    FERRUPS ® User Manual 0800-2000 through 0800-7500 2 kV A-7.5 kV A 50 and 60 Hz Uninterruptible Power Systems IMPOR T ANT SAFETY INSTRUCTIONS. SA VE THESE INSTRUCTIONS. This manual contains important instructions for your UPS. See the CheckUPS CD also for the FERRUPS Safety Information manual. Se cd-rommen CheckUPS til FERRUPS-manualen med sikkerhe ...

  • Ferrups 0800-2000 - page 3

    2 Best Power Of fices Best Power P .O. Box 280 Necedah, WI 54646 U.S.A. T elephone: 1-608-565-7200 T oll-Free: 1-800-356-5794 (U.S.A. and Canada) F AX: 1-608-565-2221 International F AX: 1-608-565-7675 W orldwide Service P .O. Box 1 1 Necedah, WI 54646 U.S.A. T elephone: 1-608-565-2100 T oll-Free: 1-800-356-5737 (U.S.A. and Canada) F AX: 1-608-565- ...

  • Ferrups 0800-2000 - page 4

    3 Contents 100 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 200 UPS Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 300 Starting the UPS . . ...

  • Ferrups 0800-2000 - page 5

    4 200 UPS Features The drawings below will help you identify the features on your UPS and separate battery cabinets. Back Panel of Standard Units* Back Panel with Optional Internal Bypass Battery Cabinet Back Panel UPS Display * Only one FERRUPS model is shown; sizes vary . The unit shown is a soft-wired (plug-in) model with output receptacles; som ...

  • Ferrups 0800-2000 - page 6

    5 300 Starting the UPS Note: If you plan to store your UPS, the storage temperature must be between –20° and +40° Celsius (–4° and +104° Fahrenheit). If the UPS does not have internal batteries, you can store it at –20° to +60° C (–4° to +140° F). The batteries must be recharged every 90-120 days. T o recharge the batteries, start t ...

  • Ferrups 0800-2000 - page 7

    6 3 Models with permanently attached power cor ds (shown): Plug in the UPS. If the plug on the UPS’ power cord does not match your outlet (receptacle), an electrician must install the proper outlet. Models with power cor ds that must be plugged in: Do not use the cord that came with your UPS to plug it in; this cord is for connecting your equipme ...

  • Ferrups 0800-2000 - page 8

    7 If your UPS has output r eceptacles/outlets on the back panel (shown) or on an attached internal bypass switch, plug the equipment you want to protect into the UPS’ receptacles. If you used the cord from your own equipment to plug in the UPS (see step 2 ), use the cord provided with the FERRUPS to plug your equipment into the FERRUPS. If the po ...

  • Ferrups 0800-2000 - page 9

    8 b. Press the t button twice until the display shows “3 System Status Info.” c. Press ¿ once. The display will now show “3 1 Unit T ime.” d. Press ¿ . A cursor will appear in the time shown. e. Notice that the bottom line of the display has changed to “ < – – > ESC” to show you that you can now use the bottom three buttons ...

  • Ferrups 0800-2000 - page 10

    400 Using the FERRUPS’ Front Panel Lights The FERRUPS display includes three lights that show you the status of FERRUPS operation. The red Alarm light means the UPS has detected a problem. When this happens, the display shows an alarm message, and the UPS beeps the Morse Code for the alarm. See Section 600 . The yellow Battery light means the UPS ...

  • Ferrups 0800-2000 - page 11

    T o scroll down through menus or menu items in the same level: Press the t button on the right side of the display . T o scroll up thr ough menus or menu items in the same level: Press the s button. Y ou can also look at the bottom line of the display , which includes the words “T op” and “ESC.” The button under the word “T op” will tak ...

  • Ferrups 0800-2000 - page 12

    11 1 Enter password 3 System Status Info 5 System Config Enter password 3 1 Unit T ime 3 2 Unit Date 3 3 Unit Y ear 3 4 AC Input V olts 3 5 AC Output V olts 3 6 AC Input Current 3 7 AC Output Current 3 8 V A Out 3 9 W atts Out 3 10 % Full Load 3 1 1 Power Factor 3 12 Output Frequency 3 13 Battery V olts 3 14 Run T ime 3 15 Unit Ambient T emp 3 16 E ...

  • Ferrups 0800-2000 - page 13

    12 503 Entering a Password Before you can change the setting of some FERRUPS parameters or menu items, you must enter a password. T o do this, follow the steps below . The User password is 0377. 1. If the display is not already showing the menus, press the bottom right button (below the word “Menu” on the bottom line of the display). Go to the ...

