    CONTENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P A GE Dimensions .................................. 2,3 Installation Requirements: Boiler Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Boiler F oundation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Chimney Requirements . . . . . . . ...

  • Slant/Fin SX-150 - page 2

    2 Sentr y ...

  • Slant/Fin SX-150 - page 3

    The installation must conf orm to the requirements of the author ity having jurisdiction or , in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1-latest edition. This installation must also conf orm to the additional requirements in this Slant/Fin Instruction Book. NA TURAL GAS-FIRED BOILER LOCA TION Pro vide a le v el, ...

  • Slant/Fin SX-150 - page 4

    A. Minimum boiler clearances shall be as f ollo ws: B. Pro vide accessibility clearance of 24” on sides requiring ser vicing and 18” on sides used for passage. C . All minimum clearances sho wn abo ve m ust be met. This may result in increased v alues of some minimum clearances in order to maintain the minimum clearances of others . D . Clearan ...

  • Slant/Fin SX-150 - page 5

    must be suppor ted to prev ent sagging b y securing each joint with metal screws and b y providing hanger spaced no greater than 5 f eet apar t. D . V ent or breeching into chimney should not be inser ted past the inside wall of the chimne y liner . E. All venting means should be inspected frequently . See Care and Maintenance and separate User&apo ...

  • Slant/Fin SX-150 - page 6

    Figure 4. Figure 6. Connecting “RECEPT ACLE B” to “MALE PLUG” inside L8148E Aquastat Bo x for Sentry P acka ged “S” and “SX” boilers. Figure 5. V ent Damper Dimensions T ABLE Figure 8. Damper V ane Figure 9. 6 Sentr y V ent S ize 4" 5" 6" 7" 8" A9 5 ⁄ 16 "1 0 5 ⁄ 16 "1 1 5 ⁄ 16 "1 2 5 ? ...

  • Slant/Fin SX-150 - page 7

    B. 1. This device must be installed after the boiler dr aft hood ( between the draft hood outlet and the connector to the out- door chimney or v ent) as close to the draft hood as pr acti- cable , and without modification of the draft hood or the v ent damper . (See figures 1, 2 and 3.) 2. The inlet size of the v ent damper must be the same nomi- n ...

  • Slant/Fin SX-150 - page 8

    BOILER ROOM AIR SUPPL Y AND VENTILA TION An ample supply of air is required to obtain combustion and ventilation. ALL AIR COMES FROM OUTSIDE, directly through wall openings to the boiler or through unsealed openings around windows , doors, etc. in the whole building. When build- ings are insulated, caulked and w eather stripped, now or later on, di ...

  • Slant/Fin SX-150 - page 9

    5. Using soap solution, chec k f or gas leaks in all gas piping from meter to boiler pilot and manif old. DO NO T use open flame. II. INITIAL ST ART Saf e lighting and other perf ormance cr iteria were met when testing various gas manif old and control assemb lies used on t he Sentr y Series Boilers under the ANSI-Z21.13-1991 S tandard. INSTRUCTION ...

  • Slant/Fin SX-150 - page 10

    Figure 13. V alve VR8204 or VR8304 Figure 14. 2. Intermittent Pilot System (IID). FOR BOILERS EQUIPPED WITH HONEYWELL GAS V AL VE VR8204 OR VR8304 (see figures 13 and 14). SAFETY INFORMA TION FOR Y OUR SAFETY READ BEFORE OPERA TING W ARNING: If you do not f ollow these instructions e xactly , a fire or e xplosion may result causing property damage, ...

  • Slant/Fin SX-150 - page 11

    a. Boiler (b urner) is ov erfiring. CA UTION! National Fuel Gas Code ANSI Z223.1-latest edition, does NO T per- mit firing at a higher input rate than the input rate indi- cated on the boiler rating plate in order to a v oid haz- ardous conditions such as e xplosion or carbon mono xide poisoning. b . P oor higher* heating v alue of gas is causing t ...

  • Slant/Fin SX-150 - page 12

    3. W ater lines: slightest leaks should be corrected. 4. Lo w water cutoff , for operation (see instructions fur- nished with unit). 2 . W A TER LEVEL CHECK DURING HEA TING SEASON A. Check w ater pressure regularly and add water slowly to system when needed. If much water is added, v enting may be necessary . B . Regular loss of water from water bo ...

  • Slant/Fin SX-150 - page 13

    S EQUENCE OF OPERA TION FOR SENTR Y BOILERS EQUIPPED WITH CONTINUOUS BURNING PILO TS F OR DIA GRAMS SHO WN ON P A GE 14. 13 Sentr y LIGHTED PILO T HEA TS THERMOCOUPLE AND KEEPS PILO TST A T OPEN. THERMOST A T CALLS FOR HEA T HIGH LIMIT CONT ACTS CLOSED? LOW W A TER CUT -OFF (WHEN USED) CONT ACTS CLOSED? VENT D AMPER RELA Y ENERGIZED . VENT D AMPER ...

  • Slant/Fin SX-150 - page 14

    WIRING DIA GRAM — CONTINUOUS PILOT 14 Sentr y CA UTION: Label all wires prior to disconnection when ser vicing controls. Wiring errors can cause improper and dangerous operation. “V er ify proper operation after ser vicing. ” ...

  • Slant/Fin SX-150 - page 15

    15 Sentr y WIRING DIA GRAM — INTERMITTENT IGNITION (IID) CA UTION: Label all wires prior to disconnection when ser vicing controls. W iring errors can cause improper and dangerous operation. “V er ify proper operation after ser vicing. ” ...

