Aprilaire 61000652C 8400 Tstat - page 1
840 0 Series Thermostats READ AND SAVE THESE INSTRUCTIONS S a f e t y & Installation Instructions 61000652C 8400 Tstat Install.indd 1 10/13/09 11:08:56 AM ...
-
Aprilaire 61000652C 8400 Tstat - page 2
2 Installation location recommendations ................................................................ 3 Outdoor temperature sensor (optional) ................................................................ 4 Thermostat mounting .............................................................................. 5 Power & reset options ........... ...
-
Aprilaire 61000652C 8400 Tstat - page 3
3 INST ALLA TION INST ALLA TION LOCA TION RECOMMENDA TIONS Thermostat should be mounted: • On aninterior wall,ina frequentlyoccupied space. • Approximately 5‘above floor . • At least18” fromoutsidewall. • Thermostat canbe mountedtoa verticaljunc ...
-
Aprilaire 61000652C 8400 Tstat - page 4
4 OUTDOOR TEMPERA TURE SENSOR (OPTIONAL) Outdoortemperature canbe measuredby attachingan 8052sensor tothe S1and S2terminals.System setting #05(Remote sensor)is usedto enablesensor . Heat pump models can use the outdoor temperature to effectivelyutilize theheat ...
-
Aprilaire 61000652C 8400 Tstat - page 5
5 THERMOST A T MOUNTING 1. Remove theback ofthethermostat, bypressing the tabon thebottom ofthe unit. 2. Pull wiresthrough theopeningon theback ofthe thermostat. 3. Position andlevel thebackof thethermostat onwall and mark t ...
-
Aprilaire 61000652C 8400 Tstat - page 6
6 WIRING TERMINAL Wire specifications 18-24gauge thermostatwire Installation notes • Ensure powerat theHVACequipmentis off. • Loosen screwterminals, insertstrippedwire and re-tighten. • Push theexcess wirebackinto theopening andplug thewal ...
-
Aprilaire 61000652C 8400 Tstat - page 7
7 WIRING – MODEL 8463 & 8444 SINGLE TRANSFORMER (USE JUMPER WIRE) INST ALLA TION C G Y W R S1 S2 RC HEA TING COOLING FAN OUTDOOR TEMP SENSOR JUMPER TRANSFORMER WIRING – MODEL 8463 & 8444 TWO TRANSFORMERS (REMOVE JUMPER WIRE) C G Y W R S1 S2 RC HEA TING COOLING FAN OUTDOOR TEMP SENSOR HEA TING TRANSFORMER COOLING TRANSFORMER 61000652C 84 ...
-
Aprilaire 61000652C 8400 Tstat - page 8
8 WIRING – MODEL 8465 & 8446 SINGLE TRANSFORMER (USE JUMPER WIRE) INST ALLA TION AUX HEA TING COMPRESSOR FAN REVERSE VAL VE FAUL T DETECT OUTDOOR TEMP SENSOR JUMPER TRANSFORMER C G Y W R L S1 S2 O/B RC WIRING – MODEL 8465 & 8446 TWO TRANSFORMERS (REMOVE JUMPER WIRE) AUX HEA TING COMPRESSOR FAN REVERSE VAL VE FAUL T DETECT OUTDOOR TEMP S ...
-
Aprilaire 61000652C 8400 Tstat - page 9
9 WIRING – MODEL 8466 & 8448 SINGLE TRANSFORMER (USE JUMPER WIRE) FOR HEA T/COOL SYSTEM INST ALLA TION 1st HEA TING 1st COOLING FAN 2nd HEA TING 2nd COOLING OUTDOOR TEMP SENSOR NOT USED NOT USED JUMPER TRANSFORMER C G Y W R L S1 S2 O/B W2 Y2 RC WI RI NG – MO DEL 8 46 6 & 844 8 TWO TR AN SF OR ME RS (R EM OV E JU MPER WIRE ) FOR HEA T/CO ...
-
Aprilaire 61000652C 8400 Tstat - page 10
10 INST ALLA TION WIRING – MODEL 8466 & 8448 SINGLE TRANSFORMER (USE JUMPER WIRE) FOR HEA T PUMP SYSTEM 1st AUX HEA TING 1st COMPRESSOR FAN REVERSE VAL VE FAUL T DETECT 2nd AUX HEA TING 2nd COMPRESSOR OUTDOOR TEMP SENSOR HEA T PUMP TRANSFORMER C G Y W R L S1 S2 O/B W2 Y2 RC JUMPER 1st AUX HEA TING 1st COMPRESSOR FAN REVERSE VAL VE FAUL T DETE ...
