Manual de instrucciones Goodman Mfg CKF50Hz

21 de páginas 0.44 mb
Descargar

Pasar a la página of 21

Summary
  • Goodman Mfg CKF50Hz - page 1

    CKF 50 Hz Condensing Unit s • Refer to Service Manual RS6100004 for installation, operation, and troubleshooting information. • All safety information must be followed as provided in the Service Manual. • Refer to the appropriate Parts Catalog for part number information. • Models listed on page 3. RT6111009r4 January 2012 This manual is to ...

  • Goodman Mfg CKF50Hz - page 2

    PRODUCT IDENTIFICA TION 2 The model number is used for positive identification of component parts used in manufacturing. Please use this number when requesting service or parts information. WARNING WARNING HIGH VOLTAGE! Disconnect ALL power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause p ...

  • Goodman Mfg CKF50Hz - page 3

    PRODUCT IDENTIFICA TION 3 The model number is used for positive identification of component parts used in manufacturing. Please use this number when requesting service or parts information. CKF24-2M CKF24-2N CKF36-2M CKF36-2N CKF36-5M CKF36-5N CKF48-5M CKF48-5N CKF60-5M CKF60-5N CKF70-5M CKF70-5N * Indicates minor revision & is not used for ord ...

  • Goodman Mfg CKF50Hz - page 4

    PRODUCT DESIGN 4 CKF 50 Hz models are available in 2 through 6 ton sizes. They are designed for 220/240 to 380 volt single phase appli- cations. The condenser air is pulled through the condenser coil by a direct drive propeller fan. This condenser air is then dis- charged out of the top of the cabinet. These units are designed for free air discharg ...

  • Goodman Mfg CKF50Hz - page 5

    PRODUCT DESIGN 5 H W D Dimensions M o d el D i m en si o n s - W x D x H C KF 24- 2* 26 " [ 6 60] x 26" [ 66 0] x 29¾ [ 7 56] C KF 36- 2* 26 " [ 6 60] x 26" [ 66 0] x 29¾ [ 7 56] C KF 36- 5* 26 " [ 6 60] x 26" [ 66 0] x 29¾ [ 7 56] C KF 48- 5* 29 " [ 7 37] x 29" [ 73 7] x 29¾ [ 7 56] C KF 60- 5* 29 " ...

  • Goodman Mfg CKF50Hz - page 6

    CONDENSING UNIT SPECIFICA TIONS 6 NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only. CKF2 4 - 2 * CK F 3 6 - 2 * CKF3 6 -5 * CKF4 8 -5 * CKF 6 0 - 5* CKF7 0 - 5 * C ooli ng C a ...

  • Goodman Mfg CKF50Hz - page 7

    7 COOLING PERFORMANCE DA T A CKF24-2* M O DE L: CKF24- 2* / A 2 4 - 00 - 2 RA C OOL IN G OP E R A T ION O utdoor Am bient Te m per ature 65°F 75°F 85°F 95°F 105°F 115 ° F 118°F 125°F E nte r i ng Indoor W et B ulb Tem pe r ature ID B Air f low 59 63 67 71 59 63 67 71 5 9 6 3 6 7 71 5 9 63 67 71 59 63 67 7 1 5 9 63 67 71 59 53 67 7 1 59 63 6 ...

  • Goodman Mfg CKF50Hz - page 8

    8 COOLING PERFORMANCE DA T A CKF24-2* M O DE L: CKF24- 2* / A 2 4 - 00 - 2 RA C OOL IN G OP E R A T ION O utdoor Am bient Te m per ature 65 75 85 95 105 115 118°F 125°F E nte r i ng Indoor W et B ulb Tem pe r ature I D B * A i r f l o w 5 96 36 77 15 96 36 7 7 1 5 9 6 3 6 7 7 1 5 9 6 3 6 7 7 1 5 96 36 7 7 1 5 96 3 6 7 7 1 5 9 5 3 6 7 7 1 5 9 6 3 ...

  • Goodman Mfg CKF50Hz - page 9

    9 COOLING PERFORMANCE DA T A CKF36-2* M O DEL: CK F36- 2* / A 36- 00- 2 C OOL IN G OP E R ATIO N O utdoor Am bi e nt Tem per a t ur e 65° F 75°F 85° F 95° F 105° F 115° F 1 18° F 125°F E nte r ing I ndoor W et B ulb Te m pe r a t ure ID B A ir flow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 53 67 71 59 63 67 ...

  • Goodman Mfg CKF50Hz - page 10

    10 COOLING PERFORMANCE DA T A CKF36-2* M O DEL: CK F36- 2* / A 36- 00- 2 C OOL IN G OP E R ATIO N O utdoor Am bi e nt Tem per a t ur e 65 75 85 95 105 115 11 8°F 125 °F E nte r ing I ndoor W et B ulb Te m pe r a t ure I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 9 6 3 6 7 7 1 5 9 6 3 6 7 7 1 5 96 36 77 15 96 3 6 7 7 1 5 9 5 3 6 7 7 1 5 9 6 3 6 ...

