    Manual 2100-508 Page 1 of 25 INST ALLA TION INSTRUCTIONS W ALL MOUNTED P ACKAGE AIR CONDITIONERS MODELS W18A1 W18L1 W24A1 W24L1 W30A1 W30L1 W36A1 W36L1 W42A1 W42L1 W48A1 W48L1 W60A1 W60L1 Manual : 2100-508 Supersedes: NEW File: V olume III T ab 16 Date: 07-07-08 Bard Manufacturing Company , Inc. Bryan, Ohio 43506 Since 1914...Moving ahead just as p ...

  • Bard W48A1 - page 2

    Manual 2100-508 Page 2 of 25 Content s Figures Figure 1 Fresh Air Damper Assembly ................... 5 Figure 2 Unit Dimensions ...................................... 7 Figure 3A Mounting Instructions .............................. 8 Figure 3B Mounting Instructions - W18, W24, W30, W36 .... 9 Figure 3C Mounting Instructions - W42, W48, W60 ..... 1 ...

  • Bard W48A1 - page 3

    Manual 2100-508 Page 3 of 25 GETTING OTHER INFORMA TION AND PUBLICA TIONS These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard. National Ele ctrical Code ...................... ANSI/ ...

  • Bard W48A1 - page 4

    Manual 2100-508 Page 4 of 25 W ALL MOUNT GENERAL INFORMA TION AIR CONDITIONER WALL MOUNT MODEL NOMENCLATURE W 42 A 1– A 10 X X X X X A NOTE: Vent options X, B and M are without exhaust capability. May require separate field supplied barometric relief in buildi ng. SHIPPING DAMAGE Upon receipt of equipment, the carton should be checked for externa ...

  • Bard W48A1 - page 5

    Manual 2100-508 Page 5 of 25 DUCT WORK All duct work, supply and return, must be properly sized for the design airflow requirement of the equipment. Air Conditioning Contractors of America (ACCA) is an excellent guide to proper sizing. All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conse ...

  • Bard W48A1 - page 6

    Manual 2100-508 Page 6 of 25 s s e c c A e c i v r e S r o f d e r i u q e R s e c n a r a e l C w o l f r i A r e s n e d n o C e t a u q e d A d n a S L E D O M E D I S T F E L E D I S T H G I R A 6 3 W , A 0 3 W , A 4 2 W , A 8 1 W " 5 1 " 0 2 L 6 3 W , L 0 3 W , L 4 2 W , L 8 1 W " 0 2 " 5 1 A 0 6 W , A 8 4 W , A 2 4 W " ...

  • Bard W48A1 - page 7

    Manual 2100-508 Page 7 of 25 SIDE VIEW BACK VIEW FRONT VIEW *Optional top outlet (factory installed only) for W30A and W36A models only. FIGURE 2 SIDE VIEW FRONT VIEW BACK VIEW ) l a n i m o N ( s t n e m e r i u q e R n o i t a l l a t s n I d n a l a r u t c e t i h c r A r o f t i n U c i s a B f o s n o i s n e m i D L E D O M H T D I W ) W ( H ...

  • Bard W48A1 - page 8

    Manual 2100-508 Page 8 of 25 FIGURE 3A W18A1, W18L1, W24A1, W24L1 MOUNTING INSTRUCTIONS ...

  • Bard W48A1 - page 9

    Manual 2100-508 Page 9 of 25 FIGURE 3B W30A1, W30L1, W36A1, W36L1 MOUNTING INSTRUCTIONS ...

  • Bard W48A1 - page 10

    Manual 2100-508 Page 10 of 25 FIGURE 3C W42A1, W42L1, W48A1, W48L1, W60A1, W60L1 MOUNTING INSTRUCTIONS ...

  • Bard W48A1 - page 11

    Manual 2100-508 Page 11 of 25 FIGURE 4 ELECTRIC HEAT CLEARANCE W30A1, W30L1, W36A1, W36L1, W42A1, W42L1, W48A1, W48L1, W60A1, W60L1 W ARNING A minimum of 1/4 inch clearance must be maintained between the supply air duct and combustible materials. This is required for the first 3 feet of ducting. It is important to insure that the 1/4 inch minimum s ...

  • Bard W48A1 - page 12

    Manual 2100-508 Page 12 of 25 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 6 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 – MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS, FIGURE 2, FOR ACTUAL DIMENSIONS IF REQUIRED IF REQUIRED ...

