    343615-YTG-B-0308 FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE SINGLE P ACKAGE GA S/ELECTRIC UNITS AND SINGLE P ACKAGE AIR CONDITIONERS DY 036, 048 & 060 3, 4 & 5 NOMINAL TONS 14.00 SEER ® TECHNICAL GUIDE DESCRIPTION YORK Sunline Magnum ™ units are convertible single pack- age air conditioners with a commo n cabin e ...

  • York DY 060 - page 2

    343615-YTG-B-0308 2 Johnson Controls Unitary Products T ABLE OF CONTENTS DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 PRODUCT NOMEN CLATURE . . . . . . . . . . . . . . . . . 3 FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 FACTORY-INSTALLED OPTIONS . . . . . . . . . . . . . . 6 FIELD-INSTALLE ...

  • York DY 060 - page 3

    343615-YTG-B-0308 Johnson Controls Unitary Produ cts 3 PRODUCT NOMENCLA TURE D Y 048 N04 A 2 A AA 2 0 1 2 4 A D = A/C, Single Pkg., R-22 Product Category Airflow D = Direct Drive/Motorized Damper B = Direct Drive/Single Input Economizer A = Direct Drive Product Generation 2 = Second Generation C00 = Cooling Only. Suitable for Field Installed Electr ...

  • York DY 060 - page 4

    343615-YTG-B-0308 4 Johnson Controls Unitary Products FEA TURES All models are available with a wide variety of factory- mounted options such as stainless steel heat exchangers, electric heaters, phase monito r , convenience outlet, dirty filter switch, disconnect switch, smo ke detectors, and coil guard to make them suitable for almost every appli ...

  • York DY 060 - page 5

    343615-YTG-B-0308 Johnson Controls Unitary Produ cts 5 Gas/Electric Electric/Electric and Heat Pump FIGURE 1 - UNIT CUT A W A Y 3/4 " PVC female condensate drain Knockout for side control entry GFCI convenience outlet Smoke detector Slide-in economizer Economizer hood HACR breaker 20 Gauge aluminized steel tubular heat exchanger Electric heat ...

  • York DY 060 - page 6

    343615-YTG-B-0308 6 Johnson Controls Unitary Products F ACTOR Y -INST ALLED OPTIONS • SINGLE INPUT ELECTR ONIC ENTHALPY ECONO- MIZERS - Includes a slide-in / plug-in damper assemb ly with fully modulating spring-return motor actuator capa- ble of introducing up to 100% outdoor air with nominal 1% leakage type dampers. The enthalpy system co ntain ...

  • York DY 060 - page 7

    343615-YTG-B-0308 Johnson Controls Unitary Produ cts 7 • ST AINLESS STEEL HEA T EXCHANGER - F or applica- tions in corrosive environments, this option provides a full stainless steel heat exch anger assembly . • ST AINLESS STEEL DRAIN P AN - An optional rust- proof stainless steel drain pan is available to provide years of trouble-free operatio ...

  • York DY 060 - page 8

    343615-YTG-B-0308 8 Johnson Controls Unitary Products • ENTHALPY ACCESSOR Y CONTROL KIT - This kit contains the required components to convert a single enthalpy economizer to dual enthalpy . • BURGLAR BARS - Mount in the supply and return openings to prevent entry into the duct work. • FLUE EXHAUST EXTENSION KIT - In l ocations wit h wind or ...

  • York DY 060 - page 9

    343615-YTG-B-0308 Johnson Controls Unitary Produ cts 9 T AB LE 4: DY036 INDOOR SOUND POWER LEVELS (HORIZONT AL DUCTED INLET) UNIT DESCRIPTION / MODEL CONFIGURATION Indoor Blower Speed (RPM) Blower Static Pressure (IWG) Airflow (CFM) Blower Motor BHP 63 80 82 80 82 78 83 81 85 1 2 5 7 6 7 77 6 7 7 8 2 8 38 1 8 2 2 5 0 5 6 5 95 6 6 0 6 0 6 15 8 6 0 5 ...

  • York DY 060 - page 10

    343615-YTG-B-0308 10 Johnson Controls Unitary Products T AB LE 6: DY03 6 IN DOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET) UNIT DESCRIPTION / MODEL CONFIGURATION Indoor Blower Speed (RPM) Blower Static Pressure (IWG) Airflow (CFM) Blower Motor BHP 63 78 82 78 82 80 85 80 84 125 70 75 70 74 71 80 71 79 250 55 60 55 60 59 61 58 62 500 47 50 47 50 52 ...

