Manual de instrucciones Eclipse Combustion VeriFlame Single Burner Monitoring System

42 de páginas 0.82 mb
Descargar

Pasar a la página of 42

Summary
  • Eclipse Combustion VeriFlame Single Burner Monitoring System - page 1

    Modulation Model Purge Model No Purge Model Instruction Manual 818 2/02 V er iFlame Single Bur ner Monitor ing System Model 5600 V ersion 1.21 ...

  • Eclipse Combustion VeriFlame Single Burner Monitoring System - page 2

    2 Eclipse V e ri-Flame Instruction Manual 818 -2/02 Cop y r igh t 1 997 b y Ec li ps e C ombustion, In c . All rights r es er v ed w orl dwide. Thi s p u b l i c a t i o n i s p r o t e c t e d b y f e d e r a l r e g u l a t i o n a n d s h a l l n o t b e c o p i e d , dis trib uted , tr ansmit ted, transcrib e d or tra nslated in to an y human o ...

  • Eclipse Combustion VeriFlame Single Burner Monitoring System - page 3

    3 Eclipse V er i-Flame Instruction Manual 818 - 2/02 A UDIENCE S COPE D OCUMENT C ONVENTIONS This man ual has been written for the people who select and install the product and the technicians who w ork on it. They ar e expected to ha v e previous expe- rience with this kind of equipment. This man ual contains essential information for the proper i ...

  • Eclipse Combustion VeriFlame Single Burner Monitoring System - page 4

    4 Eclipse V eri-Flame Instruction Manual 818 -2/02 H OW TO GET HELP If you need help , you can contact y our local Eclipse Combustion sales office. Y ou can also contact Eclipse Combustion, Inc . at: 1665 Elmwood Road Rockford, Illinois 61103 USA Phone: 815-877-3031 Fax: 815-877-3336 E-mail: eclipse @ eclipsenet.com http://www .eclipsenet.com ...

  • Eclipse Combustion VeriFlame Single Burner Monitoring System - page 5

    5 Eclipse V er i-Flame Instruction Manual 818 - 2/02 About this manual ..................................................................................... 3 T ab le of contents ........................................................................................ 5 Introduction ................................................................... ...

  • Eclipse Combustion VeriFlame Single Burner Monitoring System - page 6

    6 Eclipse V eri-Flame Instruction Manual 818 -2/02 Optional Featur es ................................................................................................. 16 Pilot T est Mode Sequence .............................................................................. 16 Air Switch Input Hold ................................................. ...

  • Eclipse Combustion VeriFlame Single Burner Monitoring System - page 7

    7 Eclipse V er i-Flame Instruction Manual 818 - 2/02 Maintenance & T r oub leshooting .................................................... 28 Introdu ction ............................................................................................................ 28 Maintenance .................................................................. ...

  • Eclipse Combustion VeriFlame Single Burner Monitoring System - page 8

    8 Eclipse V eri-Flame Instruction Manual 818 -2/02 The Eclipse Combustion V eri-Flame Single Burner Monitoring System contr ols the start-up sequence and monitors the flame of single gas, oil, or combination gas/oil burners. There ar e thr ee different models to the V eri-Flame line: the no purge, the purge and the modulation models. Each model fea ...

  • Eclipse Combustion VeriFlame Single Burner Monitoring System - page 9

    9 Eclipse V er i-Flame Instruction Manual 818 - 2/02 Specifications I NTRODUCTION Specifications This section giv es a detailed ov er view of V eri-Flame specifications and dimensions. 2 (continued onto next page ) P ARAMETER D ESCRIPTION Supply • Series 5602 & 5605: 1 20 V A C ( + 10%, - 15%), 50/60 Hz standard. Series 5603: 240 V AC ( + 10% ...

