Summary
  • Bryant 559F - page 1

    CONTENTS Page SAFETY CONSIDERA TIONS ........................1 INST ALLA TION ................................. 1-15 I. Step 1 — Provide Unit Support ...............1 II. Step 2 — Rig and Place Unit .................1 III. Step 3 — Field Fabricate Ductwork ............7 IV . Step 4 — Make Unit Duct Connections .........7 V . S t e p5—T r ...

  • Bryant 559F - page 2

    PKG. NO. REF . CURB HEIGHT DESCRIPTION 308450-201 1 8 -2 9 (305) Standard Curb 14 9 High 308450-202 2 8 -0 9 (610) Standard Curb for Units Requiring High Installation 308450-203 2 8 -0 9 (610) Side Supply and Return Kit for High Installation NOTES: 1. Roof curb accessory is shipped disassembled. 2. Insulated panels: 1 ⁄ 2 9 thick neoprene coated ...

  • Bryant 559F - page 3

    NOTE: For preassembled horizontal adapter roof curb part no. 389210-201, the accessory kit includes a factory-designed, high- static, regain transition duct. For horizontal curb part no. 308450- 203, a field-supplied transition duct is required. Fig. 2 — Horizontal Adapter Roof Curb and Roof Curb UNIT 559F MAXIMUM SHIPPING WEIGHT DIMENSIONS AB l ...

  • Bryant 559F - page 4

    POWER EXHAUST/ BAROMETRIC RELIEF (ACCESSORY ONL Y) UNIT STD UNIT WEIGHT ECONOMIZER WEIGHT CORNER A CORNER B CORNER C CORNER D DIM A DIM B DIM C Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg ft-in. mm ft-in. mm ft-in. mm 559F180 1550 703 1 10 50 391 177 365 166 384 174 410 186 3-5 1041 3-6 1067 1-10 559 559F216 1650 748 1 10 50 399 181 384 174 402 182 439 199 ...

  • Bryant 559F - page 5

    POWER EXHAUST/ BAROMETRIC RELIEF (ACCESSORY ONL Y) UNIT STD UNIT WEIGHT ECONOMIZER WEIGHT CORNER A CORNER B CORNER C CORNER D DIM A DIM B DIM C Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg ft-in. mm ft-in. mm ft-in. mm 559F240 1700 771 1 10 50 419 190 394 179 425 193 463 210 3-4 1016 3-5 1041 1-8 508 559F300 1850 839 1 10 50 428 194 412 187 511 232 499 226 ...

  • Bryant 559F - page 6

    T able 1 — Physical Data UNIT 559F 180 216 240 300 NOMINAL CAP ACITY (tons) 15 18 20 25 OPERA TING WEIGHT 1550 1650 1700 1850 COMPRESSOR Scroll, Copeland Quantity ... Model (Ckt 1 , Ckt 2) 2...ZR94KC 1...ZR108KC, 1...ZR94KC 1...ZR125KC, 1...ZR108KC 1...ZR16M3, 1...ZR125KC Number of Refrigerant Circuits 22 2 2 Oil (oz) (Ckt 1 , Ckt 2) 81, 81 106,8 ...

  • Bryant 559F - page 7

    III. STEP 3 — FIELD F ABRICA TE DUCTWORK Secure all ducts to building structure. Use flexible duct con- nectors between unit and ducts as required. Insulate and weath- erproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes. Ducts passing through an unconditioned space must b ...

  • Bryant 559F - page 8

    VI. STEP 5 — MAKE ELECTRICAL CONNECTIONS A. Field Power Supply Unit is factory wired for voltage shown on nameplate. When installing units, provide a disconnect, per NEC (Na- tional Electrical Code) requirements, of adequate size (T able 2). All field wiring must comply with NEC and local requirements. Route power lines through control box acces ...