  • Slant/Fin SX-150 - page 16

    P UMP OR V AL VE ZONING OF W A TER BOILERS COMBINA TION CONTROLS WITH T TV Z TERMINALS* 16 Sentr y Pump Zoning system using R845A Rela y . One R845A needed f or each circulator . NO TE: Pumps are powered from C1 . T otal pump load must not e xceed 7.4 amp rating of combination control pump s witch. Zone valv e zoning system using Honeywell V8043F z ...

  • Slant/Fin SX-150 - page 17

    17 Sentr y GENERAL TROUBLESHOO TING GUIDE FOR SER VICEPEOPLE BURNERS F AIL T O OPERA TE CA USE 1. Saf ety pilot out, or flame too lo w . 2. Gas supply v alv e shut off . 3. Electric s witch open. 4. Blo wn or def ectiv e line fuse. 5. Oper ating or limit control contacts open or dir ty . 6 . Def ectiv e gas v alv e or pressure regulator; or plugged ...

  • Slant/Fin SX-150 - page 18

    PIPING A HEA TING - COOLING SYSTEM T O A W A TER BOILER AND CHILLER The chiller must be piped in parallel with the boiler . Figure below illustrates a method of piping a heating-cooling system to a water boiler and a chiller . Hand v alv es (shown) or automatic valv es must be installed to prev ent circulation of chilled water in t he boiler or hot ...

  • Slant/Fin SX-150 - page 19

    (a) Seal an y unused openings in the common v enting system. (b) Visually inspect the v enting system f or proper siz e and hor- i zontal pitch and determine there is no blockage or restric- tion, leakage, corrosion and other deficiencies which could cause an unsaf e condition. (c) Insof ar as is pr actical, close all building doors and windo ws an ...

  • Slant/Fin SX-150 - page 20

    SLANT/FIN CORPORA TION, Green vale, N.Y . 11548 • Phone: (516) 484-2600 F AX: (516) 484-5921 • Canada: Slant/Fin L TD/L TEE , Mississauga, Ontar io www .slantfin.com ...

Fabricante Slant/Fin Categoría Boiler

Los documentos del dispositivo Slant/Fin SX-150 que obtenemos del fabricante se pueden dividir en varios grupos. Entre ellos están::
- dibujos técnicos Slant/Fin
- manuales de instrucciones SX-150
- hojas de producto Slant/Fin
- folletos informativos
- o etiquetas energéticas Slant/Fin SX-150
Todos son importantes, pero lo más importante desde el punto de vista del usuario de un dispositivo lo encontraremos en el manual de instrucciones Slant/Fin SX-150.

Un conjunto de documentos determinado como manual de instrucciones se divide también en tipos más detallados, tales como: instrucciones de montaje Slant/Fin SX-150, instrucciones de servicio, instrucciones cortas o instrucciones de usuario Slant/Fin SX-150. Dependiendo de la situación debes buscar el documento que necesitas. En nuestra página puedes consultar el manual de instrucciones más popular del producto Slant/Fin SX-150.

Manuales de instrucciones parecidos

El manual de instrucciones del dispositivo Slant/Fin SX-150, ¿cómo debería ser?
El manual de instrucciones, también determinado como el manual de usuario o simplemente instrucciones, es un documento técnico que tiene como objetivo ayudar a los usuarios a utilizar Slant/Fin SX-150. Las instrucciones normalmente las realiza un escritor técnico pero en un lenguaje comprensible para todos los usuarios de Slant/Fin SX-150.

El manual de instrucciones completo de Slant/Fin debe contener unos elementos básicos. Una parte de ellos es menos importante, como por ejemplo: la portada / la página principal o las páginas de autor. Sin embargo, lo demás debe facilitarnos la información más importante desde el punto de vista del usuario.

1. Introducción y pistas sobre cómo orientarse con el manual Slant/Fin SX-150 - Al principio de cada manual se deben encontrar las indicaciones acerca de la manera de usar un manual de instrucciones. Debe contener información sobre dónde encontrar el índice Slant/Fin SX-150, preguntas frecuentes o problemas más comunes – son los apartados más buscados por los usuarios de cada manual de instrucciones.
2. Índice - listados de todos los consejos acerca de Slant/Fin SX-150 que encontraremos en el documento
3. Consejos de uso de las funciones básicas del dispositivo Slant/Fin SX-150 - que deben facilitarnos los primeros pasos durante el uso de Slant/Fin SX-150
4. Troubleshooting - una secuencia sistematizada de acciones que nos ayudará a diagnosticar los problemas más importantes con Slant/Fin SX-150
5. FAQ - las preguntas frecuentes
6. Datos de contacto Información acerca de cómo encontrar los datos de contacto del fabricante / servicio de Slant/Fin SX-150 en cada país si no somos capaces de solucionar el problema por nuestra cuenta.

¿Tienes una pregunta acerca de Slant/Fin SX-150?

Utiliza el formulario que se encuentra abajo

Si con la ayuda del manual de instrucciones encontrado no has podido solucionar tu problema con Slant/Fin SX-150, haz una pregunta utilizando el formulario que se encuentra abajo. Si alguno de los usuarios ha tenido un problema parecido con Slant/Fin SX-150 probablemente compartirá una forma de solucionarlo.

Copia el texto de la imagen

Comentarios (0)