  • York DY 060 - page 11

    343615-YTG-B-0308 Johnson Controls Unitary Produ cts 11 T AB LE 8: DY048 INDOOR SOUND POWER LEVELS (HORIZONT AL DUCTED INLET) UNIT DESCRIPTION / MODEL CONFIGURATION Indoor Blower Speed (RPM) Blower Static Pressure (IWG) Airflow (CFM) Blower Motor BHP 63 74 97 74 95 77 90 77 90 125 70 86 69 86 73 78 72 77 250 53 58 52 57 60 61 58 61 500 49 55 47 54 ...

  • York DY 060 - page 12

    343615-YTG-B-0308 12 Johnson Controls Unitary Products T AB LE 10: DY048 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET) UNIT DESCRIPTION / MODEL CONFIGURATION Indoor Blower Speed (RPM) Blower Static Pressure (IWG) Airflow (CFM) Blower Motor BHP 63 76 95 77 93 80 91 79 91 1 2 5 6 8 8 46 7 8 2 7 6 8 47 3 8 0 2 5 0 5 4 5 75 2 5 6 6 3 6 15 7 5 9 5 0 ...

  • York DY 060 - page 13

    343615-YTG-B-0308 Johnson Controls Unitary Produ cts 13 T AB LE 12: DY060 INDOOR SOUND POWER LEVELS (HORIZONT AL DUCTED INLET) UNIT DESCRIPTION / MODEL CONFIGURATION Indoor Blower Speed (RPM) Blower Static Pressure (IWG) Airflow (CFM) Blower Motor BHP 63 77 84 77 84 81 85 79 84 12 57 1 7 1 7 2 7 3 7 4 7 5 7 1 7 2 25 05 7 5 8 5 5 5 6 6 6 6 6 6 0 6 1 ...

  • York DY 060 - page 14

    343615-YTG-B-0308 14 Johnson Controls Unitary Products T AB LE 14: DY060 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET) UNIT DESCRIPTION / MODEL CONFIGURATION Indoor Blower Speed (RPM) Blower Static Pressure (IWG) Airflow (CFM) Blower Motor BHP 63 77 86 79 88 81 86 83 87 125 69 70 70 72 71 73 72 72 250 56 63 56 58 64 72 63 69 500 50 52 48 49 57 ...

  • York DY 060 - page 15

    343615-YTG-B-0308 Johnson Controls Unitary Produ cts 15 T AB LE 16: DY036 COOLING CAP ACITIES (3 TON) Air on Evap- orator Co il T emperatur e of Air on Condenser Coil 75°F 85°F CFM WB (°F) To t a l Cap. 1 (MBH) To t a l 2 Input (kW) Sensible Cap acity (MBH) 1 Return Dry Bulb (°F) To t a l Cap. 1 (MBH) To t a l 2 Input (kW) Sensible Capa ci ty ( ...

  • York DY 060 - page 16

    343615-YTG-B-0308 16 Johnson Controls Unitary Products T AB LE 17: DY048 COOLING CAP ACITIES (4 TON) Air on Evap- orator Co il T emperatur e of Air on Condenser Coil 75°F 85°F CFM WB (°F) To t a l Cap. 1 (MBH) To t a l 2 Input (kW) Sensible Capacity (MBH) 1 Return Dry Bulb (°F) To t a l Cap. 1 (MBH) To t a l 2 Input (kW) Sensible Capa ci ty (MB ...

  • York DY 060 - page 17

    343615-YTG-B-0308 Johnson Controls Unitary Produ cts 17 T AB LE 18: DY060 COOLING CAP ACITIES (5 TON) Air on Evap- orator Co il T emperatur e of Air on Condenser Coil 75°F 85°F CFM WB (°F) To t a l Cap. 1 (MBH) To t a l 2 Input (kW) Sensible Cap acity (MBH) 1 Return Dry Bulb (°F) To t a l Cap. 1 (MBH) To t a l 2 Input (kW) Sensible Capa ci ty ( ...

  • York DY 060 - page 18

    343615-YTG-B-0308 18 Johnson Controls Unitary Products T AB LE 19: SUPPLY AIR BLOWER PERFORMANCE (DY036, 048, & 060 DIRECT DRIVE) SIDE DUCT APPLICATION UNIT TONNAGE MOT OR 1 SPEED A V AILABLE EXTERNAL ST A TIC PRESSURE - IWG 2 0.2 0.3 0.4 0. 5 0.6 0.7 0.8 0.9 1.0 CFM WATT S CFM WATT S CFM WATT S CFM WATT S CFM WATT S CFM WATT S CFM WATT S CFM W ...