  • Goodman Mfg CKF50Hz - page 11

    11 COOLING PERFORMANCE DA T A CKF36-5* M O DEL: C KF36-5* / A R36-00- 2 C OOL I N G OP E R AT ION O utdoo r Am bie nt Te m pe r ature 65° F 75° F 85° F 95° F 105°F 1 15°F 118° F 125°F E nte r ing I ndoor Wet B ulb Te m pe r ature ID B Air fl ow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 5 3 67 71 59 63 67 71 ...

  • Goodman Mfg CKF50Hz - page 12

    12 COOLING PERFORMANCE DA T A CKF36-5* M O DEL: C KF36-5* / A R36-00- 2 C OOL I N G OP E R AT ION O utdoo r Am bie nt Te m pe r ature 65 75 85 95 1 05 115 118°F 125°F E nte r ing I ndoor Wet B ulb Te m pe r ature I D B * A i r f l o w 5 96 36 77 15 96 36 7 7 1 5 9 6 3 6 7 7 1 5 9 6 3 6 7 7 1 5 9 6 36 7 7 1 5 96 3 6 7 7 1 5 9 5 3 6 7 7 1 5 9 6 3 6 ...

  • Goodman Mfg CKF50Hz - page 13

    13 COOLING PERFORMANCE DA T A CKF48-5* MO DEL : C K F48-5* / A 48-00- 2 C OOL IN G OP E R AT ION O utdoor Am bient Te m pe rature 65° F 75° F 85°F 95° F 105°F 115°F 118°F 125°F E n te ring Indoo r We t B ulb Te m pe r atur e ID B Air flo w 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 53 67 71 59 63 67 71 M Bh 4 ...

  • Goodman Mfg CKF50Hz - page 14

    14 COOLING PERFORMANCE DA T A CKF48-5* MO DEL : C K F48-5* / A 48-00- 2 C OOL IN G OP E R AT ION O utdoor Am bient Te m pe rature 65 75 85 95 105 115 118°F 125°F E n te ring Indoo r We t B ulb Te m pe r atur e I D B * A i r f l o w 5 96 36 77 15 96 36 7 7 1 5 9 6 3 6 77 15 9 6 3 6 7 7 1 5 96 36 7 7 1 5 96 3 6 7 7 1 5 9 5 3 6 7 7 1 5 9 6 3 6 7 7 1 ...

  • Goodman Mfg CKF50Hz - page 15

    15 COOLING PERFORMANCE DA T A CKF60-5* MO D EL: C KF6 0- 5* / A 60-00- 2 C OOL IN G OP E R AT ION O ut door Am bient Te m pe r ature 65° F 75°F 85° F 95°F 105°F 115° F 118° F 125°F E nte r ing Indoor W et B ulb Te m pe r a t ur e ID B Air f lo w 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 53 67 71 59 63 67 71 ...

  • Goodman Mfg CKF50Hz - page 16

    16 COOLING PERFORMANCE DA T A CKF60-5* MO D EL: C KF6 0- 5* / A 60-00- 2 C OOL IN G OP E R AT ION O ut door Am bient Te m pe r ature 65 75 85 95 105 115 118°F 125° F E nte r ing Indoor W et B ulb Te m pe r a t ur e I D B * A i r f l o w 5 96 36 77 15 96 3 6 77 15 9 6 3 6 77 15 9 6 3 6 7 7 1 5 96 36 7 7 1 5 96 3 6 7 7 1 5 9 5 3 6 7 7 1 5 9 6 3 6 7 ...

  • Goodman Mfg CKF50Hz - page 17

    17 COOLING PERFORMANCE DA T A CKF70-5* MO D EL : C K F70 -5* / A60-00-2 C OOL IN G OP E R A T ION O utdoor Am bient Te m pe r at ure 65°F 75°F 85°F 95°F 105°F 115°F 118°F 125°F E nte r i ng Indoor W e t B ulb Tem pe rature ID B Air f low 59 6 3 67 71 59 63 67 71 59 63 67 71 5 9 63 67 71 5 9 63 67 71 59 63 67 71 59 53 67 71 59 63 67 7 1 M Bh ...

  • Goodman Mfg CKF50Hz - page 18

    18 COOLING PERFORMANCE DA T A CKF70-5* MO D EL : C K F70 -5* / A60-00-2 C OOL IN G OP E R A T ION O utdoor Am bient Te m pe r at ure 65 75 85 95 105 1 15 11 8°F 12 5°F E nte r i ng Indoor W e t B ulb Tem pe rature I D B * A i r f l o w 5 9 6 3 6 7 7 1 5 9 6 3 6 7 7 1 5 9 6 3 6 7 7 1 5 9 6 36 7 7 1 5 9 6 3 6 7 7 1 5 9 6 3 6 7 7 15 95 36 77 15 96 3 ...