  • Bryant 559F - page 9

    T able 2 — Electrical Data UNIT 559F NOMINAL VOL T AGE (3 Ph, 60 Hz) VOL T AGE RANGE COMPRESSOR OFM IFM POWER EXHAUST ELECTRIC HEA T* POWER SUPPL Y No. 1 No. 2 Min Max RLA LRA RLA LRA Qty Hp FLA (ea) Hp FLA FLA LRA kW FLA MCA MOCP† 180 (15 T ons) 208/230 187 253 28.8 195 28.8 195 3 0.5 1.7 3.7 10.5/1 1.0 — — — — 81/81 100/100 4.6 18.8 ? ...

  • Bryant 559F - page 10

    T able 2 — Electrical Data (cont) UNIT 559F NOMINAL VOL T AGE (3 Ph, 60 Hz) VOL T AGE RANGE COMPRESSOR OFM IFM POWER EXHAUST ELECTRIC HEA T* POWER SUPPL Y No. 1 No. 2 Min Max RLA LRA RLA LRA Qty Hp FLA (ea) Hp FLA FLA LRA kW FLA MCA MOCP† 300 (25 T ons) 208/230 187 253 41.0 350 37.8 239 2 1 6.6 10.0 28.0/28.0 — — — — 130/130 150/150 4.6 ...

  • Bryant 559F - page 11

    VII. STEP 7 — MAKE OUTDOOR-AIR INLET ADJUSTMENTS A. Manual Outdoor-Air Damper All units (except those equipped with a factory-installed econo- mizer) have a manual outdoor-air damper to provide venti- lation air . Damper can be preset to admit up to 25% outdoor air into return-air compartment. T o adjust, loosen securing screws and move damper to ...

  • Bryant 559F - page 12

    VIII. STEP 8 — INST ALL OUTDOOR-AIR HOOD The same type of factory-installed hood is used on units with 25% air ventilation and units with an economizer . NOTE: The hood top panel, upper and lower filter retainers, hood drain pan, baf f le (size 300), and filter support bracket are secured opposite the condenser end of the unit. The screens, hoo ...

  • Bryant 559F - page 13

    NOTE: For maximum benefit of outdoor air , set the enthalpy control to the ‘‘A ’’ setting. At this setting, when the relative humidity is 50% and the outdoor air is below 74 F , the relay contacts on the sensor will be closed. 9. Reinstall economizer hoods if removed. IMPORT ANT : Be sure all seal strips and RTV sealant are in- tact. A wat ...

  • Bryant 559F - page 14

    T ransformer (460-v Units Only) — On 460-v units, a trans- former is required. The transformer is provided with the ac- cessory and must be field-installed. Sensor Assembly — Install the sensor assembly in the loca- tion shown in Fig. 23. Motormaster t I Control — Recommended mounting location is on the inside of the panel to the left of the ...

  • Bryant 559F - page 15

    ST ART -UP Use the following information and Start-Up Checklist on page CL-1 to check out unit PRIOR to start-up. I. UNIT PREP ARA TION Check that unit has been installed in accordance with these installation instructions and all applicable codes. II. SERVICE V AL VES Ensure that optional suction, discharge, and standard liquid line service valves ...

  • Bryant 559F - page 16

    T able 5 — Fan Performance — 559F180 559F180 (15 TONS) Airflow (Cfm) A vailable External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 1.2 Rpm Bhp W atts Rpm Bhp Watts Rpm Bhp W atts Rpm Bhp Watts Rpm Bhp W atts Rpm Bhp Watts 4500 684 1.28 1 102 791 1.49 1283 887 1.70 1466 977 1.92 1652 1061 2.13 1841 1 139 2.36 2034 4800 715 1.47 1265 817 1.68 ...

  • Bryant 559F - page 17

    T able 6 — Fan Performance — 559F216 and 240 559F216 and 240 (18 and 20 TONS) Airflow (Cfm) A vailable External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 1.2 Rpm Bhp W atts Rpm Bhp Watts Rpm Bhp W atts Rpm Bhp Watts Rpm Bhp W atts Rpm Bhp Watts 5,500 682 1.99 1675 760 2.29 1922 832 2.59 2177 901 2.90 2441 965 3.22 2712 1027 3.56 2990 6,000 ...

