    WSHP-SVX02A-EN Models “A” and later Design Sequence Installation Owner Diagnostics Water-to-Water Water-Source Heat Pump Models WPWD, GSWD and EXWA WPWD 024-072 – 60 HZ GSWD 024-072 – 60 HZ EXWA 240 – 60 HZ ...

  • Trane GSWD - page 2

    © 2002 American Standard Inc. WSHP-SVX02A-EN Notice NOTICE: Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully. WARNING -Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. CAUTION -Indicates a potentially hazardous situation which, if not avoide ...

  • Trane GSWD - page 3

    WSHP-SVX02A-EN 3 Contents Installation/Startup/Commissioning 4 Pre-installation Checklist 4 General Information 5 Dimensions/Weights 6 Installation Instructions 10 Electrical Requirements 19 Pre-Startup Checklist 20 Startup/Commissioning 21 Sequence of Operation 21 Operating Pressures 22 30 Startup Checklist & Log 24 Maintenance 25 Warranty Inf ...

  • Trane GSWD - page 4

    4 WSHP-SVX02A-EN WARNING Fiberglass Wool! Product contains fiberglass wool. Disturbing the insulation in this product during installation, maintenance or repair will expose you to airborne particles of glass wool fibers and ceramic fibers known to the state of California to cause cancer through inhalation. Glass wool fibers may also cause respirato ...

  • Trane GSWD - page 5

    WSHP-SVX02A-EN 5 General Information Unit Nameplate The unit nameplate is located at the front of the unit. It includes the unit model number, serial number, electri- cal characteristics, refrigerant charge, and other pertinent unit data. Compressor Nameplate The nameplate for the compressors are located on the compressor shell. Unit Description Be ...

  • Trane GSWD - page 6

    6 WSHP-SVX02A-EN Table 1: Unit weights Size Shipping Weight with pallet (lb) Shipping Weight w/o pallet (lb) 024 163 153 036 183 173 042 203 193 048 214 204 060 244 234 072 277 267 240 1222 1156 WARNING Improper Unit Lift! Test lift unit approximately 24 inches to verify proper center of gravity lift point. To avoid dropping of unit, reposition lif ...

  • Trane GSWD - page 7

    WSHP-SVX02A-EN 7 Dimensions WPWD/GSWD 024-036 ...

  • Trane GSWD - page 8

    8 WSHP-SVX02A-EN Dimensions WPWD/GSWD 042-072 ...

  • Trane GSWD - page 9

    WSHP-SVX02A-EN 9 Dimensions EXWA 240 ...

  • Trane GSWD - page 10

    10 WSHP-SVX02A-EN General Installation Checks The checklist below is a summary of the steps required to successfully in- stall a unit. This checklist is intended to acquaint the installing personnel with procedures required in the installation process. It does not replace the de- tailed instructions called out in the ap- plicable sections of this m ...

  • Trane GSWD - page 11

    WSHP-SVX02A-EN 11 Figure 2: Racking installation WARNING Improper Unit Lift! Test lift unit approximately 24 inches to verify proper center of gravity lift point. To avoid dropping of unit, reposition lifting point if unit is not level. Failure to properly lift unit could result in death or serious injury or possible equipment or property-only dama ...

  • Trane GSWD - page 12

    12 WSHP-SVX02A-EN Cleaning and Flushing the Water Loop After the piping system is complete, the flexible hose connectors should be doubled back to complete the water circuit external to the unit (avoiding trash settle-out in the condenser). Fig- ure 4 . An extra pipe may be necessary to connect the hose kits. See Page 14 for antifreeze/water mixtur ...

  • Trane GSWD - page 13

    WSHP-SVX02A-EN 13 Supply/Return Pipe Connections to the Loop Pump Kit (1) Connect the supply and return hos- es to the water-inlet (from supply) and water-outlet (to return) of the unit. The rubber gaskets for the water-in and water-out connections are located in the control box. These gaskets require field installation prior to connecting the wate ...

  • Trane GSWD - page 14

    14 WSHP-SVX02A-EN Water Heater Hook-up (option) Instructions for connection from the desuperheater (option) water-in/out to the domestic hot water heater may be found in WSHPC-IN-4 or 72-9006-02. This water heater kit (Figure 8) ships in all units with the desuperheater op- tion. The kit is zip tied to the compres- sor base; and consists of piping ...

  • Trane GSWD - page 15

    WSHP-SVX02A-EN 15 Filling the Loop Pump Kit System Once the loop, pump module and unit are fully connected, the system will need to be filled with water or water/ antifreeze solution. See Page 14 for an- tifreeze/water mixture by volume. Fill both sides of the outside portion of the loop first via the pump module. The hose kit and unit should be fi ...

