Manuel d’utilisation Emerson XDR

40 pages 3.87 mb
Télécharger

Aller à la page of 40

Summary
  • Emerson XDR - page 1

    Precision Cooling For Business -Critic al C ontinuity™ Li eber t ® XDR ™ User Ma nual ...

  • Emerson XDR - page 2

    I MPORT ANT S AFETY G UIDELINES SAVE THESE INSTRUCTIONS NOTICE Risk of overhead interference. Can cause module or structural damage. The module may be too tall to fit throu gh a doorwa y whil e on the skid. Measure the module and doorway heights and verify clearances by referring to the instal lation plans and other site-specific drawings and docum ...

  • Emerson XDR - page 3

    i T ABLE OF CONTENTS I MPORT ANT S AFETY G UIDELINES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I NSIDE F RONT C OVER 1.0 C OMPONENT L OCATIO NS AND M ODEL N UMBER N OMENCLAT URE . . . . . . . . . . . . . . . . . . . . . 1 2.0 I NTRODUCTI ON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...

  • Emerson XDR - page 4

    ii 6.7 Field Installation of Liebert XD Flex Pipe Kit on Liebert XDR . . . . . . . . . . . . . . . . . . . . . . 18 6.7.1 Connecting Methods—One-Shot Couplings for Pre-Charged Refriger ant Option . . . . . . . . . 19 6.7.2 Connect a Liebert XDR with One- Sho t Couplings to Liebert XD Fle x Pipe . . . . . . . . . . . . . . 20 6.7.3 Connection Meth ...

  • Emerson XDR - page 5

    iii FIGURES Figure 1 Liebert XD R component locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Figure 2 Liebert XDR mo del number nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Figure 3 Generic piping layout . . . . . . . . . . . . ...

  • Emerson XDR - page 6

    iv ...

  • Emerson XDR - page 7

    Component Locati ons and Model Numbe r Nomenclature 1 1.0 C OMPONENT L OCATIONS AND M ODEL N UMBER N OMENCLATURE Figure 1 Liebert XDR component locations Figure 2 Liebert XDR model number nomenclatu re 1. Supply Line 2. Door Safety Catch 3. Return Line 4. Evaporator Coils 5. Locking Door Latch 6. Removable Installation Handles 7. Frame 1 2 3 4 5 6 ...

  • Emerson XDR - page 8

    Introd uction 2 2.0 I NTRODUCTION 2.1 References This document must be used together with site specific documenta tion and documentation fo r other parts of the system. 2.2 Pre-Inst a llation Checks • Check the received materials to be sure all required assemblies and parts have been received. If you discover any external dama ge, report it to th ...

  • Emerson XDR - page 9

    General Product Information 3 3.0 G ENERAL P RODUCT I NFORMATION 3.1 Product/System Description The Liebert XDR is a cooling s ystem for high-den sity heat loads that mounts on the rear of a 24" x 42U rack (for other sizes consult the factory) and maintains access to the back of the server rack. Room air is drawn in through the front of the ra ...

  • Emerson XDR - page 10

    General Product Information 4 3.2.1 Recyclable Packaging All material used to package this module is recyclable. Please save for future use or dispose of the material appropriately. NOTICE Risk of improper storage. Can cause module damage. Keep the module indoors and protected from dampness, freezing temperatures and contact damage. NOTICE Risk of ...

  • Emerson XDR - page 11

    General Product Information 5 3.2.3 Unp acking the Module Do not unpack the Liebert XDR before moving it to the installation lo cation. Once at the installation point: 1. Cut the banding and place all packaged modules on the floor for unpacking . 2. Unbend all metal tabs as shown in Figure 5 . Use any of these tools to unbend th e tabs: flat-blade ...

  • Emerson XDR - page 12

    General Product Information 6 Figure 5 Removing p ackaging Cut Bands Unbend T abs Remove the T op Cover Center T op Brace Hardware and Keys Remove Side Panels Remove Foam Protecting T op of Module Ste p 1 Ste p 2 Ste p 3 Ste ps 4 , a nd 5 Step 6 Ste p 7 ...

