    1 MODELS BTP(V)-540A, 650A AND 740A COMMERCIAL GAS, GLASS-LINED, TANK-TYPE LOW NOx WA TER HEA TER CONSER CONSER CONSER CONSER CONSER V V V V V A A A A A TIONIST TIONIST TIONIST TIONIST TIONIST ® ® ® ® ® P ART NO. 195033-000 CAUTION TEXT PRINTED OR OUTLINED IN RED CONT AINS IN- FORMA TION RELA TIVE TO YOUR SAFETY . PLEASE READ THOROUGHL Y BEFOR ...

  • A.O. Smith BTP(V)-540A - page 2

    2 FOREWORD The design of the BTP 540A through 740A models complies with ANSI Z21.10.3/CSA 4.3 as an automatic circulating tank and an automatic instantaneous type heater . The BTPV 540A through 740A models are designed for sidewall venting and direct venting applications and are certified under UL 795. Detailed installation diagrams are found in th ...

  • A.O. Smith BTP(V)-540A - page 3

    3 are different from natural gas models. A natural gas heater will not function safely on LP gas and no attempt should be made to convert a heater from natural gas to LP gas. BTP(V)-540A, 650A & 740A models are not available for use with Liquefied Petroleum or LP gas. If you have obtained a BTP(V)-540A, 650A or 740A model with the intent to use ...

  • A.O. Smith BTP(V)-540A - page 4

    4 and sodium chloride (water softener salt), waxes, and process chemicals are typical compounds which are potentially corrosive. Do not store products of this sort near the heater . Also, air which is brought in contact with the heater should no contain any of these chemicals. If necessary , uncontaminated air should be obtained from remote or outs ...

  • A.O. Smith BTP(V)-540A - page 5

    5 Continued manual resetting of high limit control, preceded by higher than usual water temperature is evidence of high limit switch operation. The following are possible reasons for high limit switch operation. • A malfunction in the thermostatic controls would allow the gas valve to remain open causing water temperature to exceed the thermostat ...

  • A.O. Smith BTP(V)-540A - page 6

    6 Units, which are to be installed on combustible flooring, must be supported by a full layer of hollow concrete blocks, from 8” (203.2 mm) to 12” (304.8 mm) thick and extending 12” (304.8 mm) minimum beyond the heater in all directions. The concrete blocks must provide an unbroken concrete surface under the heater with the hollows running co ...

  • A.O. Smith BTP(V)-540A - page 7

    7 Heater must be protected from freezing downdrafts during shutdown periods. The BTP 540A, 650A and 750A water heater are classified as a category I appliance (non-positive vent pressure, non- condensing) when installed with the supplied barometric draft control assembly in a vertical vent installation. The BTPV 540A through 740A heater is classifi ...

  • A.O. Smith BTP(V)-540A - page 8

    8 Refer to T able 2 for limitations of venting system design for horizontal venting. T ABLE 2 BTPV-540A-740A Flue Outlet Dia. (Inches/mm) 9” (228.6) Flue Reducer 9” x 8” Dimensions -Supplied (Inches/mm) 228.6 x 203.2 Minimum Outlet V ent Dia. (Inches/mm) 8” (203.2) Maximum Number 90° 4 Of Elbows 45° 8 Maximum T otal V ent System 75 Length ...

  • A.O. Smith BTP(V)-540A - page 9

    9 DIRECT VENTING - FOR BTPV MODELS All exhaust vent terminal, flue reducer , and intake vent terminal are supplied with any unit intended for direct venting. These parts must be installed without alteration. This heater is category III appliance when used in a direct vent application. All national and local codes pertaining to the installation of s ...

  • A.O. Smith BTP(V)-540A - page 10

    10 1. Shall be located not less than 12” (304.8 mm) above grade. 2. Shall be located not less than 3 (.9144 m) feet horizontally from and not less than 3 feet (.9144 m) below an exhaust vent terminal. 3. Shall not be located directly above an exhaust terminal. 4 . Shall be located 12” (304.8 mm) above the snow line in geographical areas where s ...

  • A.O. Smith BTP(V)-540A - page 11

    11 5. Attach a properly sized length of Selkirk Metalbestos model PS or model G venting to the exhaust vent adapter using the inner vee bands, see Figures 7 and 7B on page 10. 6. Fill the grooves in both inner vee bands with high-temp silicone sealant, Dow Corning 736 or equivalent. 7. Position the inner vee bands around the inner pipe flanges and ...

