    58MXA 4-Way Multipoise Fixed-Capacity Direct-Vent Condensing Gas Furnace Service and Maintenance Instructions → For Sizes 040—140, Series 130 NOTE: Read the entire instruction manual before performing any service or maintenance. This symbol → indicates a change since the last issue. Index Page SAFETY CONSIDERATIONS ........................... ...

  • Carrier 4-WAY MULTIPOISE FIXED-CAPACITY DIRECT-VENT CONDENSING GAS FURNACE 58MXA - page 2

    The ability to properly perform maintenance on this equip- ment requires certain expertise, mechanical skills, tools, and equipment. If you do not possess these, do not attempt to perform any maintenance on this equipment other than those procedures recommended in the User’s Manual. FAILURE TO FOLLOW THIS WARNING COULD RESULT IN POSSIBLE DAMAGE T ...

  • Carrier 4-WAY MULTIPOISE FIXED-CAPACITY DIRECT-VENT CONDENSING GAS FURNACE 58MXA - page 3

    Step 1—Cleaning and/or Replacing Air Filter The air filter arrangement may vary depending on the application or orientation. Never operate unit without a filter or with the blower access panel removed. Failure to follow this warning could result in a fire or personal injury. To clean or replace the filters, proceed as follows: 1. Turn off electri ...

  • Carrier 4-WAY MULTIPOISE FIXED-CAPACITY DIRECT-VENT CONDENSING GAS FURNACE 58MXA - page 4

    11. Reinstall condensate trap and tubing if previously removed. a. Reinstall condensate trap in hole in blower shelf. b. Connect condensate trap drain tubes. See Fig. 8 or tubing diagram on main furnace door for proper tube location. (1.) Connect 1 tube (blue or blue and white striped) from collector box. (2.) Connect 1 tube (violet or unmarked) fr ...

  • Carrier 4-WAY MULTIPOISE FIXED-CAPACITY DIRECT-VENT CONDENSING GAS FURNACE 58MXA - page 5

    Never use matches, candles, flame, or other sources of ignition to check for gas leakage. Use a soap-and-water solution. Failure to follow this warning could result in a fire, personal injury, or death. 19. Replace main furnace door. Step 4—Cleaning Heat Exchangers The following items should be performed by a qualified service technician. PRIMARY ...

  • Carrier 4-WAY MULTIPOISE FIXED-CAPACITY DIRECT-VENT CONDENSING GAS FURNACE 58MXA - page 6

    Never use matches, candles, flame, or other sources of ignition to check for gas leakage. Use a soap-and-water solution. Failure to follow this warning could result in a fire, personal injury, or death. 18. Replace main furnace door. SECONDARY HEAT EXCHANGERS NOTE: The condensing side (inside) of the secondary heat exchangers CANNOT be serviced or ...

  • Carrier 4-WAY MULTIPOISE FIXED-CAPACITY DIRECT-VENT CONDENSING GAS FURNACE 58MXA - page 7

    4. Disconnect pressure switch tubes. 5. Disconnect vent pipe from inducer housing outlet by loosen- ing coupling clamp on inducer outlet. 6. Disconnect drain tube from inducer housing. (See Fig. 8.) 7. Remove inducer housing assembly by removing 4 bolts attaching assembly to cell panel. 8. Flush inside of collector box with water until discharge fr ...

  • Carrier 4-WAY MULTIPOISE FIXED-CAPACITY DIRECT-VENT CONDENSING GAS FURNACE 58MXA - page 8

    10. Replace main furnace door. Step 7—Electrical Controls and Wiring There may be more than 1 electrical supply to the unit. Check accessories and cooling unit for additional electrical supplies. The electrical ground and polarity for 115-v wiring must be maintained properly. Refer to Fig. 11 for field wiring information and to Fig. 15 for unit w ...

  • Carrier 4-WAY MULTIPOISE FIXED-CAPACITY DIRECT-VENT CONDENSING GAS FURNACE 58MXA - page 9

    1. Leave 115-v power to furnace turned on. 2. Remove main furnace door. 3. Look into blower access panel sight glass for current LED status. NOTE: Leave blower access panel installed to maintain power to control center to view current LED status. 4. BRIEFLY remove either wire from the main limit switch until the LED goes out, then reconnect it. Mak ...

