    Single-Package Rooftop Products with Energy-Saving Features • direct spark ignition • low sound levels • 81% AFUE on most units • 10 SEER Features/Benefits One-piece heating and cooling units with low installation costs, depend- able performance, and easy maintenance Easy installation Factory-assembled package is a compact, fully self-cont ...

  • Carrier 48SS - page 2

    Energy-saving, dir ect-spark igni- tion saves gas by operating only when the room ther mostat calls for heating. Standard units are fur nished with natural gas controls. A low- cost, field-installed kit for propane conversion is available for all units. Monoport inshot bur ners produce precise air-to-gas mixture which provides for clean and effic ...

  • Carrier 48SS - page 3

    T able of contents Page Features/Benefits .................................................. 1 , 2 Model Number Nomenclature ........................................ 3 ARI Capacities .................................................... 4 , 5 Physical Data ...................................................... 6 Options and Accessories ............ ...

  • Carrier 48SS - page 4

    ARI* capacities COOLING CAP ACITIES AND EFFICIENCIES UNIT 48SS NOMINAL TONS ST ANDARD CFM NET COOLING† CAP ACITIES SEER† SOUND RA TINGS** (Bels) 018040 1 1 ⁄ 2 600 17,000 10.0 7.4 024040 024060 2 800 24,000 10.0 7.6 030040 030060 030080 2 1 ⁄ 2 1000 29,200 10.0 8.0 036060 036080 036100 036120 3 1200 36,000 10.0 8.0 042060 042080 042100 0421 ...

  • Carrier 48SS - page 5

    HEA TING CAP ACITIES AND EFFICIENCIES UNIT 48SS HEA TING INPUT (Btuh) OUTPUT CAP ACITY (Btuh) TEMPERA TURE RISE RANGE (°F) AFUE (%) CSE (%) 018040 024040 030040 40,000 32,800 20-50 20-50 20-50 81 81 81 76.5 76.5 76.5 024060 030060 036060 042060 60,000 48,600 25-55 25-55 25-55 25-55 81 81 81 81 77.5 77.5 77.5 77.5 030080 036080 042080 048080 060080 ...

  • Carrier 48SS - page 6

    Physical data UNIT SIZE 48SS 018040 024040 024060 030040 030060 030080 036060 036080 036100 036120 NOMINAL CAP ACITY (ton) 1 1 ⁄ 2 22 2 1 ⁄ 2 2 1 ⁄ 2 2 1 ⁄ 2 3333 OPERA TING WEIGHT (lb) Without Base Rail 272 303 315 320 324 324 336 336 348 348 With Optional Base Rail 296 327 339 344 356 356 360 360 372 372 COMPRESSORS Rotary Reciprocating Q ...

  • Carrier 48SS - page 7

    Options and accessories Factory-installed options Unit with base rail provides holes for rigging and forklifts as well as an elevated mounting frame that gives additional structural support for horizontal installations. Ideal for light commercial applications. Downflow option unit is shipped from factory configured for vertical ductwork connectio ...

  • Carrier 48SS - page 8

    Base unit dimensions REQ’D CLEARANCES FOR SERVICING. in. (mm) Duct panel ........................ 0 Unit top ....................... 3 6 (914) Side opposite ducts .................. 3 6 (914) Compressor access .................. 3 6 (914) (Except for NEC requirements) REQ’D CLEARANCES TO COMBUSTIBLE MA T’L. in. (mm) Maximum extension of overh ...

  • Carrier 48SS - page 9

    48SS018-042 WITH OPTIONAL BASE RAIL REQ’D CLEARANCES FOR SERVICING. in. (mm) Duct panel ........................ 0 Unit top ...................... 3 6 (914) Side opposite ducts ................. 3 6 (914) Compressor access ................. 3 6 (914) (Except for NEC requirements) REQ’D CLEARANCES TO COMBUSTIBLE MA T’L. in. (mm) Maximum extens ...

  • Carrier 48SS - page 10

    Base unit dimensions (cont) 48SS048,060 WITHOUT OPTIONAL BASE RAIL REQ’D CLEARANCES FOR SERVICING. in. (mm) Duct panel ....................... 0 Unit top ...................... 3 6 (914) Side opposite ducts ................ 3 6 (914) Compressor access ................ 3 6 (914) (Except for NEC requirements) REQ’D CLEARANCES T O COMBUSTIBLE MA T ...

  • Carrier 48SS - page 11

    48SS048,060 WITH OPTIONAL BASE RAIL REQ’D CLEARANCES FOR SERVICING. in. (mm) Duct panel ........................ 0 Unit top ...................... 3 6 (914) Side opposite ducts ................. 3 6 (914) Compressor access ................. 3 6 (914) (Except for NEC requirements) REQ’D CLEARANCES TO COMBUSTIBLE MA T’L. in. (mm) Maximum extens ...

