    Reference Manual 00809-0100-4690, Rev EA March 2007 Rosemount 2088 and 2090 www .rosemount.com Section 3 Inst allation Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-1 Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-1 General Considerations . . . . . . . . . . . ...

  • Emerson Process Management 2090 - page 2

    Reference Manual 00809-0100-4690, Rev EA March 2007 Rosemount 2088 and 2090 3-2 W arnings Explosions could result in death or serious injury: • Do not remove the transmitter cover in explosive atmospheres when the circuit is alive. • Before connecting a HART -based commu nicator in an explosive atmosphere, make sure the instruments in the loop ...

  • Emerson Process Management 2090 - page 3

    Reference Manual 00809-0100-4690, Rev EA March 2007 3-3 Rosemount 2088 and 2090 Figure 3-1. Installation Flowchart. Check for Leaks (Process Connections) Zero T rim T ransmitter for Mounting Effect s Check Jumper or Switches Wire T ransmitter Power T ransmitter DONE Mount T ransmitter Apply Pressure Refer to T roubleshooting Section Within Specific ...

  • Emerson Process Management 2090 - page 4

    Reference Manual 00809-0100-4690, Rev EA March 2007 Rosemount 2088 and 2090 3-4 GENERAL CONSIDERATIONS The accuracy of the pressure measurement depends on proper installation of the transmitter and impulse piping. The piping between the process and transmitter must accurately transmit pr essure to the transmitter . Mount the transmitter close to th ...

  • Emerson Process Management 2090 - page 5

    Reference Manual 00809-0100-4690, Rev EA March 2007 3-5 Rosemount 2088 and 2090 MECHANICAL CONSIDERATIONS Mounting Rosemount 2088 The Rosemount 2088 Smart T ransmitter weighs approximately 2.44 lb. (1,1 1 kg). The 2088 Analog T ransmitter weighs approximately 1.9 lb. (0,86 kg). In many cases, its comp act size and light weight makes it possible to ...

  • Emerson Process Management 2090 - page 6

    Reference Manual 00809-0100-4690, Rev EA March 2007 Rosemount 2088 and 2090 3-6 Impulse Piping Impulse piping configurations depend on specific measurement conditions. Use the following information and Figur e 3-3 as a guideline when installing impulse piping. Liquids: Make the line tap on the side of the pipe to prevent sediment deposits from plug ...

  • Emerson Process Management 2090 - page 7

    Reference Manual 00809-0100-4690, Rev EA March 2007 3-7 Rosemount 2088 and 2090 Access Requirement s When choosing a mounting location and pos ition, take into account the need for access to the transmitter . Make wiring terminations through the conduit openings at the top of the electronics housing. The field terminal side of the transmitter is cl ...

  • Emerson Process Management 2090 - page 8

    Reference Manual 00809-0100-4690, Rev EA March 2007 Rosemount 2088 and 2090 3-8 Nameplate 3.9 (100) 2X 1 / 4 –20 UNC–2BX 0.60 Deep Mounting Bracket Holes 4.7 (140) T erminal Connections T ransmitter Circuitry Side Optional Meter Cover 5.0 (125) W eld Spud 1.0 (25.4) V essel W all 4.3 (110) 1.05 (26.6) 1.32 (33,4) 5.75 (146) 3X 5 / 16 –18 UNC ...

  • Emerson Process Management 2090 - page 9

    Reference Manual 00809-0100-4690, Rev EA March 2007 3-9 Rosemount 2088 and 2090 Rosemount 2090P Installing the Rosemount 2090P transmitter involves att aching a weld spud to the tapped process vessel, att aching t he transmitter to the weld spud, and making electrical connections. If you intend to use an existing weld spud, proceed to the transmitt ...

  • Emerson Process Management 2090 - page 10

    Reference Manual 00809-0100-4690, Rev EA March 2007 Rosemount 2088 and 2090 3-10 3. Hand tighten the transmitter using the knurled retaining ring, then snug an additional 1 / 8 turn with adjustable pliers. IMPORT ANT Do not over-tighten the retaining ring. A sp anner wrench (P/N 02088-0193-0001) hole is located on the knurled portion of the retaini ...

  • Emerson Process Management 2090 - page 11

    Reference Manual 00809-0100-4690, Rev EA March 2007 3-1 1 Rosemount 2088 and 2090 Rosemount 2090F The Rosemount 2090F sanitary pressu re transmitter is designed to be installed directly to a sanit ary fitting. T he transmitter is available with either a 1.5- or 2-inch clamp connection. When installing the transmitter to the sanit ary fitting it is ...

  • Emerson Process Management 2090 - page 12

    Reference Manual 00809-0100-4690, Rev EA March 2007 Rosemount 2088 and 2090 3-12 Figure 3-9. T ransmitter Load Limitations Field Wiring All power to the transmitter is supplie d over the signal wiring. Signal wiring need not be shielded, but use twisted pairs for best results. Do not run unshielded signal wiring in conduit or open trays with power ...