  • York DY 060 - page 19

    343615-YTG-B-0308 Johnson Controls Unitary Produ cts 19 1. Deduct these resistance values from the available external st atic pressure shown i n SUPPL Y AIR BLOWER PERFORMANCE T ables. 2. Add these resistance va lues to the av ailable static resi stance values on SUPP L Y AIR BLOWER PERFORMANCE T ables. 3. The pressure through the economizer is gre ...

  • York DY 060 - page 20

    343615-YTG-B-0308 20 Johnson Controls Unitary Products T AB LE 23: ELECTRICAL DA T A - DY036, 048 & 060 DIRECT DRIVE W/O POWERED CONVENIENCE OUTLET Size (Tons) Volt Compressors (each) OD Fan Motors (each) Supply Blower Motor Pwr Conv Outlet Electric Heat Option MCA 1 (Amps) Max Fuse 2 / Breaker 3 Size (Amps ) RLA LRA MCC FLA FLA FLA Model kW St ...

  • York DY 060 - page 21

    343615-YTG-B-0308 Johnson Controls Unitary Produ cts 21 060 (5.0) 208-1-60 28.8 145.0 45.0 2.3 7.6 0.0 None - - - 45.9 50 E05 4.0 1 19.2 45.9 50 E07 5.6 1 26.9 45.9 50 E10 8.0 1 38.5 57.6 60 E15 11.9 2 57.2 81.0 90 E20 15.9 2 76.4 105. 1 110 E30 22.2 2 106.7 142.9 150 230-1-60 28.8 145.0 45.0 2.3 7.6 0.0 None - - - 45.9 50 E05 5.3 1 23.0 45.9 50 E0 ...

  • York DY 060 - page 22

    343615-YTG-B-0308 22 Johnson Controls Unitary Products T AB LE 24: ELECTRICAL DA T A - DY036, 048 & 060 DIRECT DRIVE W/ POWERED CONVENIENCE OUTLET Size (Tons) Volt Compressors (each) OD Fan Motors (each) Supply Blower Motor Pwr Conv Outlet Electric Heat Option MCA 1 (Amps) Max Fuse 2 / Breaker 3 Size (Amps ) RLA LRA MCC FLA FLA FLA Model kW Sta ...

  • York DY 060 - page 23

    343615-YTG-B-0308 Johnson Controls Unitary Produ cts 23 060 (5.0) 208-1-60 28.8 145.0 45.0 2.3 7.6 10.0 None - - - 55.9 60 E05 4.0 1 19.2 55.9 60 E07 5.6 1 26.9 55.9 60 E10 8.0 1 38.5 70.1 80 E15 11.9 2 57.2 93.5 100 E20 15.9 2 76.4 117. 6 125 E30 22.2 2 106.7 155.4 175 230-1-60 28.8 145.0 45.0 2.3 7.6 10.0 None - - - 55.9 60 E05 5.3 1 23.0 55.9 60 ...

  • York DY 060 - page 24

    343615-YTG-B-0308 24 Johnson Controls Unitary Products T ABLE 25: DY PHYSICAL DATA MODELS DY 036 048 060 EV APORA TOR BLOWER Centrifuga l Blower (Di a. x Wd. in.) 12 X 10 12 X 10 12 X 10 Fan Motor H P (Direct Drive) 3/4 1 1 EV APORA TOR COIL Rows Deep 3 4 4 Fins Per Inch 13 13 13 Face Area (Ft. 2 ) 5.1 5.1 5.1 CONDENSER F ANS Propeller Di a . (in.) ...

  • York DY 060 - page 25

    343615-YTG-B-0308 Johnson Controls Unitary Produ cts 25 FIGURE 2 - TYPICAL FIELD POWER & CONTROL WIRING REFER TO THE ELECTRICAL DA T A T ABLES TO SIZE THE DISCONNECT SWITCH, O VERCURRENT PROTEC- TION AND WIRING. RC RH Y1 Y2 W1 W2 G LED 1 LED 2 COM A1 A2 T T B R Y1 Y2 G C X OCC W2 W1 THERMOSTAT 1 TERMINALS UNIT TERMINAL STRIP TB1 24 VOLT TRANSFO ...

  • York DY 060 - page 26

    343615-YTG-B-0308 26 Johnson Controls Unitary Products FIGURE 3 - UNIT DIMENSIONS (3 - 5 TO N COOLING ONL Y/ELECTRIC HEA T ) FRONT VIEW FIGURE 4 - UNIT DIMENSIONS (3 - 5 TON COOLING/GAS HEA T) FRONT VIEW ...

