hp.com/ente rprise/cache/3 16735-0-0-0- 121.html HP BladeSystem c3000 Enclosure Maintenance and Service Gu ...

Fabricante StarTech.com Categoría Server

Los documentos del dispositivo StarTech.com C3000 que obtenemos del fabricante se pueden dividir en varios grupos. Entre ellos están::
- dibujos técnicos StarTech.com
- manuales de instrucciones C3000
- hojas de producto StarTech.com
- folletos informativos
- o etiquetas energéticas StarTech.com C3000
Todos son importantes, pero lo más importante desde el punto de vista del usuario de un dispositivo lo encontraremos en el manual de instrucciones StarTech.com C3000.

Un conjunto de documentos determinado como manual de instrucciones se divide también en tipos más detallados, tales como: instrucciones de montaje StarTech.com C3000, instrucciones de servicio, instrucciones cortas o instrucciones de usuario StarTech.com C3000. Dependiendo de la situación debes buscar el documento que necesitas. En nuestra página puedes consultar el manual de instrucciones más popular del producto StarTech.com C3000.

Manuales de instrucciones parecidos

El manual de instrucciones del dispositivo StarTech.com C3000, ¿cómo debería ser?
El manual de instrucciones, también determinado como el manual de usuario o simplemente instrucciones, es un documento técnico que tiene como objetivo ayudar a los usuarios a utilizar StarTech.com C3000. Las instrucciones normalmente las realiza un escritor técnico pero en un lenguaje comprensible para todos los usuarios de StarTech.com C3000.

El manual de instrucciones completo de StarTech.com debe contener unos elementos básicos. Una parte de ellos es menos importante, como por ejemplo: la portada / la página principal o las páginas de autor. Sin embargo, lo demás debe facilitarnos la información más importante desde el punto de vista del usuario.

1. Introducción y pistas sobre cómo orientarse con el manual StarTech.com C3000 - Al principio de cada manual se deben encontrar las indicaciones acerca de la manera de usar un manual de instrucciones. Debe contener información sobre dónde encontrar el índice StarTech.com C3000, preguntas frecuentes o problemas más comunes – son los apartados más buscados por los usuarios de cada manual de instrucciones.
2. Índice - listados de todos los consejos acerca de StarTech.com C3000 que encontraremos en el documento
3. Consejos de uso de las funciones básicas del dispositivo StarTech.com C3000 - que deben facilitarnos los primeros pasos durante el uso de StarTech.com C3000
4. Troubleshooting - una secuencia sistematizada de acciones que nos ayudará a diagnosticar los problemas más importantes con StarTech.com C3000
5. FAQ - las preguntas frecuentes
6. Datos de contacto Información acerca de cómo encontrar los datos de contacto del fabricante / servicio de StarTech.com C3000 en cada país si no somos capaces de solucionar el problema por nuestra cuenta.

¿Tienes una pregunta acerca de StarTech.com C3000?

Utiliza el formulario que se encuentra abajo

Si con la ayuda del manual de instrucciones encontrado no has podido solucionar tu problema con StarTech.com C3000, haz una pregunta utilizando el formulario que se encuentra abajo. Si alguno de los usuarios ha tenido un problema parecido con StarTech.com C3000 probablemente compartirá una forma de solucionarlo.

Copia el texto de la imagen

Comentarios (0)