  • Bryant 559F - page 18

    T able 7 — Fan Performance — 559F300 559F300 (25 TONS) Airflow (Cfm) A vailable External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 1.2 Rpm Bhp W atts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts 7,000 845 3.26 2693 909 3.60 2979 969 3.96 3272 1028 4.32 3574 1083 4.70 3883 1 137 5.08 4,200 7,500 896 3.82 3156 956 ...

  • Bryant 559F - page 19

    T able 8 — Accessory/FIOP Static Pressure (in. wg) — 559F180 COMPONENT CFM 4500 5000 6000 7200 7500 Economizer 0.04 0.05 0.07 0.09 0.10 Glycol Coil 0.22 0.26 0.35 0.44 0.46 Electric Heat (kW) 26/34 0.06 0.07 0.09 0.1 1 0.12 32 0.06 0.07 0.09 0.1 1 0.12 42/56 0.07 0.08 0.12 0.16 0.17 55 0.07 0.08 0.12 0.15 0.17 56/75 0.09 0.10 0.15 0.20 0.21 80 ...

  • Bryant 559F - page 20

    XIII. BASE UNIT OPERA TION A. Cooling, Units Without Economizer When thermostat calls for cooling, terminals G and Y1 are energized. The indoor (evaporator) fan contactor (IFC), and compressor contactor no. 1 (C1) are energized and evaporator- fan motor , compressor no. 1 and condenser fans start. The condenser-fan motors run continuously while uni ...

  • Bryant 559F - page 21

    III. EV APORA TOR F AN PERFORMANCE ADJUSTMENT (Fig. 25-27) Fan motor pulleys are factory set for speed shown in T able 1. T o change fan speeds: 1. Shut of f unit power supply . 2. a. Size 180 Only: Loosen belt by loosening fan motor mounting plate nuts. b. Size 216-300 Only: Loosen nuts on the 2 carriage bolts in the motor mounting base. Install j ...

  • Bryant 559F - page 22

    4. Using jacking bolt under motor base, raise motor to top of slide and remove belt. Secure motor in this position by tightening the nuts on the carriage bolts. 5. Remove the belt drive. 6. Remove jacking bolt and tapped jacking bolt plate. 7. Remove the 2 screws that secure the motor mounting plate to the motor support channel. 8. Remove the 3 scr ...

  • Bryant 559F - page 23

    T able 1 1 — Economizer Checkout Procedures TEST PROCEDURE RESUL TS A. Disconnect power at TR and TR1. Disconnect jumper between P and P1. See Fig. 15. B. Jumper TR to 1. C. Jumper T1 to T . D. Disconnect outdoor-air thermostat connections from S O and +. Factory-installed 800 ohm resistor should remain connected to S R and +. E. Reconnect power ...

  • Bryant 559F - page 24

    Crankcase Heater Only the 559F300 unit is equipped with a 70-watt crankcase heater to prevent absorption of liquid refrigerant by oil in the crankcase when the compressor is idle. The crankcase heater is energized whenever there is a main power to the unit and the compressor is not energized. IMPORT ANT : After prolonged shutdown or servicing, ener ...

  • Bryant 559F - page 25

    TROUBLESHOOTING Refer to T able 13 for troubleshooting details. T able 13 — Cooling Service Analysis PROBLEM CAUSE REMEDY Compressor and condenser fan will not start. Power failure. Call power company . Fuse blown or circuit breaker tripped. Replace fuse or reset circuit breaker . Defective thermostat, contactor , transformer, or control relay . ...

  • Bryant 559F - page 26

    Fig. 31 — T ypical Wiring Schematic (559F180, 460-v Shown) —26— ...