  • Eclipse Combustion VeriFlame Single Burner Monitoring System - page 10

    10 Eclipse V eri-Flame Instruction Manual 818 -2/02 Specifications (continued) P ARAMETER D ESCRIPTION Approvals • No Purge & Purge Models: Series 5602: UL listed, CSA cer tified, FM approv ed and IRI acceptable. Series 5603: No appr ovals. Series 5605: UL listed, FM appro v ed and IRI acceptable . • Modulating Models: Series 5602: UL r eco ...

  • Eclipse Combustion VeriFlame Single Burner Monitoring System - page 11

    11 Eclipse V er i-Flame Instruction Manual 818 - 2/02 Dimensions (continued) * * 171mm (6-3/4") Veri-Flame/Modulating Model with Base Model Number 5602-40 Remote Display Model Number 5602-DB Contrast Adjustment Screw Ground Screw 15-pin Port Terminal Wiring Terminal 54mm (2-1/8") 102mm (4") Square 89mm (3-1/2") Square Mounting B ...

  • Eclipse Combustion VeriFlame Single Burner Monitoring System - page 12

    12 Eclipse V eri-Flame Instruction Manual 818 -2/02 I NTRODUCTION DIP Switch Location DIP Switch Selection This section details the location, selection and description of the V eri-Flame DIP switches, which allow for sequence and timing functions as well as sys- tem configuration. Caution T o avoid electr ic shock, shut off the po wer supply when i ...

  • Eclipse Combustion VeriFlame Single Burner Monitoring System - page 13

    13 Eclipse V er i-Flame Instruction Manual 818 - 2/02 Close-up of DIP switches on back side of all V eri-Flame models. Figure 3. 1 DIP Switch Location Figure 3. 2 DIP Switch Labels with Selections No Purge Models Purge Models Modulation Models ...

  • Eclipse Combustion VeriFlame Single Burner Monitoring System - page 14

    14 Eclipse V eri-Flame Instruction Manual 818 -2/02 I NTRODUCTION Function Summar y S T AND ARD FEA TURES 4 This section describes the featur es of the V eri-Flame. It is br ok en into thr ee categories: Standard f eatur es, Optional features and the LED Indicator Lights on the front co ver . Refer to Figur e 5.5 f or sequence diagrams. The followi ...

  • Eclipse Combustion VeriFlame Single Burner Monitoring System - page 15

    15 Eclipse V er i-Flame Instruction Manual 818 - 2/02 F or modulation models: This f eature is enabled when the jumper on the base is cut. The system checks that the high fire position switch and the main valve closed switch ar e both made at the end of the high fire purge. F or all models: when selected, the V eri-Flame will r estar t the sequence ...

  • Eclipse Combustion VeriFlame Single Burner Monitoring System - page 16

    16 Eclipse V eri-Flame Instruction Manual 818 -2/02 F or modulation models: the modulation f eature incorporates a high fir e purge time and a low fir e purge time into the purge sequence. This f eatur e allows the V eri-Flame to sequence internal dr y contacts which can be used b y the customer requiring a high fir e purge of the combustion chambe ...

  • Eclipse Combustion VeriFlame Single Burner Monitoring System - page 17

    17 Eclipse V er i-Flame Instruction Manual 818 - 2/02 S T A TUS L IGHTS & P USH - BUTT ON All of the status lights and the TEST/RESET push-button ar e located on the fro nt cover of the V eri-Flame. This section describes their r espectiv e functions. For all models: this green LED illuminates when the operation limits ar e made. These limits a ...

  • Eclipse Combustion VeriFlame Single Burner Monitoring System - page 18

    18 Eclipse V eri-Flame Instruction Manual 818 -2/02 System Installation In this section, the necessar y pr ocedures are detailed to integrate a V eri-Flame into a burner system; Figur es 5.1 and 5.2 illustrate the various terminal strips mentioned. Note: Shut off the power supply befor e the V eri-Flame is removed or replaced from the base. Caution ...