  • Trane GSWD - page 16

    16 WSHP-SVX02A-EN Field Installed Power Wiring Power wiring to the equipment must conform to National and Local Electric Codes (NEC) by a professional electri- cian. WARNING Live Electrical Components! During installation, testing, ser- vicing and troubleshooting of this product, it may be necessary to work with live electrical compo- nents. Have a ...

  • Trane GSWD - page 17

    WSHP-SVX02A-EN 17 Controls Using 24 VAC Before installing any wire, refer to the electrical access locations on the unit submittals located on pages 7 through 9. Ensure that the AC control wiring be- tween the controls and the unit’s ter- mination point does not exceed three (3) ohms/conductor for the length of the run. Note: Resistance in excess ...

  • Trane GSWD - page 18

    18 WSHP-SVX02A-EN Changing Freezestat or Low Pres- sure Cutout Switches (WPWD/GSWD models ONLY) Each unit has two factory installed low pressure cutout switches and one freezestat. Only one of the low pres- sure cutout switches is connected to the 24 volt control circuit, dependent on which freezestat is being used (i.e. 35 °F or 20°F). Both the ...

  • Trane GSWD - page 19

    WSHP-SVX02A-EN 19 Table E-1: Electrical performance WPWD/EXWA Table E-2: Electrical performance GSWD Model/MBH VOLTS-AC/HZ/PH Min. Util. Volt Max Util. Volt Compressor Each RLA LRA No. of Comp Without Desup With Desup MCA Max Fuse Desup RLA MCA Max Fuse WPWD024 208-230/60/1 197 253 11.4 56.0 1 14.3 25 0.4 14.7 25 220-240/50/1 198 264 9.6 47.0 1 12. ...

  • Trane GSWD - page 20

    20 WSHP-SVX02A-EN Pre-Start Checklist Pre-Start-up Checklist Before energizing the unit, the following system devices must be checked: __ __ Is the high voltage power supply correct and in accordance with the nameplate ratings? ____ Is the field wiring and circuit protection the correct size? ____ Is the low voltage control circuit wiring correct p ...

  • Trane GSWD - page 21

    WSHP-SVX02A-EN 21 Initial Unit Start-up Start-up with the system controls is included below: Note: Air Handlers should not be operated in the construction phase of dry walling. The air-to-refrigerant coil will foul, and the warranty will be void. 1. Set the system control to the desired mode of operation. 2. Set the control switch to fans and circu ...

  • Trane GSWD - page 22

    22 WSHP-SVX02A-EN Operating Pressures Table OP-1: Cooling mode operating pressures Unit Size Entering Load (Degree F) Entering Source Temperature (Degree F) 50 86 104 Suction Pressure Discharge Pressure Suction Pressure Discharge Pressure Suction Pressure Discharge Pressure EXWA 240 53.6 46-56 103-143 49-59 188-228 49-59 238-278 EXWA 240 86 61-71 1 ...

  • Trane GSWD - page 23

    WSHP-SVX02A-EN 23 Operating Pressures Table 7: Heating water pressure drops (WPD) in feet of head Unit Size GPM Source Load EWT F Ft. Head Pressure EWT F Ft. Head Pressure 024 3.8 60 1.5 80 1.3 7.0 5.1 4.5 8.9 8.3 7.2 036 4.6 60 2.2 80 1.9 8.5 7.6 6.6 10.8 12.2 10.6 042 5.2 60 2.8 80 2.4 9.5 9.8 8.6 12.1 16.2 14.1 048 6.0 60 3.8 80 3.3 11.0 13.3 11 ...

  • Trane GSWD - page 24

    24 WSHP-SVX02A-EN Start-up Checklist and Log Installing Contractor: Use this form to thoroughly check-out the system and units before and during start-up. (This form need not be returned to the factory unless requested during technical service support). Job Name: Model Number: Date: Serial Number: In order to minimize troubleshooting and costly sys ...

  • Trane GSWD - page 25

    WSHP-SVX02A-EN 25 Preventive Maintenance Maintenance on the unit is simplified with the following preventive sugges- tions: WARNING Hazardous Voltage! Disconnect all electric power, in- cluding remote disconnects be- fore servicing. Follow proper lockout/tagout procedures to en- sure the power can not be inad- vertently energized. Failure to discon ...

  • Trane GSWD - page 26

    26 WSHP-SVX02A-EN Warranty Information Standard Warranty The standard water-source heat pump warranty is Trane’s parts-only warranty, running 12-months from star- tup, not to exceed 18-months from shipment. Extended Warranty The optional extended warranty is a second through fifth year warranty. The time starts at the end of standard 1-year cover ...