  • Carrier 4-WAY MULTIPOISE FIXED-CAPACITY DIRECT-VENT CONDENSING GAS FURNACE 58MXA - page 10

    NOTE: Heat tape, when used, should be wrapped around the condensate drain trap and drain line. There is no need to use heat tape within the furnace casing. Most heat tapes are temperature activated, and it is not practical to verify the actual heating of the tape. Check the following: 1. Check for signs of physical damage to heat tape such as nicks ...

  • Carrier 4-WAY MULTIPOISE FIXED-CAPACITY DIRECT-VENT CONDENSING GAS FURNACE 58MXA - page 11

    PCB BLOWER OF F DELAY SELECTION CHART 90 SEC 135 SE C 180 SE C 225 SE C GVR HI / L O RE LA Y SEC-1 SEC-2 WHT PL1 32 1 6 5 4 9 87 LED TEST/TWIN BLOWER OFF DEL AY G R Y W C HUM H SIR ID R BL W R BLOWER SPEED SELECT FU1 COOL HEAT L2 PL3 PL2 VAC 120 L1 PR1 1 2 1 2 3 PR2 24 V A C -3A FUSE SPARE-2 SPARE-1 EAC-1 EAC-2 C 1.5 AMP 12 PL5 WHT BRN GR N BLK IDM ...

  • Carrier 4-WAY MULTIPOISE FIXED-CAPACITY DIRECT-VENT CONDENSING GAS FURNACE 58MXA - page 12

    → Fig. 16—Service Label A99107 SER VICE COMP ON ENT TE ST To in iti a te th e co m po n ent test se que nc e, sh u t OF F th e r oom the rm o st at o r disconnect t he "R" t hermostat lead. Brie fly short the TEST ter minal to t he "Com 24V " ter mi nal . S tat us L ED wi ll fl ash code an d th en t urn O N t he in du cer m ...

  • Carrier 4-WAY MULTIPOISE FIXED-CAPACITY DIRECT-VENT CONDENSING GAS FURNACE 58MXA - page 13

    Is circuit breaker closed? Close door switch and go to start. Is red LED status light on? Is door switch closed? Is red LED status light blinking rapidly without a pause? Is there 1 15v going to switch? Replace door switch. Replace control center . Replace transformer . Is red LED status light blinking ON/OFF slowly with a combination of short and ...

  • Carrier 4-WAY MULTIPOISE FIXED-CAPACITY DIRECT-VENT CONDENSING GAS FURNACE 58MXA - page 14

    11 NO PREVIOUS F A UL T - Faults are erased after 48 hrs or whenever power (1 15v or 24v) is interrupted. Run system through a heating or cooling cycle to check system. 12 BLO WER ON AFTER PO WER UP (115V OR 24V) - Normal operation. Blower will run for 90 sec when furnace power is interrupted during a call for heat, R-W closed. 13 LIMIT OR FLAME RO ...

  • Carrier 4-WAY MULTIPOISE FIXED-CAPACITY DIRECT-VENT CONDENSING GAS FURNACE 58MXA - page 15

    15 ...

  • Carrier 4-WAY MULTIPOISE FIXED-CAPACITY DIRECT-VENT CONDENSING GAS FURNACE 58MXA - page 16

    A94328 SERVICE TRAINING Packaged Service Training programs are an excellent way to increase your knowledge of the equipment discussed in this manual, including:  • Unit Familiarization • Maintenance  • Installation Overview • Operating Sequence A large selection of product, theory, and skills programs is availa ...

Fabricante Carrier Categoría Furnace

Los documentos del dispositivo Carrier 4-WAY MULTIPOISE FIXED-CAPACITY DIRECT-VENT CONDENSING GAS FURNACE 58MXA que obtenemos del fabricante se pueden dividir en varios grupos. Entre ellos están::
- dibujos técnicos Carrier
- manuales de instrucciones 4-WAY MULTIPOISE FIXED-CAPACITY DIRECT-VENT CONDENSING GAS FURNACE 58MXA
- hojas de producto Carrier
- folletos informativos
- o etiquetas energéticas Carrier 4-WAY MULTIPOISE FIXED-CAPACITY DIRECT-VENT CONDENSING GAS FURNACE 58MXA
Todos son importantes, pero lo más importante desde el punto de vista del usuario de un dispositivo lo encontraremos en el manual de instrucciones Carrier 4-WAY MULTIPOISE FIXED-CAPACITY DIRECT-VENT CONDENSING GAS FURNACE 58MXA.