  • Emerson XDR - page 13

    General Product Information 7 Figure 6 Remove Liebert XDR from p allet 3.2.4 Removing the Liebert XDR from the Pallet 1. Unfold the module bag to expose the Liebert XDR. 2. Compare the serial tag i nformation on the Li ebert XDR to the bill of lading informat ion. If the information does not matc h the product specifi e d, contact your local sales ...

  • Emerson XDR - page 14

    Mechanical Considerations 8 4.0 M ECHANICAL C ONSIDERATIONS 4.1 Liebert XDR Dimensions The Liebert XDR is engineered to fit on the rear of a rack enclosure measuring approximately 24" x 42U. Consult the factory for other sizes. Figures 7 , 8 and 9 illustrate the module’s dim ensions and the location of pipes. Figure 11 shows the attachment p ...

  • Emerson XDR - page 15

    Mechanical Considerations 9 Figure 8 Overall dimensions wit h one-shot coupling (pre-c harged) 1-1/2" (38mm) 1-5/16" (34mm) 78-3/8" (1991mm) 5-1/8" (130mm) 83-1/2" (2121mm) 5-7/8" (149mm) 1 10deg 23-1/2" (597mm) 27-3/8" (695mm) 6-1/2" (165mm) 27-3/8" (695mm) 20-1/2" (520mm) 1-1/8" (29mm) 2 ...

  • Emerson XDR - page 16

    Mechanical Considerations 10 Figure 9 Overall dimensions wit h removable coupling 4.2 Determining Placement in the Conditioned Sp ace Refer to site-specifi c drawings for exact placement. Efficient cooling of the ra ck equipment depends on proper placement of equipment, prop er us e of blanking plates in any voids in the rack, and good cable manage ...

  • Emerson XDR - page 17

    Mechanical Considerations 11 4.3 Airflow The server fans draw air into the equipment enclosur e. After heated the air, the server fans force the air across the Liebert XDR’s two coils. The Liebert XD R has a low air-side pressu re drop (similar to a rack with perforated doors). The se rver fans within the rack create su ffic ient airflow to mov e ...

  • Emerson XDR - page 18

    Installation 12 5.0 I NST ALLATION 5.1 Inst alling the Rack-M ounting Kit onto the Rack The Liebert XDR module mounts on the rear o f the rack using a mounting kit. The mounting ki t secures the Liebert XDR's fra me to the rack. Two ra ils are attached to the rear of the rack with M6 x 12 bolts. The number of bolts can vary depending on the ra ...

  • Emerson XDR - page 19

    Installation 13 5.3 Door Safety Catch The door safety catch prevents th e door from opening be yond 110°. When the doo r is fully open, th e safety catch will ho ld door in place. To re lease th e door, push up on the door catch and close the door. ...

  • Emerson XDR - page 20

    Piping 14 6.0 P IPING Refer to site-specific drawings fo r general locations of the piping connections. The drawings should specify where the piping connects to the Liebert XDR. 6.1 European Union Fluorinated Greenhouse Gas Requirement s Stationary air conditioning, refrigerat ion, heat pu mp equipment and stationa ry fire protection sys- tems in t ...

  • Emerson XDR - page 21

    Piping 15 Figure 13 T ypical Lieb ert XDR piping—non-interlaced conne ction 6.3 Connection Met hods and Point s Refer to site specific drawings for general locati ons of the piping connect ions. For Liebert XDR con- nection locations, refer also to Figures 14 , 17 and 21 . The assembly and connection means used for piping in the Liebert XD system ...

  • Emerson XDR - page 22

    Piping 16 6.5.1 Brazing Prep arations The assembly and connection means used for piping in the Liebert XD system are similar to those used for conven tional refrigeration s ystems. All piping shoul d be installed with hig h-temperature brazed joints. Soft soldering is not recommended. After the holding charge has been v ented and before brazing, wr ...