  • Carrier 48SS - page 12

    Accessory dimensions ROOF CURB DIMENSIONS P ART NUMBER ‘ ‘A ’’ 48SS CPRFCURB001A00 8 9 [203] CPRFCURB002A00 1 1 9 [279] CPRFCURB003A00 14 9 [356] NOTES: 1. Roof curb must be set up for unit being installed. 2. Seal strip must be applied as required for unit being installed. 3. Dimensions in [ ] are in millimeters. 4. Roof curb is made of 16 ...

  • Carrier 48SS - page 13

    Selection procedure (with example) I Deter mine cooling and heating requir ements at design conditions: Given: Required Cooling Capacity (TC) ...... 34,000 Btuh Sensible Heat Capacity (SHC) ....... 24,000 Btuh Required Heating Capacity .......... 60,000 Btuh Condenser Entering-Air T emperature ........ 9 5 F Indoor-Air T emperature ....... 8 0 F ed ...

  • Carrier 48SS - page 14

    Performance data COOLING CAP ACITIES 48SS018 TEMP (F) AIR ENT COND EV AP AIR — CFM/BF 525/0.10 600/0.12 675/0.13 Evap Air — Ewb (F) 62 67 72 62 67 72 62 67 72 85 TC 15.8 17.4 19.0 16.0 17.6 19.2 16.1 17.8 19.3 SHC 13.6 1 1.2 8.7 14.4 1 1.8 9.0 15.1 12.4 9.2 kW 1.76 1.80 1.85 1.81 1.86 1.90 1.86 1.91 1.95 95 TC 15.3 16.9 18.5 15.5 17.0 18.7 15.6 ...

  • Carrier 48SS - page 15

    COOLING CAP ACITIES (cont) 48SS048 TEMP (F) AIR ENT COND EV AP AIR — CFM/BF 1400/0.08 1600/0.10 1800/0.11 Evap Air — Ewb (F) 62 67 72 62 67 72 62 67 72 85 TC 43.8 48.3 52.9 44.5 49.1 53.7 45.1 49.6 53.9 SHC 39.4 32.7 25.6 41.9 34.6 26.4 44.1 36.4 27.1 kW 4.76 4.85 4.95 4.87 4.97 5.07 4.99 5.08 5.17 95 TC 41.9 46.4 50.9 42.6 47.0 51.7 43.3 47.5 ...

  • Carrier 48SS - page 16

    Performance data (cont) DR Y COIL AIR DELIVERY* — HORIZONT AL DISCHARGE (Deduct 10% for 208 v) UNIT SIZE 48SS MOTOR SPEED 230 AND 460 VOL T HORIZONT AL DISCHARGE External Static Pressure (in. wg) 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 018 Low W atts 230 225 220 210 195 170 ————— C f m 7 6 0 7 4 5 7 2 5 6 9 5 6 4 0 5 4 0 ———? ...

  • Carrier 48SS - page 17

    DR Y COIL AIR DELIVERY* — VER TICAL DISCHARGE (Deduct 10% for 208 v) UNIT SIZE 48SS MOTOR SPEED 230 AND 460 VOL T VERTICAL DISCHARGE External Static Pressure (in. wg) 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 018 Low W atts — 295 251 223 201 176 149 124 — — — Cfm — 821 817 753 665 536 343 164 — — — High W atts 401 376 346 322 29 ...

  • Carrier 48SS - page 18

    Performance data (cont) WET COIL PRESSURE DROP UNIT SIZE AIRFLOW (cfm) PRESSURE DROP (in. wg) 018 600 0.069 700 0.082 800 0.102 900 0.1 16 024 600 0.039 700 0.058 800 0.075 900 0.088 030 900 0.088 1000 0.095 1200 0.123 036 1000 0.068 1200 0.088 1400 0.108 1600 0.123 042 1000 0.048 1200 0.069 1400 0.088 1600 0.102 048 1400 0.068 1600 0.075 1800 0.08 ...

  • Carrier 48SS - page 19

    T ypical piping and wiring Power Wiring Control Wiring Outdoor Airflow Indoor Airflow NEC — National Electrical Code HORIZONT AL DISCHARGE DOWNFLOW DISCHARGE CEILING SUPPL Y -AIR FLEXIBLE DUCT ROOF-MOUNTING CURB ROOF RETURN-AIR FLEXIBLE DUCT 19 ...