  • York DY 060 - page 27

    343615-YTG-B-0308 Johnson Controls Unitary Produ cts 27 FIGURE 5 - UNIT WITH ECONOMIZER RAINHOOD DETAIL “A” FIGURE 6 - UNIT WITH FIXED OUTD OOR AIR/MOTORIZED DAMPER RAINHOOD DETAIL “B” ...

  • York DY 060 - page 28

    343615-YTG-B-0308 28 Johnson Controls Unitary Products FIGURE 7 - UNIT DIMENSIONS (REAR VIEW) FIGURE 8 - DISCONNECT/B LOWER ACCESS LOCA TION T ABLE 28: UTILITIES ENTR Y HOLE OPENIN G SIZE (DIA.) USED FOR A 7/8” KO 1 1. Opening in the bottom to the unit can be located by the side in the insulation. Control Wi ri ng 2 2. Do not remove the 2” knoc ...

  • York DY 060 - page 29

    343615-YTG-B-0308 Johnson Controls Unitary Produ cts 29 FIGURE 9 - TYPICAL APPLICA TIONS ...

  • York DY 060 - page 30

    343615-YTG-B-0308 30 Johnson Controls Unitary Products FIGURE 10 -FOUR A ND SIX POINT LOADING 44 7 / 8 82 1 / 4 Y X A B C D CONDENSER COIL END OF UNIT FRONT OF UNIT APPROXIMATE CENTER OF GRAVITY BACK OF UNIT 44 7 / 8 82 1 / 4 Y X A B C D E F CONDENSER COIL END OF UNIT FRONT OF UNIT APPROXIMATE CENTER OF GRAVITY BACK OF UNIT T AB LE 30: DY 4 AND 6 P ...

  • York DY 060 - page 31

    343615-YTG-B-0308 Johnson Controls Unitary Produ cts 31 T ABLE 32: OPERA TING WEIGHTS (LBS.) MO DE L S IZ E 3 TON 4 TO N 5 TO N BASIC UNIT DY (Cooling Onl y) 575 58 5 590 DY (Gas/Electric) N04 615 - - N06 - 635 - N08 635 - 650 N10 - 655 660 D06 625 635 640 D10 645 655 660 OPTIONS Economizer 5 0 Motorized Damp er 26 Electric H eater 5 - 7 kW 18 10 - ...

  • York DY 060 - page 32

    343615-YTG-B-0308 32 Johnson Controls Unitary Products GUIDE SPECIFICA TIONS GENERAL Units shall be manufactured by Y ork International Unitary Products Group in an ISO 9001 certified facility . Y ork's Sunline Magnum ™ units are convertible single pack- age units. Although the units are primarily designed for curb mounting on a roof, they c ...

  • York DY 060 - page 33

    343615-YTG-B-0308 Johnson Controls Unitary Produ cts 33 Coils: a. Evaporator and condenser coils shall have alumi- num plate fins mechanically bonded to seamless internally enhanced copper tubes with all joints brazed. S pecial Phenolic coating shall be availab le as a factory option. b. Evaporator and Condenser coils shall be of the direct expansi ...

  • York DY 060 - page 34

    343615-YTG-B-0308 34 Johnson Controls Unitary Products OPTIONAL OUTDOOR AIR (Shall be made availa ble by either/or): • ELECTRONIC ENTHALPY AUT OMA TIC ECONO- MIZER - Outdoor and return air dampers that are inter- locked and positioned by a fully-modulating, spring return damper actuator . The maximum leakage rate for the outdoor air intake damper ...

  • York DY 060 - page 35

    343615-YTG-B-0308 Johnson Controls Unitary Produ cts 35 ...

  • York DY 060 - page 36

    Subject to change without notice. Pr inted in U.S.A. 343615-YTG-B-0308 Copyright © 2008 b y Johnson Controls, Inc. All righ ts reserved. Supersedes: 343615-YT G-A-0807 Johnson Controls Un itary Products 5005 York Drive Norman, OK 73069 ...

Fabricant York Catégorie Air Conditioner

Les documents que nous recevons du fabricant de l'appareilYork DY 060 peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques York
- manuels d’utilisations DY 060
- fiches produit York
- dépliants
- ou étiquettes-énergie York DY 060
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation York DY 060.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation York DY 060, manuels d’entretien, brefs manuels ou manuels de l’utilisateur York DY 060. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit York DY 060.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil York DY 060, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser York DY 060 par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs York DY 060.

Le manuel d’utilisation complet York, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel York DY 060 - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières York DY 060, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lYork DY 060 qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil York DY 060 - qui devraient nous aider dans les premières étapes lors de l'utilisation York DY 060
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de York DY 060
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service York DY 060 dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de York DY 060?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec York DY 060, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec York DY 060 il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)