  • A.O. Smith BTP(V)-540A - page 12

    12 T ABLE 9A MAXIMUM CAP ACITY OF PIPE IN CUBIC FEET OF GAS PER HOUR (Based upon a Pressure Drop of 0.5 inch Water Column and 0.5 Specific Gravity Gas and max. gas press. of .5 psig) LENGTH I N Nominal Iron Pipe Sizes, Millimeters METERS 1/2" 3/4" 1" 1 1/4" 1 1/2" 2" 2 1/2" 3 " 4 " 3.0 51 105 199 410 615 ...

  • A.O. Smith BTP(V)-540A - page 13

    13 ROBERTSHA W ® 7000 DERHC GAS CONTROL V AL VE FIGURE 10. W A TER LINE CONNECTIONS Following are detailed installation diagrams for typical methods of application for the water heaters. The water heater may be installed by itself, or with a separate storage tank, on both single and two-temperature systems. When used with a separate storage tank, ...

  • A.O. Smith BTP(V)-540A - page 14

    14 INST ALLA TION DIAGRAMS ONE TEMPERA TURE - ONE HEA TER VERTICAL STORAGE T ANK FORCED CIRCULA TION WITH OR WITHOUT BUILDING RECIRCULA TION DANGER IF BUILDING COLD W A TER SUPPL Y HAS A BACKFLOW PREVENTER, CHECK V A L VE OR W A TER METER WITH CHECK VAL VE, PROVISIONS FOR THERMAL EXP ANSION OF W A TER IN THE HOT WA TER SYSTEM MUST BE PROVIDED. NOTE ...

  • A.O. Smith BTP(V)-540A - page 15

    15 TWO TEMPERA TURE - ONE HEA TER HIGH TEMPERA TURE WITH OR WITHOUT BUILDING RECIRCULA TION TWO TEMPERA TURE - TWO HEA TERS HIGH TEMPERA TURE WITH OR WITHOUT BUILDING RECIRCULA TION *PIPE RELIEF V AL VE TO OPEN DRAIN NOTE: IF TEMPERED W A TER IS RECIRCULA TED, RETURN LINE SHOULD BE CONNECTED A T POINT “A”. INSTALL IN ACCORDANCE WITH LOCAL CODES ...

  • A.O. Smith BTP(V)-540A - page 16

    16 CAUTION: IF BUILDING COLD W A TER SUPPL Y HAS A BACKFLOW PREVENTER, CHECK V ALVE OR W A TER METER WITH CHECK V AL VE, PROVISIONS FOR THERMAL EXP ANSION OF WA TER IN THE HOT WA TER SYSTEM MUST BE PROVIDED. TWO TEMPERA TURE - THREE HEA TERS (TWO PRE-HEA TERS/ONE BOOSTER) WITH OR WITHOUT BUILDING RECIRCULA TION TWO TEMPERA TURE - TWO HEA TERS (ONE ...

  • A.O. Smith BTP(V)-540A - page 17

    17 TWO TEMPERA TURE - ONE HEA TER HIGH TEMPERA TURE WITH RECIRCULA TION OF SANITIZING LOOP CAUTION: IF BUILDING COLD WA TER SUPPL Y HAS A BACKFLOW PREVENTER, CHECK V AL VE OR W A TER METER WITH CHECK V AL VE, PROVISIONS FOR THERMAL EXP ANSION OF W A TER IN THE HOT WA TER SYSTEM MUST BE PROVIDED. DANGER TEMPERA TURE SETTING SHOULD NOT EXCEED SAFE TE ...

  • A.O. Smith BTP(V)-540A - page 18

    18 MANIFOLD KITS Precision cut type “L” all copper A. O. Smith manifold kits assure water flow balance of all units. Without this balance, the full water heating and storage potential of the system cannot be achieved. Plus, the units with the higher water flow may have a shortened life. Unions shown in piping diagrams are not included in the ma ...

  • A.O. Smith BTP(V)-540A - page 19

    19 HEA TER WIRING IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE MUST BE REPLACED, IT MUST BE REPLACED WITH 105°C WIRE OR ITS EQUIV ALENT , EXCEPT IN THE BURNER HOUSING USE 200°C WIRE. The power burner is wired to the heater as shown in Figure 1 1 for BTP models and Figure 12 for BTPV models. The model and rating plate provided the el ...