  • Bard W48A1 - page 13

    Manual 2100-508 Page 13 of 25 FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS ...

  • Bard W48A1 - page 14

    Manual 2100-508 Page 14 of 25 WIRING – MAIN POWER Refer to the unit rating plate for wire sizing information and maximum fuse or “HACR” type circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. Depending on the installed KW ...

  • Bard W48A1 - page 15

    Manual 2100-508 Page 15 of 25 ST ART UP THESE UNITS REQUIRE R-410A REFRIGERANT AND POL YOL ESTER OIL. GENERAL: 1. Use separate service equipment to avoid cross contamination of oil and refrigerants. 2. Use recovery equipment rated for R-410A refrigerant. 3. Use manifold gauges rated for R-410A (800 psi/250 psi low). 4. R-410A is a binary blend of H ...

  • Bard W48A1 - page 16

    Manual 2100-508 Page 16 of 25 ST ART UP (Continued) IMPORTANT INSTALLER NOTE For improved start up performance wash the indoor coil with a dish washing detergent. HIGH PRESSURE SWITCH All W**A/W**L wall mounted air conditioner series models are supplied with a remote reset for the high and low pressure switch. If tripped, this pressure switch may b ...

  • Bard W48A1 - page 17

    Manual 2100-508 Page 17 of 25 SEQUENCE OF OPERATION COOLING – Circuit R-Y makes at thermostat pulling in compressor contactor, starting the compressor and outdoor motor. The G (indoor motor) circuit is automatically completed on any call for cooling operation or can be energized by manual fan switch on subbase for constant air circulation. On a c ...

  • Bard W48A1 - page 18

    Manual 2100-508 Page 18 of 25 TROUBLESHOOTING FIGURE 8 FAN BLADE SETTING MIS-1724 TABLE 1 FAN BLADE DIMENSION REMOVAL OF FAN SHROUD 1. Disconnect all power to the unit. 2. Remove the screws holding both grilles, one on each side of unit, and remove grilles. 3. Remove screws holding fan shroud to condenser and bottom. Nine (9) screws. 4. Unwire cond ...

  • Bard W48A1 - page 19

    Manual 2100-508 Page 19 of 25 TABLE 3 COOLING PRESSURE TABLE Air Temperature Entering Outdoor Coil °F Low side pressure ± 2 PSIG High side pressure ± 5 PSIG Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge being in the system, the charge should be removed, system evacuated ...

  • Bard W48A1 - page 20

    Manual 2100-508 Page 20 of 25 TABLE 4 1 Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. 2 Based on 75C copper wire. All wiring must conform to the National Electrical Code and all local codes. 3 These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductor ...

  • Bard W48A1 - page 21

    Manual 2100-508 Page 21 of 25 TABLE 5 1 Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. 2 Based on 75C copper wire. All wiring must conform to the National Electrical Code and all local codes. 3 These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductor ...

  • Bard W48A1 - page 22

    Manual 2100-508 Page 22 of 25 TABLE 6 RECOMMENDED AIRFLOW TABLE 7 INDOOR BLOWER PERFORMANCE TABLE 8 MAXIMUM ESP OF OPERATION ELECTRIC HEAT ONLY V alues shown are for units equipped with st andard 1-inch throwaway filter or 1-inch washable filter . Derate ESP by .15 for 2-inch pleated filters. l e d o M d e t a R * M F C d e t a R * P S E d e d n e ...

  • Bard W48A1 - page 23

    Manual 2100-508 Page 23 of 25 TABLE 9 ELECTRIC HEAT s l e d o M1 - V 0 4 21 - V 8 0 23 - V 0 4 23 - V 8 0 23 - V 0 6 4 W Ks p m AH U T Bs p m AH U T Bs p m AH U T Bs p m AH U T Bs p m AH U T B 47 . 6 10 5 6 3 14 . 4 10 4 2 0 1 58 . 0 25 6 0 7 11 . 8 10 0 8 2 1 64 . 4 10 0 5 0 25 . 2 10 6 3 5 12 . 70 0 5 0 2 83 . 3 30 0 3 7 28 . 8 25 7 4 0 2 97 . 1 ...