-
Aprilaire 61000652C 8400 Tstat - page 11
11 SYSTEM SETUP INSTRUCTIONS How to enter the system setup menu to change system settings Press repeatedly until system is set to OFF . Press and hold and for three seconds. Thescreen ofthe firstsetting willbedisplayed. SETUP & TESTING Press or to change the setting. Press to changeto thenext option. ...
-
Aprilaire 61000652C 8400 Tstat - page 12
12 SETUP & TESTING SYSTEM SETUP INSTRUCTIONS (CONTINUED) Thermostatmodels 8448& 8466have theoptionof beingused inheat pumpor heat/coolsystems.Switch SW1 locatedon theback ofthe thermostat’ sface isused toselect this.System settingnumber? ...
-
Aprilaire 61000652C 8400 Tstat - page 13
13 SETUP & TESTING System setting Setting range, default in bold 00 Equipmenttype (8466,8448) (Set by SW1) 0: heat/cool 1: heatpump 01 T emperature scale 0 : Fahrenheit 1: Celsius 02 Fan control in heating 0 : Gas or oil furnace (Equipment controls fan) 1: Electric(Thermostat controlsfan) 0 ...
-
Aprilaire 61000652C 8400 Tstat - page 14
14 SETUP & TESTING System setting Setting range, default in bold 09 1st stage differential 1°F (0.5°C) 1°Fto 4°F(0.5°C to2°C) 10 2ndstage differential(8448, 8466) 1°F (0.5°C) 1°Fto 4°F(0.5°C to2°C) 11 3rdstage differential(8448HP ,8466HP) 1°F (0.5°C) 1°Fto ...
-
Aprilaire 61000652C 8400 Tstat - page 15
15 SETUP & TESTING System setting Setting range, default in bold 16 LowBalance Pt.(8446,8448HP , 8465,8466HP) Systemsetting 05must beenabled 20°F (–7°C) 1°Fto 35°F(–17°C to1°C) or“OFF”to disable 17 HighBalance Pt.(8446,8448HP , 8465,? ...
-
Aprilaire 61000652C 8400 Tstat - page 16
16 SYSTEM TEST MODE Thesystem testmode isused totesta systemafter installation.The outputsof thethermostatcan bemanually activatedone ata timeto testtheirfunction. Thefollowing instructionsshow howto enterthetest modeand turn o ...
-
Aprilaire 61000652C 8400 Tstat - page 17
17 How to enter the system test menu Press repeatedly until system is set to OFF . Press and hold and for three seconds. Thescreen ofthe firsttest step#50is displayed: SYSTEM TEST MODE (CONTINUED) SETUP & TESTING Press to turnon theoutput (01).Formulti stage output, press again? ...
-
Aprilaire 61000652C 8400 Tstat - page 18
18 SETUP & TESTING T est steps for 8444 & 8463 Step Key Input System Setting Display (Output) #2 01 HEA TING ON (W) 01 COOLING ON (Y) 01 FAN ON (G) #50Heat [UP] 0 :Gas ON 1: Elec ON ON [DOWN] #51Cool [UP] ON ON [DOWN] #52 Fan [UP] ON [DOWN] 61000652C 8400 Tstat Install.indd 18 10/13/09 11:09:01 AM ...
-
Aprilaire 61000652C 8400 Tstat - page 19
19 SETUP & TESTING T est steps for 8448HC & 8466HC Step Key Input System Setting Display (Output) #2 01 HEA TING ON (W) 02 HEA TING ON (W2) 01 COOLING ON (Y) 02 COOLING ON (Y2) 01 FAN ON (G) #50Heat 1st[UP] 0 :Gas ON 1: Elec ON ON 2nd[UP] 0 :Gas ON ON 1: Elec ON ON ON [DOWN] #51Cool 1st[UP] ON ON 2nd? ...
