    DESCRIPTION YORK Sunline 2000 Heat Pumps are convertible single package units with a common cabinet and common roof curb for the 3, 4 and 5 ton sizes. The units were designed for residential and light commercial applications. They can easily be installed on a roof curb, slab, roof jack or frame. All units are self--contained and assembled on rigid ...

  • York 2000 - page 2

    SYSTEM PROTECTION -- Crankcase heaters and internal compressor protection are standard on all compressors. Every unit has a liquid line filter--drier , low pressure switch, high pressure switch and high temperature switch to protect all system components. A suction line freezestat is supplied on all three--phase units to protect against loss of cha ...

  • York 2000 - page 3

    036-21564-003-A-1005 Unitary Products Group 3 MODELS BCH 036 048 060 SUPPL Y AIR BLOWER CENTRIFUGAL BLOWER (Dia. x Wd. in.) 12 x 10 12 x 10 12 x 10 F AN MOTOR HP (DIRECT -DRIVE) 1 2 3 4 1 F AN MOTOR HP (BEL T -DRIVE) 1.5 1.5 1.5 INDOOR COIL ROWS DEEP 4 3 3 FINS PER INCH 16 15 15 F ACE AREA (Sq. Ft.) 4.3 5.1 5.1 OUTDOOR FA N PROPELLER DIA. (in.) 22 ...

  • York 2000 - page 4

    036-21564-003-A-1005 4 Unitary Products Group COOLING CAP ACITIES - 3 TON (BCH036) Air On Indoor Coil T emperature of Air on Outdoor Coil 85 ° F9 5 ° F To t a l Cap. 1 MBH Power Input 2 KW Sensible Capacity 1 , MBH To t a l Cap. 1 MBH Power Input 2 KW Sensible Capacity 1 , MBH CFM WB ° F Entering Dry Bulb, ° F Entering Dry Bulb, ° F 86 83 80 7 ...

  • York 2000 - page 5

    036-21564-003-A-1005 Unitary Products Group 5 COOLING CAP ACITIES - 4 TON (BCH048) Air On Indoor Coil T emperature of Air on Outdoor Coil 85 ° F9 5 ° F To t a l Cap. 1 MBH Power Input 2 KW Sensible Capacity 1 , MBH To t a l Cap. 1 MBH Power Input 2 KW Sensible Capacity 1 , MBH CFM WB ° F Entering Dry Bulb, ° F Entering Dry Bulb, ° F 86 83 80 7 ...

  • York 2000 - page 6

    036-21564-003-A-1005 6 Unitary Products Group COOLING CAP ACITIES - 5 TON (BCH060) Air On Indoor Coil T emperature of Air on Outdoor Coil 85 ° F9 5 ° F To t a l Cap. 1 MBH Power Input 2 KW Sensible Capacity 1 , MBH To t a l Cap. 1 MBH Power Input 2 KW Sensible Capacity 1 , MBH CFM WB ° F Entering Dry Bulb, ° F Entering Dry Bulb, ° F 86 83 80 7 ...

  • York 2000 - page 7

    036-21564-003-A-1005 Unitary Products Group 7 HEA TING CAP ACITIES BCH036 CFM RET . AIR CAP OUTDOOR AIR TEMPERATURE, ° F (72% RH) ° F & K W - 1 0 0 1 02 03 04 05 06 0 1750 55 MBH 13.1 16.4 23.5 29.1 30.2 41.7 47.0 48.2 KW 2.9 3.0 3.2 3.3 3.5 3.7 3.8 3.9 70 MBH 1 1.9 15.0 21.5 26.7 27.7 38.2 43.1 44.1 KW 3.0 3.1 3.4 3.4 3.6 3.8 3.9 4.1 80 MBH ...

  • York 2000 - page 8

    036-21564-003-A-1005 8 Unitary Products Group SUPPL Y AIR BLOWER PERFORMANCE - BCH036 & 048 with Belt-Drive MODEL BCH AIR FLOW CFM Available External S tatic Pressure - IWG* 0.20 0.30 0.40 0.50 0.60 0.70 0.80 RPM W atts RPM W atts RPM W atts RPM Watt s RPM W atts RPM W atts RPM W atts 048 2000 843 860 880 925 919 1005 956 1065 993 1 145 1030 1 ...

  • York 2000 - page 9

    036-21564-003-A-1005 Unitary Products Group 9 SUPPL Y AIR BLOWER PERFORMANCE - BCH036, 048 & 060 with Direct-Drive SUPPL Y AIR BLOWER PERFORMANCE - BCH060 with Belt-Drive MODEL BCH AIR FLOW CFM Available External S tatic Pressure - IWG* 0.20 0.30 0.40 0.50 0.60 0.70 0.80 RPM W atts RPM W atts RPM W atts RPM Watt s RPM W atts RPM W atts RPM W at ...