  • Emerson Process Management 2090 - page 13

    Reference Manual 00809-0100-4690, Rev EA March 2007 3-13 Rosemount 2088 and 2090 Figure 3-10. Rosemount 2088 Smart Signal Wiring T erminals. FAILURE MODE AND SECURITY JUMPERS Failure Mode As part of normal operation, the Rosemount 2088/2090 Smart Pressure T ransmitter continuously monitors its own operation. This automatic diagnostic routine is a t ...

  • Emerson Process Management 2090 - page 14

    Reference Manual 00809-0100-4690, Rev EA March 2007 Rosemount 2088 and 2090 3-14 With a meter inst alled The failure mode alarm jumper is located on the LCD faceplate in the electronics module side of the transm itter housing and is labeled ALARM (See Figure 3-1 1). Do not remove the transmitter cover in explosive atmospheres when the circuit is al ...

  • Emerson Process Management 2090 - page 15

    Reference Manual 00809-0100-4690, Rev EA March 2007 3-15 Rosemount 2088 and 2090 NOTE If either the alarm or security jumper is dislodged or removed from its position the transmitter reverts to default alarm or security settings of: Alarm: Output high; Security: Off ZERO AND SP AN ADJUSTMENT S The smart Rosemount 2088 is equipped with local zero an ...

  • Emerson Process Management 2090 - page 16

    Reference Manual 00809-0100-4690, Rev EA March 2007 Rosemount 2088 and 2090 3-16 Disabling the Zero and Sp an Adjustment s After you rerange the transmitter usi ng the sp an and zero adjustments, you may wish to disable the adjustments to prevent further reranging. T o disable the span and zero adjustment s, activate the transmitter security jumper ...

Fabricante Emerson Process Management Categoría Satellite Radio

Los documentos del dispositivo Emerson Process Management 2090 que obtenemos del fabricante se pueden dividir en varios grupos. Entre ellos están::
- dibujos técnicos Emerson Process Management
- manuales de instrucciones 2090
- hojas de producto Emerson Process Management
- folletos informativos
- o etiquetas energéticas Emerson Process Management 2090
Todos son importantes, pero lo más importante desde el punto de vista del usuario de un dispositivo lo encontraremos en el manual de instrucciones Emerson Process Management 2090.

Un conjunto de documentos determinado como manual de instrucciones se divide también en tipos más detallados, tales como: instrucciones de montaje Emerson Process Management 2090, instrucciones de servicio, instrucciones cortas o instrucciones de usuario Emerson Process Management 2090. Dependiendo de la situación debes buscar el documento que necesitas. En nuestra página puedes consultar el manual de instrucciones más popular del producto Emerson Process Management 2090.

Manuales de instrucciones parecidos

El manual de instrucciones del dispositivo Emerson Process Management 2090, ¿cómo debería ser?
El manual de instrucciones, también determinado como el manual de usuario o simplemente instrucciones, es un documento técnico que tiene como objetivo ayudar a los usuarios a utilizar Emerson Process Management 2090. Las instrucciones normalmente las realiza un escritor técnico pero en un lenguaje comprensible para todos los usuarios de Emerson Process Management 2090.

El manual de instrucciones completo de Emerson Process Management debe contener unos elementos básicos. Una parte de ellos es menos importante, como por ejemplo: la portada / la página principal o las páginas de autor. Sin embargo, lo demás debe facilitarnos la información más importante desde el punto de vista del usuario.

1. Introducción y pistas sobre cómo orientarse con el manual Emerson Process Management 2090 - Al principio de cada manual se deben encontrar las indicaciones acerca de la manera de usar un manual de instrucciones. Debe contener información sobre dónde encontrar el índice Emerson Process Management 2090, preguntas frecuentes o problemas más comunes – son los apartados más buscados por los usuarios de cada manual de instrucciones.
2. Índice - listados de todos los consejos acerca de Emerson Process Management 2090 que encontraremos en el documento
3. Consejos de uso de las funciones básicas del dispositivo Emerson Process Management 2090 - que deben facilitarnos los primeros pasos durante el uso de Emerson Process Management 2090
4. Troubleshooting - una secuencia sistematizada de acciones que nos ayudará a diagnosticar los problemas más importantes con Emerson Process Management 2090
5. FAQ - las preguntas frecuentes
6. Datos de contacto Información acerca de cómo encontrar los datos de contacto del fabricante / servicio de Emerson Process Management 2090 en cada país si no somos capaces de solucionar el problema por nuestra cuenta.

¿Tienes una pregunta acerca de Emerson Process Management 2090?

Utiliza el formulario que se encuentra abajo

Si con la ayuda del manual de instrucciones encontrado no has podido solucionar tu problema con Emerson Process Management 2090, haz una pregunta utilizando el formulario que se encuentra abajo. Si alguno de los usuarios ha tenido un problema parecido con Emerson Process Management 2090 probablemente compartirá una forma de solucionarlo.