  • A.O. Smith BTP(V)-540A - page 20

    20 FIGURE 1 1. ...

  • A.O. Smith BTP(V)-540A - page 21

    21 FIGURE 12. ...

  • A.O. Smith BTP(V)-540A - page 22

    22 FOR YOUR SAFETY READ BEFORE LIGHTING 1. Remove thermostat control cover . 2 . Set thermostat to lowest setting. 3 . Turn burner switch to “OFF”. W ARNING: If you do not follow these instructions exactly , a fire or explosion may result causing property damage, personal injury or loss of life. A. This appliance is equipped with an ignition de ...

  • A.O. Smith BTP(V)-540A - page 23

    23 SEQUENCE OF OPERA TION – Power on. – Heater in standby mode. – Thermostat calls for heat. – Blower motor starts. – Blower operation closes the normally open blower prover/ blocked outlet safety pressure switch. – On proof of airflow , Honeywell S8680J flame control module energized. – 45 seconds prepurge cycle begins. – Following ...

  • A.O. Smith BTP(V)-540A - page 24

    24 1. Check gas line pressure with a manometer . Set initial gas line pressure at 9-10” w .c. before turning the heater “ON”. Read gas line pressure and gas manifold pressure when the heater main gas is “ON”. Adjust gas line regulator setting if the gas line pressure drops below 8” w .c. when heater main gas is “ON”. Check heater ga ...

  • A.O. Smith BTP(V)-540A - page 25

    25 PREMIX LOW NOx BURNER - EXPLODED VIEW FOR BTP MODELS FIGURE 13. ...

  • A.O. Smith BTP(V)-540A - page 26

    26 PREMIX LOW NOx BURNER - EXPLODED VIEW FOR BTPV MODELS FIGURE 14. ...

  • A.O. Smith BTP(V)-540A - page 27

    27 GENERAL INFORMA TION POWER BURNER The initial start-up procedure of the gas power burner is provided on page 18 thru 21. Refer to Figure 12, burner exploded view for burner components location. The sequence of operation of the power burner is provided on page 15. For detailed Power Burner Operation, Maintenance and Troubleshooting refer to the s ...

  • A.O. Smith BTP(V)-540A - page 28

    28 DRAINING The heater must be drained if it is to be shut down and exposed to freezing temperatures. Maintenance and service procedures may also require draining the heater . 1. Turn off the heater electrical disconnect switch. 2. Close the cold water inlet valve to heater . 3. Open a nearby hot water faucet to vent the system. 4. Open the heater ...

  • A.O. Smith BTP(V)-540A - page 29

    29 ABOVE ALL, DO NOT PLUG THE TEMPERA TURE AND PRESSURE RELIEF V AL VE. THIS IS NOT A SOLUTION AND CAN CREA TE A HAZARDOUS SITUA TION. CIRCULA TING PUMP The water heating system may include a circulating pump. Where used, it should be lubricated as directed by the circulator manufacturer . LOW EMISSION POWER BURNER KEEP THE AREA AROUND THE BURNER C ...

  • A.O. Smith BTP(V)-540A - page 30

    30 2. Check the fuses. • The electrical disconnect switch usually contains fuses. 3. The capacity of the heater may have been exceeded by a large demand for hot water . 4. Colder incoming water temperature will lengthen the time required to heat water to the desired temperature. • If the heater was installed when incoming water temperature was ...

  • A.O. Smith BTP(V)-540A - page 31

    31 Refer to the SEQUENCE OF OPERA TION and burner exploded view , see Figure 12 and the wiring diagram located on page 20, and the troubleshooting section of burner manual before continuing. Make sure the appliance is connected to a 120 V ac power supply , burner switch is “ON” and manual gas valve is in the “ON” position, and all electrica ...

  • A.O. Smith BTP(V)-540A - page 32

    32 • Do not proceed to Step 5 unless 24V is detected at “24V” terminal of the Honeywell Module. 5. As soon as the pilot gas valve is energized, check for the burner pilot flame through the burner peek-hole. If the pilot flame is established inside the burner , then proceed to Step 6. • Turn the burner switch to “OFF” position for at lea ...