  • York 2000 - page 10

    036-21564-003-A-1005 10 Unitary Products Group HEA TER / CFM LIMIT ATIONS HEA TER SIZE NOM. KW VOL TAGE 1 UNIT MODEL SIZE, NOMINAL TONS 345 MINIMUM SUPPL Y AIR CFM 5 7 10 15 20 30 208 / 230-1-60 1,100 1,100 1,200 1,200 1,300 2 - 1,300 1,300 1,300 1,300 1,300 2 - 1,600 1,600 1,600 1,600 1,600 1,600 5 7 10 15 20 30 208 / 230-3-60 1,100 1,100 1,200 1, ...

  • York 2000 - page 11

    036-21564-003-A-1005 Unitary Products Group 11 ELECTRICAL DA T A - Basic Unit (Direct-Drive) MODEL BCH POWER SUP - PL Y VOL TAGE LIMIT ATIONS (SEE NOTE 1) COMPRESSOR OUTDOOR FA N MOTOR, FLA SUPPL Y AIR BLOWER MOTOR, FLA MINIMUM CIRCUIT AMP ACITY MAX. FUSE SIZE, (SEE NOTE 2) AMPS MAX. HACR BREAKER SIZE, AMPS MIN. MAX. RLA LRA 036 208/230-1-60 208/23 ...

  • York 2000 - page 12

    036-21564-003-A-1005 12 Unitary Products Group MODEL BCH POWER SUPPL Y HEA TER ACCESSORY MODEL NUMBER SUPPL Y AIR BLOWER MOTOR FLA ELECTRIC HEA TERS MINIMUM CIRCUIT AMP ACITY MAX. FUSE SIZE 1 AMPS MAX. SIZE HACR 2 BREAKER AMPS KW ST AGES TO T AL AMPS 048 208-1-60 2CE04510506 2CE04510706 2CE0451 1006 2CE0451 1506 2CE04512006 5.0 4.0 5.6 8.0 1 1.9 15 ...

  • York 2000 - page 13

    036-21564-003-A-1005 Unitary Products Group 13 ELECTRICAL DA T A - Basic Unit (Belt-Drive) MODEL BCH POWER SUP - PL Y VOL TAGE LIMIT ATIONS (SEE NOTE 1) COMPRESSOR OUTDOOR FA N MOTOR, FLA SUPPL Y AIR BLOWER MOTOR, FLA MINIMUM CIRCUIT AMP ACITY MAX. FUSE SIZE, (SEE NOTE 2) AMPS MAX. HACR BREAKER SIZE, AMPS MIN. MAX. RLA LRA 036 208/230-1-60 208/230- ...

  • York 2000 - page 14

    036-21564-003-A-1005 14 Unitary Products Group MODEL BCH POWER SUPPL Y HEA TER ACCESSORY MODEL NUMBER SUPPL Y AIR BLOWER MOTOR FLA ELECTRIC HEA TERS MINIMUM CIRCUIT AMP ACITY MAX. FUSE SIZE 1 AMPS MAX. SIZE HACR 2 BREAKER AMPS KW ST AGES TO T AL AMPS 048 208-1-60 2CE04510506 2CE04510706 2CE0451 1006 2CE0451 1506 2CE04512006 8.6 4.0 5.6 8.0 1 1.9 15 ...

  • York 2000 - page 15

    036-21564-003-A-1005 Unitary Products Group 15 CLEARANCES Front 24" Back 12" (Less Economizer) 36" (With Economizer or Fixed Air/Motorized Air Damper) Left Side (Filter Access) 24" (Less Economizer) 36" (With Economizer) Right Side (OD Coil) 24" Below Unit 1 2 0" Above Unit 2 72" (For Outdoor Air Discharge) N ...

  • York 2000 - page 16

    036-21564-003-A-1005 16 Unitary Products Group UNIT DIMENSIONS - CONT'D. ( B C H-3 ,4&5T O N ) REAR VIEW SIDE SUPPL Y AND RETURN AIR DUCT OPENINGS 17 1 2 3 11 1 2 4 5 8 17 1 2 11 1 2 7 7 8 6 1 2 DUCT COVERS - Units are shipped with all air duct openings covered. For side duct applications; 1.Remove and discard the supply and return air duc ...

  • York 2000 - page 17

    036-21564-003-A-1005 Unitary Products Group 17 ROOF CURB DIMENSIONS B C H-3 ,4&5T O N COMPRESSOR AND OUTDOOR COIL END OF UNIT DUCT SIZES: Supply Air = 19" x 19" Return Air = 19" x 19" 82 1 4 40 3 4 BACK APPROXIMA TE CENTER OF GRA VITY 44 7 8 FRONT 19 3 4 CENTER OF GRA VITY CORNER CORNER CORNER OPTIONS / ACCESSORIES Electric ...

  • York 2000 - page 18

    FIELD--INST ALLED ACCESSORIES SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZER -- Includes a slide--in/plug--in damper assembly with fully modulating spring return motor actuator capable of introducing up to 100% outdoor air , one outdoor air electronic enthalpy sensor and a rainhood with filters. The rainhood is painted to match the basic unit and must ...