  • Bryant 559F - page 27

    LEGEND AND NOTES FOR FIG. 31 AND 32 Fig. 31 — T ypical Wiring Schematic (559F180, 460-v Shown) (cont) AHA — Adjustable Heat Anticipator BKR W/A T — Breaks with Amp Turns C— Contactor , Compressor CAP — Capacitor CB — Circuit Breaker CC — Cooling Compensator CLO — Compressor Lockout CLS — Compressor Lockout Switch COMP — Compress ...

  • Bryant 559F - page 28

    Fig. 32 — T ypical Component Arrangement (559F180 Shown) —28— ...

  • Bryant 559F - page 29

    ...

  • Bryant 559F - page 30

    SERVICE TRAINING Packaged Service T raining programs are an excellent way to increase your knowledge of the equipment discussed in this manual, including: • Unit Familiarization • Installation Overview • Maintenance • Operating Sequence A large selection of product, theory , and skills programs are available, using popular video-based forma ...

  • Bryant 559F - page 31

    ...

  • Bryant 559F - page 32

    ST ART -UP CHECKLIST MODEL NO.: DA TE: SERIAL NO.: TECHNICIAN: I. PRE-ST ART -UP: M VERIFY THA T ALL P ACKING MA TERIALS HA VE BEEN REMOVED FROM UNIT M VERIFY INST ALLA TION OF INDOOR F AN MOTOR ADJUSTMENT BOL T (180 UNITS) OR ADJUSTMENT BOL T AND PLA TE (216-300 UNITS) M OPEN ALL SER VICE V AL VES (SUCTION, DISCHARGE, AND LIQUID) M VERIFY INST ALL ...

Fabricante Bryant Categoría Air Conditioner

Los documentos del dispositivo Bryant 559F que obtenemos del fabricante se pueden dividir en varios grupos. Entre ellos están::
- dibujos técnicos Bryant
- manuales de instrucciones 559F
- hojas de producto Bryant
- folletos informativos
- o etiquetas energéticas Bryant 559F
Todos son importantes, pero lo más importante desde el punto de vista del usuario de un dispositivo lo encontraremos en el manual de instrucciones Bryant 559F.

Un conjunto de documentos determinado como manual de instrucciones se divide también en tipos más detallados, tales como: instrucciones de montaje Bryant 559F, instrucciones de servicio, instrucciones cortas o instrucciones de usuario Bryant 559F. Dependiendo de la situación debes buscar el documento que necesitas. En nuestra página puedes consultar el manual de instrucciones más popular del producto Bryant 559F.

Manuales de instrucciones parecidos

El manual de instrucciones del dispositivo Bryant 559F, ¿cómo debería ser?
El manual de instrucciones, también determinado como el manual de usuario o simplemente instrucciones, es un documento técnico que tiene como objetivo ayudar a los usuarios a utilizar Bryant 559F. Las instrucciones normalmente las realiza un escritor técnico pero en un lenguaje comprensible para todos los usuarios de Bryant 559F.

El manual de instrucciones completo de Bryant debe contener unos elementos básicos. Una parte de ellos es menos importante, como por ejemplo: la portada / la página principal o las páginas de autor. Sin embargo, lo demás debe facilitarnos la información más importante desde el punto de vista del usuario.

1. Introducción y pistas sobre cómo orientarse con el manual Bryant 559F - Al principio de cada manual se deben encontrar las indicaciones acerca de la manera de usar un manual de instrucciones. Debe contener información sobre dónde encontrar el índice Bryant 559F, preguntas frecuentes o problemas más comunes – son los apartados más buscados por los usuarios de cada manual de instrucciones.
2. Índice - listados de todos los consejos acerca de Bryant 559F que encontraremos en el documento
3. Consejos de uso de las funciones básicas del dispositivo Bryant 559F - que deben facilitarnos los primeros pasos durante el uso de Bryant 559F
4. Troubleshooting - una secuencia sistematizada de acciones que nos ayudará a diagnosticar los problemas más importantes con Bryant 559F
5. FAQ - las preguntas frecuentes