  • A.O. Smith BTP(V)-540A - page 33

    33 Model BTP(V) Limited Warranty A.O. Smith Corporation, the warrantor , extends the following LIMITED W ARRANTY to the owner of this water heater . 1. THE T ANK If the glass-lined tank in this water heater shall prove upon examination by the warrantor to have leaked due to the natural corrosion from potable water therein, during the first THREE ye ...

  • A.O. Smith BTP(V)-540A - page 34

    34 NOTES ...

  • A.O. Smith BTP(V)-540A - page 35

    35 NOTES ...

  • A.O. Smith BTP(V)-540A - page 36

    36 REPLACEMENT P ARTS 5621 W . 1 15TH STREET , ALSIP , IL 60803 Phone: 800-433-2545 Fax: 800-433-2515 w w w .aosmithwaterheaters.com E-Mail: parts@hotwater .com ...

Fabricante A.O. Smith Categoría Water Heater

Los documentos del dispositivo A.O. Smith BTP(V)-540A que obtenemos del fabricante se pueden dividir en varios grupos. Entre ellos están::
- dibujos técnicos A.O. Smith
- manuales de instrucciones BTP(V)-540A
- hojas de producto A.O. Smith
- folletos informativos
- o etiquetas energéticas A.O. Smith BTP(V)-540A
Todos son importantes, pero lo más importante desde el punto de vista del usuario de un dispositivo lo encontraremos en el manual de instrucciones A.O. Smith BTP(V)-540A.

Un conjunto de documentos determinado como manual de instrucciones se divide también en tipos más detallados, tales como: instrucciones de montaje A.O. Smith BTP(V)-540A, instrucciones de servicio, instrucciones cortas o instrucciones de usuario A.O. Smith BTP(V)-540A. Dependiendo de la situación debes buscar el documento que necesitas. En nuestra página puedes consultar el manual de instrucciones más popular del producto A.O. Smith BTP(V)-540A.

Manuales de instrucciones parecidos

El manual de instrucciones del dispositivo A.O. Smith BTP(V)-540A, ¿cómo debería ser?
El manual de instrucciones, también determinado como el manual de usuario o simplemente instrucciones, es un documento técnico que tiene como objetivo ayudar a los usuarios a utilizar A.O. Smith BTP(V)-540A. Las instrucciones normalmente las realiza un escritor técnico pero en un lenguaje comprensible para todos los usuarios de A.O. Smith BTP(V)-540A.

El manual de instrucciones completo de A.O. Smith debe contener unos elementos básicos. Una parte de ellos es menos importante, como por ejemplo: la portada / la página principal o las páginas de autor. Sin embargo, lo demás debe facilitarnos la información más importante desde el punto de vista del usuario.

1. Introducción y pistas sobre cómo orientarse con el manual A.O. Smith BTP(V)-540A - Al principio de cada manual se deben encontrar las indicaciones acerca de la manera de usar un manual de instrucciones. Debe contener información sobre dónde encontrar el índice A.O. Smith BTP(V)-540A, preguntas frecuentes o problemas más comunes – son los apartados más buscados por los usuarios de cada manual de instrucciones.
2. Índice - listados de todos los consejos acerca de A.O. Smith BTP(V)-540A que encontraremos en el documento
3. Consejos de uso de las funciones básicas del dispositivo A.O. Smith BTP(V)-540A - que deben facilitarnos los primeros pasos durante el uso de A.O. Smith BTP(V)-540A
4. Troubleshooting - una secuencia sistematizada de acciones que nos ayudará a diagnosticar los problemas más importantes con A.O. Smith BTP(V)-540A
5. FAQ - las preguntas frecuentes
6. Datos de contacto Información acerca de cómo encontrar los datos de contacto del fabricante / servicio de A.O. Smith BTP(V)-540A en cada país si no somos capaces de solucionar el problema por nuestra cuenta.

¿Tienes una pregunta acerca de A.O. Smith BTP(V)-540A?

Utiliza el formulario que se encuentra abajo

Si con la ayuda del manual de instrucciones encontrado no has podido solucionar tu problema con A.O. Smith BTP(V)-540A, haz una pregunta utilizando el formulario que se encuentra abajo. Si alguno de los usuarios ha tenido un problema parecido con A.O. Smith BTP(V)-540A probablemente compartirá una forma de solucionarlo.

Copia el texto de la imagen

Comentarios (0)