  • Eclipse Combustion VeriFlame Single Burner Monitoring System - page 19

    19 Eclipse V er i-Flame Instruction Manual 818 - 2/02 Ignition Wiring Lo w Fire Input Main V alve Closed Switch High Purge Input Remote Reset Route ignition wiring a sufficient distance fr om all sensors and other low v olt- age wiring to a void electrical interference, which ma y cause erratic operation of the V eri-Flame system. K eep the high vo ...

  • Eclipse Combustion VeriFlame Single Burner Monitoring System - page 20

    20 Eclipse V eri-Flame Instruction Manual 818 -2/02 Figure 5. 1 No Purg e and Purg e Wiring Diagrams No Purg e Models Purg e Models Figure 5. 2 Modulation Wiring Diagram On/Off 15 A Fuse 7 S1 S2 V 1 2 Alarm Interlocks & Limits 3 4 5 On/Off 15 A Fuse A Piloted Burner Pilot Ignition Main Piloted Burner Pilot Ignition Main 7 S2 S1 1 2 Alarm Interl ...

  • Eclipse Combustion VeriFlame Single Burner Monitoring System - page 21

    21 Eclipse V er i-Flame Instruction Manual 818 - 2/02 Notes f or Figur es 5.1, 5.2 & 5.3: 1. Ground, shielding and conduit must not be connected to terminal S2. 2. Control circuit wir es must meet 90°C (194°F) specif ication minimum and must be No. 16 A WG or larger and in accor dance with all applicable codes. 3. Flame sensor wir es must be ...

  • Eclipse Combustion VeriFlame Single Burner Monitoring System - page 22

    22 Eclipse V eri-Flame Instruction Manual 818 -2/02 Figure 5. 4 Purge and No Purge Bases Model Number 5602-10 Model Number 5602-10-1 5 6 S2 S1 7 8 3 4 V 2 1 A 5 6S 2 S 1 7 8 A 1 2 V 4 3 P3 P2 P1 Gnd Gnd P3 P1 P2 Jumper Jumper 1 2 3 4 5 6 7 8 A D 11 12 13 10 S2 S1 J2 J1 1 1 Modulating Base Jumper P3 P2 P1 6 4 6 4 3 1 2 3 1 2 1 6 4 6 4 3 1 2 3 1 2 1 ...

  • Eclipse Combustion VeriFlame Single Burner Monitoring System - page 23

    23 Eclipse V er i-Flame Instruction Manual 818 - 2/02 Figure 5. 5 Sequence Dia grams T erminal 1 3 4 5 8 6 7 V Function Control P ow er Pilot V alve Ignition Main V alve Fan Air Switch Interlocks PO VC Outputs Inputs Start Air Pr ov e n Flame Check 5 Sec Pilot T rial Main T rial 10 Sec End Pilot Off (Intermittent) Pilot Off (Interr upted) Firing Cy ...

  • Eclipse Combustion VeriFlame Single Burner Monitoring System - page 24

    24 Eclipse V eri-Flame Instruction Manual 818 -2/02 Flame Rods This section describes the pr oper wiring, installation and sighting considerations for all sensors that can be used with a V eri-Flame . W arning Incorr ect sensor installation ma y cause the sensor to generate a false flame signal, possibly resulting in the collection of unburned fuel ...

  • Eclipse Combustion VeriFlame Single Burner Monitoring System - page 25

    25 Eclipse V er i-Flame Instruction Manual 818 - 2/02 1) K eep the flame r od as short as possible and at least 13 mm (1/2") awa y from any refractory . 2) Position the r od into the side of both the pilot and main flames, pref erably at a descending angle to minimize dr ooping of the flame rod against burner parts, as sho wn in Figure 6.1. Fl ...

  • Eclipse Combustion VeriFlame Single Burner Monitoring System - page 26

    26 Eclipse V eri-Flame Instruction Manual 818 -2/02 I NTRODUCTION Flame Signal Strength T est Pr ocedures 7 This section describes the test pr ocedures that must be perf ormed after instal- lation to insur e that the V eri-Flame is operating properly; these pr ocedures are mandatory . Insert the positive probe of a 0-15 VDC , digital volt meter int ...