  • Trane GSWD - page 27

    WSHP-SVX02A-EN 27 WARNING Hazardous Service Procedures! The maintenance and trouble shooting procedures recommend- ed in this section of the manual could result in exposure to electri- cal, mechanical or other potential safety hazards. Always refer to the safety warnings provided throughout this manual concern- ing these procedures. When possi- ble ...

  • Trane GSWD - page 28

    28 WSHP-SVX02A-EN Troubleshooting Checklist Problem Heating Cooling Cause Correction No response to any thermostat setting X X Main power off Check fuses X X Defective control transformer Replace X X Broken or loose connection Repair X X Defective thermostat Replace X X Transformer Reset Transformer Unit short cycles X X Thermostat or sensor improp ...

  • Trane GSWD - page 29

    WSHP-SVX02A-EN 29 Unit Wiring 2-ton through 6-Ton Equipment ...

  • Trane GSWD - page 30

    30 WSHP-SVX02A-EN Unit Wiring 20-Ton Equipment ...

  • Trane GSWD - page 31

    Since Trane has a policy of continuous product and data improvement and reserves the right to change design and specifications without notice. Literature Order Number WSHP-SVX02A-EN File Number SV-UN-WSHP-SVX02A-8-02 Supersedes WSHPC-IOM-4 and 72-9036-02 Stocking Location Inland Trane An American Standard Company www.trane.com For more information, ...

Fabricante Trane Categoría Heat Pump

Los documentos del dispositivo Trane GSWD que obtenemos del fabricante se pueden dividir en varios grupos. Entre ellos están::
- dibujos técnicos Trane
- manuales de instrucciones GSWD
- hojas de producto Trane
- folletos informativos
- o etiquetas energéticas Trane GSWD
Todos son importantes, pero lo más importante desde el punto de vista del usuario de un dispositivo lo encontraremos en el manual de instrucciones Trane GSWD.

Un conjunto de documentos determinado como manual de instrucciones se divide también en tipos más detallados, tales como: instrucciones de montaje Trane GSWD, instrucciones de servicio, instrucciones cortas o instrucciones de usuario Trane GSWD. Dependiendo de la situación debes buscar el documento que necesitas. En nuestra página puedes consultar el manual de instrucciones más popular del producto Trane GSWD.

Manuales de instrucciones parecidos

El manual de instrucciones del dispositivo Trane GSWD, ¿cómo debería ser?
El manual de instrucciones, también determinado como el manual de usuario o simplemente instrucciones, es un documento técnico que tiene como objetivo ayudar a los usuarios a utilizar Trane GSWD. Las instrucciones normalmente las realiza un escritor técnico pero en un lenguaje comprensible para todos los usuarios de Trane GSWD.

El manual de instrucciones completo de Trane debe contener unos elementos básicos. Una parte de ellos es menos importante, como por ejemplo: la portada / la página principal o las páginas de autor. Sin embargo, lo demás debe facilitarnos la información más importante desde el punto de vista del usuario.

1. Introducción y pistas sobre cómo orientarse con el manual Trane GSWD - Al principio de cada manual se deben encontrar las indicaciones acerca de la manera de usar un manual de instrucciones. Debe contener información sobre dónde encontrar el índice Trane GSWD, preguntas frecuentes o problemas más comunes – son los apartados más buscados por los usuarios de cada manual de instrucciones.
2. Índice - listados de todos los consejos acerca de Trane GSWD que encontraremos en el documento
3. Consejos de uso de las funciones básicas del dispositivo Trane GSWD - que deben facilitarnos los primeros pasos durante el uso de Trane GSWD
4. Troubleshooting - una secuencia sistematizada de acciones que nos ayudará a diagnosticar los problemas más importantes con Trane GSWD
5. FAQ - las preguntas frecuentes
6. Datos de contacto Información acerca de cómo encontrar los datos de contacto del fabricante / servicio de Trane GSWD en cada país si no somos capaces de solucionar el problema por nuestra cuenta.

¿Tienes una pregunta acerca de Trane GSWD?

Utiliza el formulario que se encuentra abajo

Si con la ayuda del manual de instrucciones encontrado no has podido solucionar tu problema con Trane GSWD, haz una pregunta utilizando el formulario que se encuentra abajo. Si alguno de los usuarios ha tenido un problema parecido con Trane GSWD probablemente compartirá una forma de solucionarlo.

Copia el texto de la imagen

Comentarios (0)