  • Emerson XDR - page 23

    Piping 17 Figure 15 Hard pipe connection diagram 6.6.1 Leak-Checking and Evacuation Refer to the Lieb ert XDC or Liebert XDP user ma nual for procedures fo r evacuation, leak check, charging and startup. 6.6.2 Header System The Liebert XDR module sy stem with op tional flex ible piping requires use of the Liebert XD prefabri- cated piping assembly. ...

  • Emerson XDR - page 24

    Piping 18 6.7 Field Inst allation of Liebert XD Flex Pipe Kit on Liebert XDR If you are not performing a service installation or a field-ret rofit, skip this section and proceed with the instructions in 6.7.2 - Connect a Liebert XDR with One-Shot Couplings to Lieber t XD Flex Pipe . Liebert XD Flex Pipe kit s are available i n lengths of 4, 6, 8 an ...

  • Emerson XDR - page 25

    Piping 19 6.7.1 Connecting Methods—One-Shot Couplings for Pre-Charged Refrigerant Option Liebert XDRs with the pre-charged option are equipped wi th one-shot coupling s on the supply and return fittings. These contain a ch arge of R-134a refrigerant under pressure wi thin the module. This charge must not be vented. Do not remove the pipe caps or ...

  • Emerson XDR - page 26

    Piping 20 6.7.2 Connect a Liebert XDR with One-Shot Couplings to Liebert XD Flex Pipe NOTICE Risk of improper reuse of Li ebert XD Flex Pipes with on e-shot couplings. Can cause refrigerant leaks. Liebert XD Flex Pipe s with one-shot coup lings must not be removed from the Liebert XDR unless they are being replace d with Liebert XD Flex Pipes with ...

  • Emerson XDR - page 27

    Piping 21 Figure 20 Hex body , union nut on one-shot coupling NOTICE Risk of improper tightening . Can cause equipment damage. It is impe rative that t he brass body on t he Liebert XD Flex Pipe coupling doe s not rotate wh ile the union nut is being tightened. If the brass bo dy rotates, it may dama ge the Liebert XD Flex Pipe. 5. Hold the brass b ...

  • Emerson XDR - page 28

    Piping 22 6.7.3 Connection Methods—Removable Couplings The assembly and connection means used for piping in the Liebert XD system are the same as those used in conventional refrigera tion systems. Observe all standard practices during installa tion and startup to prevent damage and contamination. Both supply and return fittings may be su pplied w ...

  • Emerson XDR - page 29

    Piping 23 Figure 22 Removable couplings 6.7.5 Connect a Liebert XDR with Liebert XD Flex Pipe to a Liebert XD System NOTICE Risk of refrigerant loss. Can cause environmental polluti on and equipment malfunction. Before connecting the Liebert XDR with Liebert XD Flex Pipe to the prefabricated piping mains, check t he whol e system for leaks. Check t ...

  • Emerson XDR - page 30

    Piping 24 Figure 23 Coupling size indicator Figure 24 Liebert XD pref abricated piping assembly 7. Use mineral oil or polyol ester oil to lubrica te th e face of the poppet valve and the seal around the poppet valve on the female connector (on the Liebert XD Flex Pipe ) (see Figure 25 ). 8. Apply mineral oil or polyol ester oil to the stainless ste ...

  • Emerson XDR - page 31

    Piping 25 Figure 25 Oil rings on header and Liebert XD Flex Pipe connectors 9. Thread the union nut of the Lieb ert XD Flex Pipe coupling onto the port coupling to ensure the threads mate properly. 10. Using the wrench arrangem ent shown in Figure 26 , torque the couplings to the values in Table 5 . NOTICE Risk of twisted or kinked piping. Can caus ...

  • Emerson XDR - page 32

    Piping 26 Figure 27 Det ail view of Liebert XD Fl ex Pipe and prefabricated pipin g port 11. Repeat Steps 3 through 10 for the re maining Liebert XD Flex Pipe. 12. For a Liebert XDR module with removable coupli ngs, open the return an d then supply service valves. If the Liebert XDR is pre-charged DO NOT open either of the service valves. 13. Refer ...

