Manual de instrucciones Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit

28 de páginas 0.57 mb
Descargar

Pasar a la página of 28

Summary
  • Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit - page 1

    All information contained herein is subject to change without notice. I NST ALLA TION I NSTRUCTIONS F OR L IGHT C OMMERCIAL S ELF -C ONT AINED P ACKAGED H EA TING & C OOLING U NIT 3 T ON - 6 T ON CPC/CPH S ERIES Goodman Manufacturing Company , L.P . IO-399B 5151 Felipe, Suite 500, Houston, TX 77056 7/12 www .goodmanmfg.com www .amana-hac.com © ...

  • Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit - page 2

    2 REPLACEMENT PARTS O RDERING P ARTS When reporting shortages or damages, or ordering rep air part s, give the complete unit model and serial numbers as stamped on the unit’ s nameplate. Replacement parts for this appliance are available through your contractor or local distributor . For the location of your nearest distributor , consult the whit ...

  • Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit - page 3

    3 T HIS UNIT MU ST NOT BE USED AS A “ CONST RUC TION HEATE R ” DURING THE FINISHING PHAS ES OF CONST RUC TION ON A NEW STRUCT UR E . T HIS TYPE OF USE MA Y RESU LT IN PREMAT UR E FAILURE OF THE UNIT DUE TO EXT REME LY LOW RETURN AIR TEMP ERAT URES AND EXPO SURE TO CORR OSIVE OR VER Y DIRT Y ATMO SPHE RES . W ARNING HI G H VO L T A G E ! D ISCO ...

  • Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit - page 4

    4 a. Original Bill of Lading, certified copy , or indemnity bond. b. Original paid freight bill or indemnity in lieu thereof. c. Original invoice or certified copy thereof, showing trade and other discounts or reductions. d. Copy of the inspection report issued by carrier representative at the time damage is reported to the carrier . The carrier is ...

  • Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit - page 5

    5 R OOF C URB I NSTALLATIONS O NLY : Curb installations must comply with local codes and should be done in accordance with the established guidelines of the National Roofing Contractors Association. Proper unit installation requires that the roof curb be firmly and permanently attached to the roof structure. Check for adequate fastening method prio ...

  • Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit - page 6

    6 ROOF CURB POST -INST ALLA TION CHECKS After installation, check the top of the curb, duct connection frame and duct flanges to make sure gasket has been ap- plied properly . Gasket should be firmly applied to the top of the curb perimeter , duct flanges and any exposed duct con- nection frame. If gasket is loose, reapply using strong weather resi ...

  • Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit - page 7

    7 Lower unit carefully onto roof mounting curb. While rigging unit, center of gravity will cause condenser end to be lower than supply air end. T o assist in determining rigging requirements, unit weights are shown as follows: A B C D CG SUPP LY RETURN EV APORA TOR COIL CONDENSER COIL COMPRESSOR Y X CORNER & CENTER OF GRAVITY LOCATIONS AB CD CP ...

  • Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit - page 8

    8 T O PRE VENT SEVE RE DAMAG E TO THE BOTTOM OF THE UNIT , DO NOT FORK LIFT UNIT AFTER WOOD STRUT S HAVE BEEN REMOV ED . CAUTION Bring condenser end of unit into alignment with the curb. With condenser end of the unit resting on curb member and using curb as a fulcrum, lower opposite end of the unit until entire unit is seated on the curb. When a r ...

  • Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit - page 9

    9 LOW VOLT AGE BLOCK MA IN PO WER LOW VO L T AGE ENTRANCE POWER THRU THE CURB CONTROL BOX F AILU RE OF UNIT DUE TO OPERATION ON IMP ROPER LINE VOLTAGE OR WITH EXC ESSI VE PHAS E UNBAL ANC E CONSTITUTES PRODUCT ABUSE AND WILL VO I D YO U R WARRANT Y AND MA Y CAUSE SEVE RE DAMAG E TO THE UNIT ELECTR ICAL COMPONE NTS . W ARN I NG Areas Without Conveni ...

  • Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit - page 10

    10 CIRCULA TING AIR AND FIL TERS D UCTWORK The supply duct from the unit through a wall may be installed without clearance. However , minimum unit clearances must be maintained (see “Clearances” section). The supply duct should be provided with an access panel large enough to inspect the air chamber downstream of the heat exchanger . A cover sh ...

  • Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit - page 11

    11 T OOLS R EQUIRED Refrigeration gauge and manifold V oltmeter Clamp-on ammeter Ohmmeter T est lead (Minimum #16 A WG with insulated alligator clips) Air temperature measuring device General refrigeration mechanics’ tools T EMPORARY H EATING O R C OOLING If the unit is to be used for temporary heating or cooling, a “S tartup, Adjustments, and ...

  • Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit - page 12

    12 t = Span length, inches C = Center distance, inches D = Larger sheave diameter , inches d = Smaller sheave diameter , inches h = Deflection height, inches DRIVE BELT TENSION ADJUSTMENT BE L T DR IV E Use d Ne w A , A X Sta nda r d 3.0 to 4 .0 4. 2 ± .5 5. 5 ± . 5 0. 313 DE F L ECT I O N (in) DE F L ECT I O N FO RCE ( lbs) SH EA VE DIAM E T E R ...

  • Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit - page 13

    13 1 1. Slowly raise the heating temperature setting. When the heating first stage makes contact, stop raising the temperature setting.. The compressor , blower and fan should now be running with the reversing valve in the de-energized (heating) position. After giving the unit time to settle out, make sure the unit is supplying heated air . 12. If ...

  • Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit - page 14

    14 E V A P O R A T O R COOLI NG SERV I C E VALVE SERVICE PO RT REVERSI NG VALVE C O N D E N S E R SERV I C E PORT COM PRES S OR SERV I C E PORT ACCUMULAT O R EXPANSION D EVI C E CH ECK VALVE ORI FI CE SERV I C E VALVE CHECK VA LVE ORIFI CE IN DO O R COI L DI ST RIBUTOR OUTD OOR CO I L E V A P O R A T O R HEAT I NG SERV I C E VALVE SERV I C E PORT R ...

  • Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit - page 15

    15 DRIVE ADJUSTMENTS MOTOR SHEA VE ADJUSTMENTS V L , V M , & 2 VP V ARIABLE P ITCH K EY T YPE M OTOR S HEAVES The driving and driven motor sheaves should be in align- ment with each other and the shaft s parallel. V L & V M S HEAVES A DJUSTMENT 1. Loosen set screw “B” using a 5/32" Allen key . 2. Making half or full turns from clos ...

  • Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit - page 16

    16 L UBRICATION The fan shaft bearings, the 1 to 2 HP supply fan motors the condenser fan motors and compressors are permanently lu- bricated. F UNCTIONAL P ARTS Refer to the unit Parts Catalog for a list of functional p arts. Parts are available from your distributor . SERVICE THE FOLLOWING INFORMA TION IS FOR USE BY QUALI- FIED SERVICE AGENCY ONL ...

  • Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit - page 17

    17 APPENDIX A BLOWER PERFORMANCE TABLES DIRECT DRIVE ST ANDARD DOWN SHOT AND HORIZONT AL SPE ED T A P E XTE RNAL S T ATIC PR E SS UR E ( ESP ) in w . c . S T A N DARD CFM A M PS WA T TS R PM 0. 10 1287 1 .66 3 50 770 0. 20 1233 1 .63 3 42 815 0. 30 1176 1 .59 3 32 858 0. 40 1107 1 .55 3 20 891 0. 50 1044 1 .51 3 12 924 0. 60 965 1 .45 2 96 957 0. 1 ...

  • Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit - page 18

    18 APPENDIX A BLOWER PERFORMANCE TABLES DIRECT DRIVE ST ANDARD DOWN SHOT AND HORIZONT AL SPE ED T A P E XTE RNAL S T ATIC PR E SS UR E ( ESP ) in w . c . S T A N DARD CFM A M PS WA T TS R PM 0. 10 1602 2 .48 5 28 835 0. 20 1538 2 .37 5 06 878 0. 30 1474 2 .26 4 84 921 0. 40 1390 2 .15 4 60 950 0. 50 1306 2 .04 4 36 979 0. 10 1805 2 .84 6 20 935 0. ...

  • Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit - page 19

    19 APPENDIX A BLOWER PERFORMANCE TABLES DIRECT DRIVE ST ANDARD CPC/H060 DOWN SHOT SP EED TAP E XTE RNAL S T ATIC PR E SSU R E ( ESP ) in w . c . S T ANDAR D CF M AM P S W ATTS R P M 0. 10 1 334 1.6 5 180 62 7 0. 20 1 286 1.7 5 192 66 5 0. 30 1 212 1.8 3 202 71 5 0. 40 1 144 1.9 4 216 75 9 0. 50 1 077 1.9 9 222 79 2 0. 60 1 039 2.1 0 238 83 0 0. 70 ...

  • Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit - page 20

    20 APPENDIX A BLOWER PERFORMANCE TABLES DIRECT DRIVE ST ANDARD CPC/H060 HORIZONT AL SP EED TAP E XTE RNAL S T AT IC PR E SSU R E ( ESP ) in w . c . STANDAR D CF M AMP S W AT T S R PM 0. 10 1 355 1.57 174 59 9 0. 20 1 281 1.66 182 65 1 0. 30 1 235 1.76 196 69 3 0. 40 1 168 1.81 202 72 6 0. 50 1 118 1.94 218 77 5 0. 60 1 049 2.03 232 81 9 0. 70 9 82 ...

  • Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit - page 21

    21 APPENDIX A BLOWER PERFORMANCE TABLES BEL T DRIVE ST ANDARD DOWN SHOT CP C/H0 36 ST AND AR D BEL T DR I VE DO W N SHO T CFM BHP C FM BHP CFM BH P CF M B HP C F M BHP CFM BH P 0. 2 1 42 4 0. 3 0 1 2 39 0. 2 3 0. 4 152 0 0. 39 1 292 0.2 9 10 73 0 .22 77 9 0 .14 0. 6 14 39 0 .40 119 2 0. 30 9 44 0. 2 1 6 19 0 .1 2 0. 8 1 350 0. 4 2 11 01 0 . 31 86 4 ...

  • Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit - page 22

    22 APPENDIX A BLOWER PERFORMANCE TABLES BEL T DRIVE HIGH ST A TIC DOWN SHOT CP C/H036 HI G H S T AT I C BE L T DRI V E DOWN S HOT CFM BHP C FM BHP CFM BH P CF M B HP C F M BHP CFM BH P 0. 6 16 9 2 0 . 54 1 44 9 0. 4 1 1 1 73 0. 2 9 0. 8 167 8 0. 58 1 397 0.4 4 11 07 0 .3 1 85 4 0 .21 1. 0 16 81 0 . 65 138 1 0. 49 1 078 0. 3 4 7 94 0 .2 2 1. 2 1 681 ...

  • Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit - page 23

    23 APPENDIX A BLOWER PERFORMANCE TABLES BEL T DRIVE ST ANDARD HORIZONT AL CP C/H036 STAND ARD BE L T DRI VE HORI Z O NT AL CFM BHP C FM BHP CF M BH P C FM B HP C FM BHP CFM BH P 0. 2 1 65 8 0. 3 5 1 4 89 0. 2 8 0. 4 1 560 0. 3 6 13 39 0 . 28 112 9 0 .21 0. 6 16 82 0 .47 143 6 0. 36 1 196 0.2 7 9 49 0 .19 0. 8 1 581 0.5 0 13 54 0 .38 109 6 0. 28 8 2 ...

  • Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit - page 24

    24 APPENDIX A BLOWER PERFORMANCE TABLES BEL T DRIVE HIGH ST A TIC HORIZONT AL CP C/H036 HI G H S T AT I C BE L T DRI V E HORIZO NTAL CFM BHP C FM BHP CFM BH P CF M B HP C F M BHP CFM BH P 0. 6 1 74 2 0. 5 0 1 4 31 0. 3 6 0. 8 16 2 6 0 . 52 1 35 7 0. 3 9 1 0 78 0. 2 7 1 161 1 0. 56 1 31 5 0.4 2 10 11 0 . 28 1. 2 16 05 0 . 62 129 9 0. 46 9 76 0. 3 1 ...

  • Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit - page 25

    25 APPENDIX B ELECTRICAL DA T A MIN. M AX . Q TY RLA LRA QTY H P R LA H P FLA 20 8 /2 3 0- 60 - 1 18 7 2 53 1 1 6. 6 7 7 9 1 1 / 4 1. 4 0 DD S T D S T A T I C 1 / 3 2. 5 DD S TD S TA T I C 1 / 3 2.5 BD ST D ST A T I C 1. 0 3 .8 46 0- 60 -3 41 4 5 06 1 5 .7 7 3 8. 0 1 1 / 4 0. 8 0 BD ST D S T A T I C 1 . 0 1. 9 57 5- 60 -3 51 8 6 33 1 3. 8 3 7. 0 1 ...

  • Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit - page 26

    26 A TTENTION INST ALLING PERSONNEL Use only the heater kit specified for each model as dict ated by the table above. APPENDIX B ELECTRICAL DA T A UNIT HE AT ER KIT MO DE L NU M B ER MI N I MU M C F M EH K *-1 0 1 2 5 0 EH K *-1 5 1 2 5 0 EH K *-1 0 1 3 0 0 EH K *-1 5 1 4 0 0 EH K *-1 8 1 4 0 0 EH K *-1 0 1 7 0 0 EH K *-1 5 1 7 0 0 EH K *-2 0 1 8 0 ...

  • Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit - page 27

    27 APPENDIX C UNIT DIMENSIONS HORIZONTAL DISCHARGE VERTICAL DISCHARGE NOTE For horizontal discharge, remove the supply and return duct covers and place them over the vertical discharge return and supply openings. Install with insulation facing up, using the longer screws provided in the literature package. RETURN SUPPL Y 12” 17” 7 3/ 8” 11 ? ...

  • Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit - page 28

    28 Goodman Manufacturing Company , L.P . 5151 Felipe, Suite 500, Houston, TX 77056 www .goodmanmfg.com www .amana-hac.com © 2010,2012 Goodman Manufacturing Company , L.P . ...

Fabricante Goodman Mfg Categoría Air Conditioner

Los documentos del dispositivo Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit que obtenemos del fabricante se pueden dividir en varios grupos. Entre ellos están::
- dibujos técnicos Goodman Mfg
- manuales de instrucciones Light Commercial Self-Contained Packaged Heating & Cooling Unit
- hojas de producto Goodman Mfg
- folletos informativos
- o etiquetas energéticas Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit
Todos son importantes, pero lo más importante desde el punto de vista del usuario de un dispositivo lo encontraremos en el manual de instrucciones Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit.

Un conjunto de documentos determinado como manual de instrucciones se divide también en tipos más detallados, tales como: instrucciones de montaje Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit, instrucciones de servicio, instrucciones cortas o instrucciones de usuario Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit. Dependiendo de la situación debes buscar el documento que necesitas. En nuestra página puedes consultar el manual de instrucciones más popular del producto Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit.

Manuales de instrucciones parecidos

El manual de instrucciones del dispositivo Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit, ¿cómo debería ser?
El manual de instrucciones, también determinado como el manual de usuario o simplemente instrucciones, es un documento técnico que tiene como objetivo ayudar a los usuarios a utilizar Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit. Las instrucciones normalmente las realiza un escritor técnico pero en un lenguaje comprensible para todos los usuarios de Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit.

El manual de instrucciones completo de Goodman Mfg debe contener unos elementos básicos. Una parte de ellos es menos importante, como por ejemplo: la portada / la página principal o las páginas de autor. Sin embargo, lo demás debe facilitarnos la información más importante desde el punto de vista del usuario.

1. Introducción y pistas sobre cómo orientarse con el manual Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit - Al principio de cada manual se deben encontrar las indicaciones acerca de la manera de usar un manual de instrucciones. Debe contener información sobre dónde encontrar el índice Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit, preguntas frecuentes o problemas más comunes – son los apartados más buscados por los usuarios de cada manual de instrucciones.
2. Índice - listados de todos los consejos acerca de Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit que encontraremos en el documento
3. Consejos de uso de las funciones básicas del dispositivo Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit - que deben facilitarnos los primeros pasos durante el uso de Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit
4. Troubleshooting - una secuencia sistematizada de acciones que nos ayudará a diagnosticar los problemas más importantes con Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit
5. FAQ - las preguntas frecuentes
6. Datos de contacto Información acerca de cómo encontrar los datos de contacto del fabricante / servicio de Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit en cada país si no somos capaces de solucionar el problema por nuestra cuenta.

¿Tienes una pregunta acerca de Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit?

Utiliza el formulario que se encuentra abajo

Si con la ayuda del manual de instrucciones encontrado no has podido solucionar tu problema con Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit, haz una pregunta utilizando el formulario que se encuentra abajo. Si alguno de los usuarios ha tenido un problema parecido con Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit probablemente compartirá una forma de solucionarlo.

Copia el texto de la imagen

Comentarios (0)