-
Aprilaire 61000652C 8400 Tstat - page 20
20 T est steps for 8446 & 8465 Step Key Input System Setting Display (Output) #2 #12 01 AUX HEA TING ON (W) 01 COOL/HEA T ON (Y) 01 FAN ON (G) O/B #50Aux [UP] 0 :Gas ON 1: Elec ON ON [DOWN] #51Cool [UP] 0: O ON ON ON 1: B ON ON [DOWN] 0: O ON 1: B #52 Heat [UP] 0: O ON ON 1: B ON ON ON [DOWN ...
-
Aprilaire 61000652C 8400 Tstat - page 21
21 T est steps for 8448HP & 8466HP Step Key Input System Setting Display (Output) #2 #12 01 AUX HEA TING ON (W) 02 AUX HEA TING ON (W2) 01 COOL/HEA T ON (Y) 02 COOL/HEA T ON (Y2) 01 FAN ON (G) O/B #50Aux 1st[UP] 0 :Gas ON 1: Elec ON ON 2nd[UP] 0 :Gas ON ON 1: Elec ON ON ON [DOWN] #51Cool 1st[UP] 0 :O ...
-
Aprilaire 61000652C 8400 Tstat - page 22
22 QUICK REFERENCE TO CONTROLS & DISPLA Y NON-PROGRAMMABLE MODELS (8444, 8446, 8448) NOTE: BACKLIGHT ISACTIVA TED WITHFIRST BUTTONPRESSAND AUTOMA TICALL Y TURNSOFF . CURRENTINDOOR TEMPERA TURE SYSTEMMODE SETTING FANSETTING SYSTEMMODE FANSETTING BA TTERYDOOR MESSAGECENTER LOW BA TTER ...
-
Aprilaire 61000652C 8400 Tstat - page 23
23 QUICK REFERENCE TO CONTROLS & DISPLA Y PROGRAMMABLE MODELS (8463, 8465, 8466) NOTE: BACKLIGHT ISACTIVA TED WITHFIRST BUTTONPRESSAND AUTOMA TICALL Y TURNSOFF . CURRENTINDOOR TEMPERA TURE SYSTEMMODE SETTING FANSETTING SYSTEMMODE FANSETTING BA TTERYDOOR MESSAGECENTER LOW BA TTERY ...
-
Aprilaire 61000652C 8400 Tstat - page 24
24 THERMOST A T FEA TURES ALL 8400 SERIES THERMOST A TS • Large, clear ,backlit displayiseasy toread –even in the dark. • Displays roomtemperature, temperaturesetting,and optional outdoor temperature. • Dual poweroption (Batteryor24 V AC). • Front ...
-
Aprilaire 61000652C 8400 Tstat - page 25
25 TROUBLESHOOTING DISPLA Y IS BLANK • Check circuitbreaker andresetif necessary . • Make surepower switchatheating &cooling system is on. • Make surefurnace doorisclosed securely . • If thermostatis batterypowered,make surefresh ...
-
Aprilaire 61000652C 8400 Tstat - page 26
26 TROUBLESHOOTING COOLING SYSTEM DOES NOT RESPOND (“COOLING” APPEARS ON SCREEN) • Check for24 V AC atthe equipmentonthe secondary sideof thetransformer betweenpower and common.If voltageis notpresent, checkthecooling equipmentto findthe causeof ...
-
Aprilaire 61000652C 8400 Tstat - page 27
27 SPECIFICA TIONS Electrical Operatingvoltage 24 V AC (18– 30VAC) Current Maximum:2.5A (total),1.0A (singleoutput) Maximumsurge current:5A Power supply Dualpower . Canbe batteryor 24V ACpowered. Whenboth thesources areavailable, batterywillbe usedas? ...
-
Aprilaire 61000652C 8400 Tstat - page 28
28 SPECIFICA TIONS Thermal Outdoor temperature sensor Maximumdistance: 300feet Roomtemperature measurement Displayrange: 32°to 99°F(0°to 40°C) Outdoor temperature measurement Displayrange: -20°to 130°F(-30° to55°C) T emperature setting range Heat:45° to90°F (7°to ...
¿Tienes una pregunta acerca de Aprilaire 61000652C 8400 Tstat?
Utiliza el formulario que se encuentra abajo
Si con la ayuda del manual de instrucciones encontrado no has podido solucionar tu problema con Aprilaire 61000652C 8400 Tstat, haz una pregunta utilizando el formulario que se encuentra abajo. Si alguno de los usuarios ha tenido un problema parecido con Aprilaire 61000652C 8400 Tstat probablemente compartirá una forma de solucionarlo.