Un conjunto de documentos determinado como manual de instrucciones se divide también en tipos más detallados, tales como: instrucciones de montaje Carrier 4-WAY MULTIPOISE FIXED-CAPACITY DIRECT-VENT CONDENSING GAS FURNACE 58MXA, instrucciones de servicio, instrucciones cortas o instrucciones de usuario Carrier 4-WAY MULTIPOISE FIXED-CAPACITY DIRECT-VENT CONDENSING GAS FURNACE 58MXA. Dependiendo de la situación debes buscar el documento que necesitas. En nuestra página puedes consultar el manual de instrucciones más popular del producto Carrier 4-WAY MULTIPOISE FIXED-CAPACITY DIRECT-VENT CONDENSING GAS FURNACE 58MXA.

Manuales de instrucciones parecidos

El manual de instrucciones del dispositivo Carrier 4-WAY MULTIPOISE FIXED-CAPACITY DIRECT-VENT CONDENSING GAS FURNACE 58MXA, ¿cómo debería ser?
El manual de instrucciones, también determinado como el manual de usuario o simplemente instrucciones, es un documento técnico que tiene como objetivo ayudar a los usuarios a utilizar Carrier 4-WAY MULTIPOISE FIXED-CAPACITY DIRECT-VENT CONDENSING GAS FURNACE 58MXA. Las instrucciones normalmente las realiza un escritor técnico pero en un lenguaje comprensible para todos los usuarios de Carrier 4-WAY MULTIPOISE FIXED-CAPACITY DIRECT-VENT CONDENSING GAS FURNACE 58MXA.

El manual de instrucciones completo de Carrier debe contener unos elementos básicos. Una parte de ellos es menos importante, como por ejemplo: la portada / la página principal o las páginas de autor. Sin embargo, lo demás debe facilitarnos la información más importante desde el punto de vista del usuario.

1. Introducción y pistas sobre cómo orientarse con el manual Carrier 4-WAY MULTIPOISE FIXED-CAPACITY DIRECT-VENT CONDENSING GAS FURNACE 58MXA - Al principio de cada manual se deben encontrar las indicaciones acerca de la manera de usar un manual de instrucciones. Debe contener información sobre dónde encontrar el índice Carrier 4-WAY MULTIPOISE FIXED-CAPACITY DIRECT-VENT CONDENSING GAS FURNACE 58MXA, preguntas frecuentes o problemas más comunes – son los apartados más buscados por los usuarios de cada manual de instrucciones.
2. Índice - listados de todos los consejos acerca de Carrier 4-WAY MULTIPOISE FIXED-CAPACITY DIRECT-VENT CONDENSING GAS FURNACE 58MXA que encontraremos en el documento
3. Consejos de uso de las funciones básicas del dispositivo Carrier 4-WAY MULTIPOISE FIXED-CAPACITY DIRECT-VENT CONDENSING GAS FURNACE 58MXA - que deben facilitarnos los primeros pasos durante el uso de Carrier 4-WAY MULTIPOISE FIXED-CAPACITY DIRECT-VENT CONDENSING GAS FURNACE 58MXA
4. Troubleshooting - una secuencia sistematizada de acciones que nos ayudará a diagnosticar los problemas más importantes con Carrier 4-WAY MULTIPOISE FIXED-CAPACITY DIRECT-VENT CONDENSING GAS FURNACE 58MXA
5. FAQ - las preguntas frecuentes
6. Datos de contacto Información acerca de cómo encontrar los datos de contacto del fabricante / servicio de Carrier 4-WAY MULTIPOISE FIXED-CAPACITY DIRECT-VENT CONDENSING GAS FURNACE 58MXA en cada país si no somos capaces de solucionar el problema por nuestra cuenta.

¿Tienes una pregunta acerca de Carrier 4-WAY MULTIPOISE FIXED-CAPACITY DIRECT-VENT CONDENSING GAS FURNACE 58MXA?

Utiliza el formulario que se encuentra abajo

Si con la ayuda del manual de instrucciones encontrado no has podido solucionar tu problema con Carrier 4-WAY MULTIPOISE FIXED-CAPACITY DIRECT-VENT CONDENSING GAS FURNACE 58MXA, haz una pregunta utilizando el formulario que se encuentra abajo. Si alguno de los usuarios ha tenido un problema parecido con Carrier 4-WAY MULTIPOISE FIXED-CAPACITY DIRECT-VENT CONDENSING GAS FURNACE 58MXA probablemente compartirá una forma de solucionarlo.

Copia el texto de la imagen

Comentarios (0)