  • York 2000 - page 19

    036-21564-003-A-1005 Unitary Products Group 19 TYPICAL APPLICATIONS TYPICAL ROOF-TOP INST ALLA TION ROOF JACK INST ALLA TION ROOF CURB INST ALLA TION SLAB ON GROUND INST ALLA TION FIELD-SUPPLIED DISCONNECT SWITCH TO POWER SUPPL Y CONTROL WIRING TO INDOOR THERMOST A T ROOF CURB SUPPL Y AIR DUCT RETURN AIR DUCT CONDENSA TE TRAP ...

  • York 2000 - page 20

    GENERAL DESCRIPTION Units shall be factory--assembled, single packaged Heat Pumps, designed for outdoor mounted inst allation. Units shall have minimum SEER ratings of 10.0. They shall have built in field convertible duct connections for down discharge supply/return or horizontal discharge supply/return, and be available with factory installed opti ...

  • York 2000 - page 21

    (1) -- Loss--of--charge/Low--pressure switch. (2) -- High--pressure switch. If any of the above safety devices trip, an LED (light emitting diode) indicator shall illuminate. C. Unit shall incorporate “AUTO RESET” compressor over--temperature, over--current protection. D. Unit shall operate with conventional thermostat designs and have a low vo ...

  • York 2000 - page 22

    6. THERMOST A TS -- Multiple models available from A.C.O., M.C.O., Electronic or Electrical Mechanical ver - sions. 7. ANTI--RECYCLE TIMER -- Assures 5--minute off--time between compressor cycles. 8. ELECTRIC HEA T -- Slide--in design, provides single point power and ranges from 5 to 30 KW . OTHER F ACTOR Y INST ALLED OPTIONS 1. HIGH PERFORMANCE BE ...

  • York 2000 - page 23

    036-21564-003-A-1005 Unitary Products Group 23 ...

  • York 2000 - page 24

    8QLWDU3URGXFWV*URXS < RUN'ULYH1RUPDQ2. 6XEMHFWWRFKDQJHZLWKRXWQRWLFH3ULQWHGLQ86$ &RSULJKWE< RUN,QWHUQDWLRQDO&RUSRUDWLRQ$OO5LJKWV5HVHUYHG $? ...

Fabricante York Categoría Heat Pump

Los documentos del dispositivo York 2000 que obtenemos del fabricante se pueden dividir en varios grupos. Entre ellos están::
- dibujos técnicos York
- manuales de instrucciones 2000
- hojas de producto York
- folletos informativos
- o etiquetas energéticas York 2000
Todos son importantes, pero lo más importante desde el punto de vista del usuario de un dispositivo lo encontraremos en el manual de instrucciones York 2000.

Un conjunto de documentos determinado como manual de instrucciones se divide también en tipos más detallados, tales como: instrucciones de montaje York 2000, instrucciones de servicio, instrucciones cortas o instrucciones de usuario York 2000. Dependiendo de la situación debes buscar el documento que necesitas. En nuestra página puedes consultar el manual de instrucciones más popular del producto York 2000.

Manuales de instrucciones parecidos

El manual de instrucciones del dispositivo York 2000, ¿cómo debería ser?
El manual de instrucciones, también determinado como el manual de usuario o simplemente instrucciones, es un documento técnico que tiene como objetivo ayudar a los usuarios a utilizar York 2000. Las instrucciones normalmente las realiza un escritor técnico pero en un lenguaje comprensible para todos los usuarios de York 2000.

El manual de instrucciones completo de York debe contener unos elementos básicos. Una parte de ellos es menos importante, como por ejemplo: la portada / la página principal o las páginas de autor. Sin embargo, lo demás debe facilitarnos la información más importante desde el punto de vista del usuario.

1. Introducción y pistas sobre cómo orientarse con el manual York 2000 - Al principio de cada manual se deben encontrar las indicaciones acerca de la manera de usar un manual de instrucciones. Debe contener información sobre dónde encontrar el índice York 2000, preguntas frecuentes o problemas más comunes – son los apartados más buscados por los usuarios de cada manual de instrucciones.
2. Índice - listados de todos los consejos acerca de York 2000 que encontraremos en el documento
3. Consejos de uso de las funciones básicas del dispositivo York 2000 - que deben facilitarnos los primeros pasos durante el uso de York 2000
4. Troubleshooting - una secuencia sistematizada de acciones que nos ayudará a diagnosticar los problemas más importantes con York 2000
5. FAQ - las preguntas frecuentes
6. Datos de contacto Información acerca de cómo encontrar los datos de contacto del fabricante / servicio de York 2000 en cada país si no somos capaces de solucionar el problema por nuestra cuenta.

¿Tienes una pregunta acerca de York 2000?

Utiliza el formulario que se encuentra abajo

Si con la ayuda del manual de instrucciones encontrado no has podido solucionar tu problema con York 2000, haz una pregunta utilizando el formulario que se encuentra abajo. Si alguno de los usuarios ha tenido un problema parecido con York 2000 probablemente compartirá una forma de solucionarlo.

Copia el texto de la imagen

Comentarios (0)