  • Bard W48A1 - page 24

    Manual 2100-508 Page 24 of 25 W18*1-A W24*1-A W24*1-B W24*1-C W30*1-A W30*1-B W30*1-C W36*1-A W36*1-B W36*1-C W42*1-A W42*1-B W42*1-C W48*1-A W48*1-B W48*1-C W60*1-A W60*1-B W60*1-C TABLE 10 OPTIONAL ACCESSORIES r e b m u N t r a P 5 0 A - 2 0 A W H EX X 8 0 A - A 2 0 W H EX X 0 1 A - A 2 0 A W H EX X 6 0 B - 4 2 A W H EX 6 0 C - B 4 2 H W H EX 5 0 ...

  • Bard W48A1 - page 25

    Manual 2100-508 Page 25 of 25 TABLE 11 VENT & CONTROL OPTIONS W18, W24 W30, W36 W42, W48, W60 r e b m u N t r a Pn o i t p i r c s e D 4 1 - C M CT D O XXX 5 1 - C M C) e s a h P - 1 V 0 3 2 ( t i K t r a t S XXX 3 2 - C M CC D DX X 4 2 - C M CC D DX 8 2 - C M CC A L XXX 2 - D A F Bd r a d n a t S - r e p m a D r i A h s e r F c i r t e m o r a ...

Fabricante Bard Categoría Air Conditioner

Los documentos del dispositivo Bard W48A1 que obtenemos del fabricante se pueden dividir en varios grupos. Entre ellos están::
- dibujos técnicos Bard
- manuales de instrucciones W48A1
- hojas de producto Bard
- folletos informativos
- o etiquetas energéticas Bard W48A1
Todos son importantes, pero lo más importante desde el punto de vista del usuario de un dispositivo lo encontraremos en el manual de instrucciones Bard W48A1.

Un conjunto de documentos determinado como manual de instrucciones se divide también en tipos más detallados, tales como: instrucciones de montaje Bard W48A1, instrucciones de servicio, instrucciones cortas o instrucciones de usuario Bard W48A1. Dependiendo de la situación debes buscar el documento que necesitas. En nuestra página puedes consultar el manual de instrucciones más popular del producto Bard W48A1.

Manuales de instrucciones parecidos

El manual de instrucciones del dispositivo Bard W48A1, ¿cómo debería ser?
El manual de instrucciones, también determinado como el manual de usuario o simplemente instrucciones, es un documento técnico que tiene como objetivo ayudar a los usuarios a utilizar Bard W48A1. Las instrucciones normalmente las realiza un escritor técnico pero en un lenguaje comprensible para todos los usuarios de Bard W48A1.

El manual de instrucciones completo de Bard debe contener unos elementos básicos. Una parte de ellos es menos importante, como por ejemplo: la portada / la página principal o las páginas de autor. Sin embargo, lo demás debe facilitarnos la información más importante desde el punto de vista del usuario.

1. Introducción y pistas sobre cómo orientarse con el manual Bard W48A1 - Al principio de cada manual se deben encontrar las indicaciones acerca de la manera de usar un manual de instrucciones. Debe contener información sobre dónde encontrar el índice Bard W48A1, preguntas frecuentes o problemas más comunes – son los apartados más buscados por los usuarios de cada manual de instrucciones.
2. Índice - listados de todos los consejos acerca de Bard W48A1 que encontraremos en el documento
3. Consejos de uso de las funciones básicas del dispositivo Bard W48A1 - que deben facilitarnos los primeros pasos durante el uso de Bard W48A1
4. Troubleshooting - una secuencia sistematizada de acciones que nos ayudará a diagnosticar los problemas más importantes con Bard W48A1
5. FAQ - las preguntas frecuentes
6. Datos de contacto Información acerca de cómo encontrar los datos de contacto del fabricante / servicio de Bard W48A1 en cada país si no somos capaces de solucionar el problema por nuestra cuenta.

¿Tienes una pregunta acerca de Bard W48A1?

Utiliza el formulario que se encuentra abajo

Si con la ayuda del manual de instrucciones encontrado no has podido solucionar tu problema con Bard W48A1, haz una pregunta utilizando el formulario que se encuentra abajo. Si alguno de los usuarios ha tenido un problema parecido con Bard W48A1 probablemente compartirá una forma de solucionarlo.

Copia el texto de la imagen

Comentarios (0)