  • Ferrups 0800-2000 - page 14

    3. Move the cursor to the first digit you want to change, and use the s and t buttons to increase or decrease the number . Repeat this step for each digit that needs to be changed. 4. When you have finished, press ¿ to save the new setting. If you decide not to change the setting, press the bottom right button below the word “ESC” on the displ ...

  • Ferrups 0800-2000 - page 15

    14 Menu 2: System Status (continued) Menu 3: System Status Info By pressing ¿ while displaying this parameter , you can start a User T est alarm to make sure the FERRUPS alarms properly or to test alarm contacts at the DB9 communication port. By pressing ¿ again, you can stop the User T est alarm. This parameter shows the results of the last syst ...

  • Ferrups 0800-2000 - page 16

    15 Menu 3: System Status Info (continued) Menu 4: System ID Item and Sample Display Password to Change Range Explanation 3 10 % Full Load pctfload 90 % No change allowed. Not applicable. Percent of Full Load. The percentage of the FERRUPS’ total capacity that your equipment is using. 3 16 EEPROM Stat W ord eeword 0000 hex 3 15 Unit Ambient T emp ...

  • Ferrups 0800-2000 - page 17

    16 506 Reading the FERRUPS Logs Y our FERRUPS makes an entry in its logs every time it sounds an alarm or runs on inverter (battery power). This information can help diagnose power problems. Y ou can display both the Alarm and Inverter logs at the unit’ s display panel; both logs are in menu 6. Inverter Log The Inverter Log is in menu 6, submenu ...

  • Ferrups 0800-2000 - page 18

    These are the inverter codes: Alarm Log The Alarm Log is in menu 6, submenu 3. If you have already displayed inverter log entries, press the bottom right button to display “6 2 Inverter Log,” and press t once to scroll down to the alarm log. Then press ¿. If not, follow the steps below to display the log, follow these steps: 1. Press the botto ...

  • Ferrups 0800-2000 - page 19

    18 Alarm Message Morse Code What It Means How to React A Low Battery vbatt 40.0 V lowbatv 41.0 V minbattv 38.34 • — (A) The UPS has shut down because the battery voltage is too low for the UPS to continue operating on battery power . The battery charge is low because the UPS was running on battery power or because the DC switch on one or more s ...

  • Ferrups 0800-2000 - page 20

    19 Alarm Message Morse Code What It Means How to React K Circuit Br eaker W arning Shutdown — • — (K) Y our equipment is drawing more current (amps) than the UPS is designed to provide. (See your model’ s output current rating.) The unit will shut down; the time until shutdown depends on the amount of overcurrent. The least important equipm ...

  • Ferrups 0800-2000 - page 21

    20 Optional Interface Kits: For computer systems that already have UPS monitoring software, Best Power offers interface cable kits for connecting the FERRUPS to your computer system. The kit includes the cable, adapters, and instructions. Optional Internal Bestlink™ SNMP/W eb Adapter: Using Simple Network Management Protocol (SNMP), system admini ...

  • Ferrups 0800-2000 - page 22

    21 1. a. Press the bottom right button (below “Menu” on the display) to switch from the normal display to the menus. The display will show the top menu, “1 Enter Password.” b. Press t four times (until the display shows “5 System Config”). c. Press ¿ . The display will show “5 1 System Config.” d. Press t twice. The display will sh ...

  • Ferrups 0800-2000 - page 23

    22 900 Specifications * Size input protection according to all applicable local or national codes. Fuse and circuit breaker sizes vary . Sizes shown are for the U.S. and Canada. ** At 0.7 leading or distortion power factor . Size output protection according to all applicable local or national codes. *** Height includes switch. Model 0800-2000 2 kV ...

  • Ferrups 0800-2000 - page 24

    23 AC Output with Nominal Input Power and Loads (Protected Equipment) V oltage Regulation: ±3% load regulation. T otal voltage regulation under any line, load, or battery condition to within –8.3% and +5% of nominal. Input V oltage Range: At low voltages: 85-135 V AC. At high voltages: 165-275 V AC. Overload Capability: 150% sur ge and 125% for ...

  • Ferrups 0800-2000 - page 25

    24 Protection DC Input: DC fuse and battery charger overvoltage limit network. Output Pr otection: The ferroresonant transformer inherently limits current and provides overload protection. FERRUPS has high AC and low AC output voltage alarms, as well as an overload alarm. If the AC output voltage falls below the low AC output voltage alarm setpoint ...