  • Eclipse Combustion VeriFlame Single Burner Monitoring System - page 27

    27 Eclipse V er i-Flame Instruction Manual 818 - 2/02 1) Man ually shut off the fuel supply to the pilot and the main burner . 2) Place system in pilot test mode (please r e fer to page 15). 3) Start the system normally . The controller should lock out*; if it doesn’ t, then the controller is detecting a false flame signal (see Section 6). Find t ...

  • Eclipse Combustion VeriFlame Single Burner Monitoring System - page 28

    28 Eclipse V eri-Flame Instruction Manual 818 -2/02 I NTRODUCTION 8 This section is divided into tw o parts: • The first part describes the maintenance pr ocedures. • The second part describes troubleshooting pr ocedures, from identifying pr ob- lems to interpr eting the operating conditions by the lit LEDs on the fr ont cove r . Pre v entativ ...

  • Eclipse Combustion VeriFlame Single Burner Monitoring System - page 29

    29 Eclipse V er i-Flame Instruction Manual 818 - 2/02 T R OUBLESHOO TING Check main valve closed switch. No voltage on V (or D). Check air pressure switch adjustment. Check air filter . Check blower rotation. Check outlet pr essur e from blow er . No voltage on 6 after 8 is on. Check incomming gas pressure; adjust gas pressur e if necessar y . Chec ...

  • Eclipse Combustion VeriFlame Single Burner Monitoring System - page 30

    30 Eclipse V eri-Flame Instruction Manual 818 -2/02 LED S T A TUS This section describes the status of operating conditions based on the LED or combination of LEDs which are lit on the fr ont cov er of each V eri-Flame model. T able 8.1 LED Status & Conditions for V eri-Flame No Purge Models LED( S ) L IT P OSSIBLE C AUSES INTERLOCKS CLOSED SYS ...

  • Eclipse Combustion VeriFlame Single Burner Monitoring System - page 31

    31 Eclipse V er i-Flame Instruction Manual 818 - 2/02 T able 8.2 LED Status & Conditions for V eri-Flame Purg e Models LED( S ) L IT P OSSIBLE C AUSES INTERLOCKS CLOSED SYSTEM ERR OR 1) The interlocks are closed (normal operation), pow er on terminal 7. 1) The flame detected is out of sequence , flame signal light is on. 2) The sensor is “run ...

  • Eclipse Combustion VeriFlame Single Burner Monitoring System - page 32

    32 Eclipse V eri-Flame Instruction Manual 818 -2/02 T able 8.3 LED Status & Conditions for V eri-Flame Modulation Models Modulation Model LED( S ) L IT P OSSIBLE C AUSES SYSTEM ERR OR 1) The flame detected is out of sequence , flame signal light is on. 2) The sensor is “runawa y”, flame signal light is on. 3) Inductance is detected on senso ...

  • Eclipse Combustion VeriFlame Single Burner Monitoring System - page 33

    33 Eclipse V er i-Flame Instruction Manual 818 - 2/02 I NTRODUCTION 9 This section co vers how the optional remote displa y is used with the V eri-Flame . The remote displa y provides LCD messages which monitor the status of the V eri- Flame’ s functions as w ell as an y lock out conditions. This section is divided into two parts or tables: • T ...

  • Eclipse Combustion VeriFlame Single Burner Monitoring System - page 34

    34 Eclipse V eri-Flame Instruction Manual 818 -2/02 T able 9.1 V eri-Flame Operating Sequence PO WER ON W as internal safe start check successful? EXTERNAL INTERLOCK CHECKS Is flame signal present? BURNER ST AR T -UP (see next page) YES NO YES NO YES NO YES NO V arious lockout messages Fan output is energized; modu- lator is sent to low fir e. YES ...