  • Carrier 48SS - page 20

    Application data Condensate trap — A 2-in. condensate trap must be field supplied. Ductwork — Secure downflow discharge ductwork to roof curb. For horizontal discharge applications, attach duct- work to unit with flanges. T o convert a unit to downflow dischar ge or horizon- tal discharge — Units are equipped with factory-installed duct co ...

  • Carrier 48SS - page 21

    T ypical control wiring schematic, 48SS018-060; 208/230-1-60 LEGEND AW G — American Wire Gage BR — Blower Relay C— Contactor CAP — Capacitor CH — Crankcase Heater COMP — Compressor Motor CR — Combustion Relay EQUIP — Equipment FL — Fuse Link FS — Flame Sensor FU — Fuse GND — Ground GVR — Gas V alve Relay HS — Hall Effect ...

  • Carrier 48SS - page 22

    T ypical control wiring schematic, 48SS030-060; 208/230-3-60 LEGEND AW G — American Wire Gage BR — Blower Relay C— Contactor CAP — Capacitor CH — Crankcase Heater COMP — Compressor Motor CR — Combustion Relay EQUIP — Equipment FL — Fuse Link FS — Flame Sensor FU — Fuse GND — Ground GVR — Gas V alve Relay HS — Hall Effect ...

  • Carrier 48SS - page 23

    T ypical control wiring schematic, 48SS036-060; 460-3-60 LEGEND AW G — American Wire Gage BR — Blower Relay C— Contactor CAP — Capacitor CH — Crankcase Heater COMP — Compressor Motor CR — Combustion Relay EQUIP — Equipment FS — Flame Sensor FU — Fuse GND — Ground GVR — Gas V alve Relay HS — Hall Effect Sensor HV TRAN — H ...

  • Carrier 48SS - page 24

    Electrical data UNIT 48SS V -PH-HZ VOL T AGE RANGE COMPRESSOR COND FA N MOTOR INDOOR FA N POWER SUPPL Y A W G6 0C MIN WIRE SIZE† MAX WIRE LENGTH (ft) Min Max RLA LRA FLA FLA MCA MOCP* 018 208/230-1-60 187 253 7.6 45 0.7 1.8 12.0 15 14 75 024 208/230-1-60 187 253 12.4 61 0.7 2.0 18.2 30 12 80 030 208/230-1-60 187 253 14.4 82 1.4 2.0 21.8 30 10 100 ...

  • Carrier 48SS - page 25

    Controls Sequence of operation Heating — On a call for heating, ter minal ‘‘W’’ of the ther- mostat is energized, starting the induced-draft motor . When the hall-effect sensor on the induced-draft motor senses that it has reached the required speed, the bur ner sequence be- gins. This function is per for med by the integrated control boa ...

  • Carrier 48SS - page 26

    Guide specifications Packaged Heating/Cooling Units Constant V olume Application HV AC Guide Specifications Size Range: 1 1 ⁄ 2 to 5 T ons, Nominal Cooling 40,000 to 140,000 Btuh, Nominal Input Heating Carrier Model Number: 48SS Part 1 — General 1.01 SYSTEM DESCRIPTION Outdoor rooftop mounted, gas heating/electric cool- ing unit utilizing a r ...

  • Carrier 48SS - page 27

    I. Operating Characteristics: 1. Unit shall be capable of starting and running at 125 F ambient outdoor temperature per maxi- mum load criteria of ARI Standard 210/240. 2. Compressor with standard controls shall be ca- pable of operation in cooling down to 40 F am- bient outdoor temperature. 3. Unit provided with fan time delay to prevent cold air ...

  • Carrier 48SS - page 28

    Carrier Corporation • Syracuse, New Y ork 13221 9-98 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 1 4 Ta b 1 a 6 a Page 28 Catalog No. 524-890 Printed in U.S.A. PC 1 1 1 Form 48SS-4PD Replaces: 48SS-3PD ...

Fabricant Carrier Catégorie Gas Heater

Les documents que nous recevons du fabricant de l'appareilCarrier 48SS peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques Carrier
- manuels d’utilisations 48SS
- fiches produit Carrier
- dépliants
- ou étiquettes-énergie Carrier 48SS
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation Carrier 48SS.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation Carrier 48SS, manuels d’entretien, brefs manuels ou manuels de l’utilisateur Carrier 48SS. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit Carrier 48SS.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil Carrier 48SS, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser Carrier 48SS par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs Carrier 48SS.

Le manuel d’utilisation complet Carrier, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel Carrier 48SS - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières Carrier 48SS, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lCarrier 48SS qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil Carrier 48SS - qui devraient nous aider dans les premières étapes lors de l'utilisation Carrier 48SS
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de Carrier 48SS
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service Carrier 48SS dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de Carrier 48SS?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec Carrier 48SS, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec Carrier 48SS il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)