  • Ferrups 0800-2000 - page 26

    25 incompatible or defective. Replacement or repair will be made at BEST POWER’ s W orldwide Service, Highway 80, Necedah, W isconsin 54646, U.S.A. Such repair or replacement shall be at BEST POWER’ s expense. This warranty does not cover any taxes which may be due in connection with replacement or repair , nor any installation, removal, transp ...

  • Ferrups 0800-2000 - page 27

    26 This warranty does not include any taxes which may be due in connection with replacement or repair nor any installation, transportation or postage costs. These expenses will be paid by PURCHASER. Replacement or repair will be made at BEST POWER’ s W orldwide Service, Highway 80, Necedah, W isconsin 54646, U.S.A. This warranty does not cover re ...

  • Ferrups 0800-2000 - page 28

    27 1 100 Notices 2-3 kV A Soft-wired (Plug-in) and 50 Hz Models: This device complies with part 15 of the FCC rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference that may cause undesired operation. Note: This equipment has been tested and f ...

Fabricante Ferrups Categoría Power Supply

Los documentos del dispositivo Ferrups 0800-2000 que obtenemos del fabricante se pueden dividir en varios grupos. Entre ellos están::
- dibujos técnicos Ferrups
- manuales de instrucciones 0800-2000
- hojas de producto Ferrups
- folletos informativos
- o etiquetas energéticas Ferrups 0800-2000
Todos son importantes, pero lo más importante desde el punto de vista del usuario de un dispositivo lo encontraremos en el manual de instrucciones Ferrups 0800-2000.

Un conjunto de documentos determinado como manual de instrucciones se divide también en tipos más detallados, tales como: instrucciones de montaje Ferrups 0800-2000, instrucciones de servicio, instrucciones cortas o instrucciones de usuario Ferrups 0800-2000. Dependiendo de la situación debes buscar el documento que necesitas. En nuestra página puedes consultar el manual de instrucciones más popular del producto Ferrups 0800-2000.

Manuales de instrucciones parecidos

El manual de instrucciones del dispositivo Ferrups 0800-2000, ¿cómo debería ser?
El manual de instrucciones, también determinado como el manual de usuario o simplemente instrucciones, es un documento técnico que tiene como objetivo ayudar a los usuarios a utilizar Ferrups 0800-2000. Las instrucciones normalmente las realiza un escritor técnico pero en un lenguaje comprensible para todos los usuarios de Ferrups 0800-2000.

El manual de instrucciones completo de Ferrups debe contener unos elementos básicos. Una parte de ellos es menos importante, como por ejemplo: la portada / la página principal o las páginas de autor. Sin embargo, lo demás debe facilitarnos la información más importante desde el punto de vista del usuario.

1. Introducción y pistas sobre cómo orientarse con el manual Ferrups 0800-2000 - Al principio de cada manual se deben encontrar las indicaciones acerca de la manera de usar un manual de instrucciones. Debe contener información sobre dónde encontrar el índice Ferrups 0800-2000, preguntas frecuentes o problemas más comunes – son los apartados más buscados por los usuarios de cada manual de instrucciones.
2. Índice - listados de todos los consejos acerca de Ferrups 0800-2000 que encontraremos en el documento
3. Consejos de uso de las funciones básicas del dispositivo Ferrups 0800-2000 - que deben facilitarnos los primeros pasos durante el uso de Ferrups 0800-2000
4. Troubleshooting - una secuencia sistematizada de acciones que nos ayudará a diagnosticar los problemas más importantes con Ferrups 0800-2000
5. FAQ - las preguntas frecuentes
6. Datos de contacto Información acerca de cómo encontrar los datos de contacto del fabricante / servicio de Ferrups 0800-2000 en cada país si no somos capaces de solucionar el problema por nuestra cuenta.

¿Tienes una pregunta acerca de Ferrups 0800-2000?

Utiliza el formulario que se encuentra abajo

Si con la ayuda del manual de instrucciones encontrado no has podido solucionar tu problema con Ferrups 0800-2000, haz una pregunta utilizando el formulario que se encuentra abajo. Si alguno de los usuarios ha tenido un problema parecido con Ferrups 0800-2000 probablemente compartirá una forma de solucionarlo.

Copia el texto de la imagen

Comentarios (0)