  • Eclipse Combustion VeriFlame Single Burner Monitoring System - page 35

    35 Eclipse V er i-Flame Instruction Manual 818 - 2/02 T able 9.1 V eri-Flame Operating Sequence (continued) BURNER ST AR T -UP Is volta g e pr esent at air flo w switch within ten seconds? Is flame signal present? (see next page) Spark turns off at end of TFI; sequence dela y ed 5 seconds. Spark and pilot valve energized for selected trial for igni ...

  • Eclipse Combustion VeriFlame Single Burner Monitoring System - page 36

    36 Eclipse V eri-Flame Instruction Manual 818 -2/02 T able 9.1 V eri-Flame Operating Sequence (continued) BURNER ST AR T -UP (continued) Is flame signal present? NO Modulator sent to automatic 20 seconds after main valve is energized. Pilot will shut off 10 seconds after main flame is energized. Main flame of burner is pro ven. Flame signal = XX.XV ...

  • Eclipse Combustion VeriFlame Single Burner Monitoring System - page 37

    37 Eclipse V er i-Flame Instruction Manual 818 - 2/02 T able 9.1 V eri-Flame Operating Sequence (continued) BURNER SHUTDO WN Shutdo wn is started b y opening the operating interlock cir cuit. Is volta g e pr esent at interlocks? YES NO Fuel valves de-energized; fan energized for 15 seconds. Is main valve closed s witch made?* YES NO Is volta g e pr ...

  • Eclipse Combustion VeriFlame Single Burner Monitoring System - page 38

    38 Eclipse V eri-Flame Instruction Manual 818 -2/02 Lockout For purge & modulation models: Combustion air flow limit switch opened for more than two seconds once initially proven. Status For purge & modulation models: Combustion air flow limit switch opened; if “recycle” has been selected, the Veri-Flame will restart the sequence after ...

  • Eclipse Combustion VeriFlame Single Burner Monitoring System - page 39

    39 Eclipse V er i-Flame Instruction Manual 818 - 2/02 Lockout Main valve has been energized and main flame proven during trial for ignition. St at us Pilot valve is de-energized and main flame is on. Lockout For purge and no purge models: Main valve closed switch is open before start-up or after burner shutdown. Lockout For purge & modulation m ...

  • Eclipse Combustion VeriFlame Single Burner Monitoring System - page 40

    40 Eclipse V eri-Flame Instruction Manual 818 -2/02 Hold Flame signal—actual, induced, or runaway scanner—is detected be- fore start-up or after shutdown. The fan is energized. If the cause is corrected within 30 seconds, as in afterburn, the control will turn off the fan and continue the sequence. Lockout Same conditions as above, except the c ...

  • Eclipse Combustion VeriFlame Single Burner Monitoring System - page 41

    41 Eclipse V er i-Flame Instruction Manual 818 - 2/02 C ONVERSION F A CT ORS Appendix Metric to English. F ROM T O M UL TIPL Y BY cubic meter (m 3 ) cubic f oot (ft 3 ) 35.31 cubic meter/hour (m 3 /h) cubic foot/hour (cfh) 35.31 degr ees Celsius (°C) degrees Fahrenheit (°F) (°C x 1.8) + 32 kilogram (kg) pound (lb) 2.205 kilowatt (kW) Btu/hr 3414 ...

  • Eclipse Combustion VeriFlame Single Burner Monitoring System - page 42

    I LLUSTRA TED P AR TS L IST Litho in USA Instruction Manual 818 2/02 Straight U .V . scanner 5600-91 49600-91 NEMA 4 U .V . scanner 5600-91N4 20898 90˚ U .V . scanner 5600-90A 49600-90 I.R. scanner 5600-92B 49600-92 Self-check scanner 5602-91 49602-91 10-f oot cable f or self-chec k scanner 5602-91-7 49602-91-7 Scanner suppor t (max. temp . 220˚F ...