  • Goodman Mfg CKF50Hz - page 19

    19 PERFORMANCE DA T A PERFORMANCE TEST All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoo r air cubic feet per minute (CFM) as listed in the Performance Data Sheets: If conditions vary from this, results will change as follows: 1. As indoor dry bulb temperatures increase, a ...

  • Goodman Mfg CKF50Hz - page 20

    WIRING DIAGRAMS 20 HIGH VOL T A GE! DISCONNECT ALL POWER BEFORE SERVICING OR INS T A LLING THIS UNIT . MUL TIPL E POW ER SOURCES M A Y BE P RESENT . F AI LURE TO DO SO MA Y CAUS E PROPERTY DAM AGE, PERSO NAL INJURY OR DEA TH. Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. CKF[24-36]M/N/P ...

  • Goodman Mfg CKF50Hz - page 21

    WIRING DIAGRAMS 21 HIGH VOL T A GE! DISCONNECT ALL POWER BEFORE SERVICING OR INS T A LLING THIS UNIT . MUL TIPL E POW ER SOURCES M A Y BE P RESENT . F AI LURE TO DO SO MA Y CAUS E PROPERTY DAM AGE, PERSO NAL INJURY OR DEA TH. Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. CKF[48-70]M/N/P ...

Fabricante Goodman Mfg Categoría Air Conditioner

Los documentos del dispositivo Goodman Mfg CKF50Hz que obtenemos del fabricante se pueden dividir en varios grupos. Entre ellos están::
- dibujos técnicos Goodman Mfg
- manuales de instrucciones CKF50Hz
- hojas de producto Goodman Mfg
- folletos informativos
- o etiquetas energéticas Goodman Mfg CKF50Hz
Todos son importantes, pero lo más importante desde el punto de vista del usuario de un dispositivo lo encontraremos en el manual de instrucciones Goodman Mfg CKF50Hz.

Un conjunto de documentos determinado como manual de instrucciones se divide también en tipos más detallados, tales como: instrucciones de montaje Goodman Mfg CKF50Hz, instrucciones de servicio, instrucciones cortas o instrucciones de usuario Goodman Mfg CKF50Hz. Dependiendo de la situación debes buscar el documento que necesitas. En nuestra página puedes consultar el manual de instrucciones más popular del producto Goodman Mfg CKF50Hz.

Manuales de instrucciones parecidos

El manual de instrucciones del dispositivo Goodman Mfg CKF50Hz, ¿cómo debería ser?
El manual de instrucciones, también determinado como el manual de usuario o simplemente instrucciones, es un documento técnico que tiene como objetivo ayudar a los usuarios a utilizar Goodman Mfg CKF50Hz. Las instrucciones normalmente las realiza un escritor técnico pero en un lenguaje comprensible para todos los usuarios de Goodman Mfg CKF50Hz.

El manual de instrucciones completo de Goodman Mfg debe contener unos elementos básicos. Una parte de ellos es menos importante, como por ejemplo: la portada / la página principal o las páginas de autor. Sin embargo, lo demás debe facilitarnos la información más importante desde el punto de vista del usuario.

1. Introducción y pistas sobre cómo orientarse con el manual Goodman Mfg CKF50Hz - Al principio de cada manual se deben encontrar las indicaciones acerca de la manera de usar un manual de instrucciones. Debe contener información sobre dónde encontrar el índice Goodman Mfg CKF50Hz, preguntas frecuentes o problemas más comunes – son los apartados más buscados por los usuarios de cada manual de instrucciones.
2. Índice - listados de todos los consejos acerca de Goodman Mfg CKF50Hz que encontraremos en el documento
3. Consejos de uso de las funciones básicas del dispositivo Goodman Mfg CKF50Hz - que deben facilitarnos los primeros pasos durante el uso de Goodman Mfg CKF50Hz
4. Troubleshooting - una secuencia sistematizada de acciones que nos ayudará a diagnosticar los problemas más importantes con Goodman Mfg CKF50Hz
5. FAQ - las preguntas frecuentes
6. Datos de contacto Información acerca de cómo encontrar los datos de contacto del fabricante / servicio de Goodman Mfg CKF50Hz en cada país si no somos capaces de solucionar el problema por nuestra cuenta.

¿Tienes una pregunta acerca de Goodman Mfg CKF50Hz?

Utiliza el formulario que se encuentra abajo

Si con la ayuda del manual de instrucciones encontrado no has podido solucionar tu problema con Goodman Mfg CKF50Hz, haz una pregunta utilizando el formulario que se encuentra abajo. Si alguno de los usuarios ha tenido un problema parecido con Goodman Mfg CKF50Hz probablemente compartirá una forma de solucionarlo.

Copia el texto de la imagen

Comentarios (0)