  • Emerson XDR - page 33

    Piping 27 6.7.6 Disconnect a Liebert XD Flex Pipe from a L iebert XD System T ools Required • Two adjustable wrenches with a ma ximum adjustment size of 2 inches 1. Close the serv ice valve in the supply line. 2. Ensure there is ai rflow across the coil. 3. Wait tw o minutes for the refrigerant to flow o ut of the module. 4. Close the serv ice va ...

  • Emerson XDR - page 34

    Piping 28 6.7.7 Disconnecting the Liebert XD Flex Pipe from the Liebert XDR NOTICE Risk of improper reuse of Li ebert XD Flex Pipes with on e-shot connections. Can cause refrigerant leaks. Liebert XD Flex Pipe s with one-shot conn ections must not be remov ed from the Liebert XD R unless they are being replace d with Liebert XD Flex Pipes with one- ...

  • Emerson XDR - page 35

    Installation Checklist and System F ill for S t artup 29 7.0 I NST ALLATION C HECK LIST AND S YSTEM F ILL FOR S T ARTUP 7.1 Checklist for Proper Inst allation ___ 1. Liebert XDR modules are securely attached to the ca binet and aligned properly wit h the rack. ___ 2. Check to ensure there are no obstructions that prevent the Liebert X DR from openi ...

  • Emerson XDR - page 36

    Starting the Liebert XD System 30 8.0 S TA R T I N G THE L IEBERT XD S YSTEM Refer to the user manual for the refrigerant supply unit, either a Liebert XDP or Liebert XDC, for details on starting the system. Th e Liebert XDP use r manual is SL-16644 and the Liebert XDC user manual is SL-1667 1. The user manuals were supplied with the un its and are ...

  • Emerson XDR - page 37

    Maintenance 31 9.0 M AINTENANCE Minimal maintenance is required to keep the Liebert XDR operatin g a t optimal levels. The module should be cleaned and checked for da mage. Suggested main tenance includes: • Cooling fins—Clean any dust and debris from the coolin g fins, taking care not to bend them. 9.1 Fluorinated Greenhouse Gas Requirement s ...

  • Emerson XDR - page 38

    Specifications 32 10.0 S PECIFICATIONS T able 6 Liebert XDR specifications Models XDR20B1- * XDR20B1P * (Pre-Charged R-134a) XDR20B1R * Cooling Capacity, Nominal, rated at 104ºF (40°C) EAT & 2400 ft 3 /m (68m 3 /m) 20.5 kW (5.8 tons) Conditions 55°F (13°C) entering fluid tempera ture 50°F (10°C) or lower dew point Dimensions, inches (mm) ...

  • Emerson XDR - page 39

    ...

  • Emerson XDR - page 40

    Ensuring The Hi gh A vai lab ilit y Of Mission-Critic al Dat a And App lic ations. Emerson Net work P ower , the global leader in enabling business-critical continuity , ensures network re siliency and adaptabilit y through a family of technologies—inc luding Liebert power and cooling technologies—that prot ect and suppor t business-critical sy ...

Fabricant Emerson Catégorie Air Conditioner

Les documents que nous recevons du fabricant de l'appareilEmerson XDR peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques Emerson
- manuels d’utilisations XDR
- fiches produit Emerson
- dépliants
- ou étiquettes-énergie Emerson XDR
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation Emerson XDR.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation Emerson XDR, manuels d’entretien, brefs manuels ou manuels de l’utilisateur Emerson XDR. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit Emerson XDR.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil Emerson XDR, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser Emerson XDR par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs Emerson XDR.

Le manuel d’utilisation complet Emerson, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel Emerson XDR - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières Emerson XDR, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lEmerson XDR qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil Emerson XDR - qui devraient nous aider dans les premières étapes lors de l'utilisation Emerson XDR
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de Emerson XDR
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service Emerson XDR dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de Emerson XDR?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec Emerson XDR, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec Emerson XDR il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)