Fabricante Eclipse Combustion Categoría Burner

Los documentos del dispositivo Eclipse Combustion VeriFlame Single Burner Monitoring System que obtenemos del fabricante se pueden dividir en varios grupos. Entre ellos están::
- dibujos técnicos Eclipse Combustion
- manuales de instrucciones VeriFlame Single Burner Monitoring System
- hojas de producto Eclipse Combustion
- folletos informativos
- o etiquetas energéticas Eclipse Combustion VeriFlame Single Burner Monitoring System
Todos son importantes, pero lo más importante desde el punto de vista del usuario de un dispositivo lo encontraremos en el manual de instrucciones Eclipse Combustion VeriFlame Single Burner Monitoring System.

Un conjunto de documentos determinado como manual de instrucciones se divide también en tipos más detallados, tales como: instrucciones de montaje Eclipse Combustion VeriFlame Single Burner Monitoring System, instrucciones de servicio, instrucciones cortas o instrucciones de usuario Eclipse Combustion VeriFlame Single Burner Monitoring System. Dependiendo de la situación debes buscar el documento que necesitas. En nuestra página puedes consultar el manual de instrucciones más popular del producto Eclipse Combustion VeriFlame Single Burner Monitoring System.

Manuales de instrucciones parecidos

El manual de instrucciones del dispositivo Eclipse Combustion VeriFlame Single Burner Monitoring System, ¿cómo debería ser?
El manual de instrucciones, también determinado como el manual de usuario o simplemente instrucciones, es un documento técnico que tiene como objetivo ayudar a los usuarios a utilizar Eclipse Combustion VeriFlame Single Burner Monitoring System. Las instrucciones normalmente las realiza un escritor técnico pero en un lenguaje comprensible para todos los usuarios de Eclipse Combustion VeriFlame Single Burner Monitoring System.

El manual de instrucciones completo de Eclipse Combustion debe contener unos elementos básicos. Una parte de ellos es menos importante, como por ejemplo: la portada / la página principal o las páginas de autor. Sin embargo, lo demás debe facilitarnos la información más importante desde el punto de vista del usuario.

1. Introducción y pistas sobre cómo orientarse con el manual Eclipse Combustion VeriFlame Single Burner Monitoring System - Al principio de cada manual se deben encontrar las indicaciones acerca de la manera de usar un manual de instrucciones. Debe contener información sobre dónde encontrar el índice Eclipse Combustion VeriFlame Single Burner Monitoring System, preguntas frecuentes o problemas más comunes – son los apartados más buscados por los usuarios de cada manual de instrucciones.
2. Índice - listados de todos los consejos acerca de Eclipse Combustion VeriFlame Single Burner Monitoring System que encontraremos en el documento
3. Consejos de uso de las funciones básicas del dispositivo Eclipse Combustion VeriFlame Single Burner Monitoring System - que deben facilitarnos los primeros pasos durante el uso de Eclipse Combustion VeriFlame Single Burner Monitoring System
4. Troubleshooting - una secuencia sistematizada de acciones que nos ayudará a diagnosticar los problemas más importantes con Eclipse Combustion VeriFlame Single Burner Monitoring System
5. FAQ - las preguntas frecuentes
6. Datos de contacto Información acerca de cómo encontrar los datos de contacto del fabricante / servicio de Eclipse Combustion VeriFlame Single Burner Monitoring System en cada país si no somos capaces de solucionar el problema por nuestra cuenta.

¿Tienes una pregunta acerca de Eclipse Combustion VeriFlame Single Burner Monitoring System?

Utiliza el formulario que se encuentra abajo

Si con la ayuda del manual de instrucciones encontrado no has podido solucionar tu problema con Eclipse Combustion VeriFlame Single Burner Monitoring System, haz una pregunta utilizando el formulario que se encuentra abajo. Si alguno de los usuarios ha tenido un problema parecido con Eclipse Combustion VeriFlame Single Burner Monitoring System probablemente compartirá una forma de solucionarlo.

Copia el texto de la imagen

Comentarios (0)