    PLACE THESE INSTRUCTIONS ADJACENT TO BOILER AND NOTIFY OWNER TO KEEP FOR FUTURE REFERENCE PRINTED 0210 317693-000 GAS-FIRED COMMERCIAL COPPER BOILERS FOR HYDRONIC HEA TING AND HOT W A TER SUPPL Y • INST ALLA TION • OPERA TION • MAINTENANCE • LIMITED W ARRANTY • INDOOR ONL Y MODELS HW 300, 399, 420, 520, 610, 670 UP-FLOW MODELS W ARNING: I ...

  • A.O. Smith HW 610 - page 2

    2 IMPORT ANT DEFINITIONS • Qualied Installer: A qualied installer must have ability equivalent to a licensed tradesman in the elds of plumbing, air supply , venting and gas supply , including a thorough understanding of the requirements of the National Fuel Gas Code or the Natural Gas and Propane Installation Code as it relates to the in ...

  • A.O. Smith HW 610 - page 3

    3 GENERAL SAFETY ...

  • A.O. Smith HW 610 - page 4

    4 SAFE INST ALLA TION, USE AND SER VICE.......................................................................................................................................................................... 2 GENERAL SAFETY............................................................................................................................ ...

  • A.O. Smith HW 610 - page 5

    5 EXTRA OPENING FOR THERMOMETER AND RELIEF V AL VE HW-520, 610 AND HW--670 DIMENSIONS AND CAP ACITY DA T A T ABLE 1 DIMENSIONS IN INCHES MODELS HW-300 HW-399 HW-420 HW -520 PROP ANE HW-610/670 NA TURAL HW-610/670 A Overall height 65 (1651) 57-1/8 (1451) 57-1/8 (1451) 68-5/16 (1735) 67 (1702) 64-3/4 (1645) B Height to T op of Jacket 43-1/4 (1099) 45 ...

  • A.O. Smith HW 610 - page 6

    6 T ABLE 2, RECOVERY CAP ACITIES Model Input °F 20 40 50 60 70 80 BTUH (kW) °C 1 1.1 22.2 27.7 33.3 38.8 44.4 HW 300 300,000 (88) GPH 1439 719 576 480 41 1 360 LPH 5448 2724 2179 1816 1556 1362 HW 399 399,000 (1 17) GPH 1914 957 765 638 547 478 LPH 7245 3623 2898 2415 2070 181 1 HW 420 420,000 (123) GPH 2014 1007 806 671 576 504 LPH 7627 3813 305 ...

  • A.O. Smith HW 610 - page 7

    7 INTRODUCTION This design complies with the current edition of the ANSI Z21.13 low-pressure boiler standard. Compliance under this standard implies that when the boiler underwent test, the gas manifold and control assembly pro vided on the boiler met safe lighting and other performance criteria. Detailed installation diagrams are found in this man ...

  • A.O. Smith HW 610 - page 8

    8 HIGH AL TITUDE INST ALLA TIONS IN CANADA Acceptance of these models for use at altitudes above 2000 feet (600 m) is based on eld test of the individual installation by the provincial/state authority having jurisdiction. IN THE U.S.A. W ARNING INST ALLA TIONS ABOVE 2000 FEET REQUIRE REPLACEMENT OF THE BURNER ORIFICES IN ACCORDANCE WITH THE CURR ...

  • A.O. Smith HW 610 - page 9

    9 THERMAL BALANCER Figure 4 shows the internal wiring of the thermal balancer . The device may be tested after disconnecting the four leads from their respective terminals on the unit. 1. Apply a test light to the yellow and red leads. • The lamp should light as the contact in this circuit is normally closed when the resistor is cool. 2. Apply a ...

  • A.O. Smith HW 610 - page 10

    10 CAUTION Paddle must be trimmed at the dotted arc. It must not touch the pipe or have any restriction when installed. FIGURE 6. T o adjust the ow rate setting: 1. Remove the ow switch cover . 2. For higher ow rate - turn the range adjusting screw clockwise. 3 . For lower flow rate - turn the range adjusting screw counterclockwise. CAUTIO ...

  • A.O. Smith HW 610 - page 11

    11 Co de, S ect ion IV o r CSA B51 , as ap pli cab le . Sel ect a r el ie f val ve wi th a discharge NOT less than the boiler input, and a pressure rating NOT exceeding the working pressure of any component in the system. A. O. Sm ith su ppl ie s a 125 psi re lief v al ve for h ot wat er su pply s ys tems and 50 psi rel ief val ve for space h eatin ...

  • A.O. Smith HW 610 - page 12

    12 W ater T emperature T ime to Produce 2nd & 3rd Degree Burns on Adult Skin OVER: 170°F (77°C) 160°F (71°C) 150°F (65°C) 140°F (60°C) 130°F (54°C) 120°F (49°C) Nearly Instantaneous About 1/2 second About 1-1/2 seconds Less than 5 seconds About 30 seconds More than 5 minutes USE A NTI- SCA LD VAL V E( S) in the hot water system to r ...

  • A.O. Smith HW 610 - page 13

    13 P ER MI T O PE RATI ON O F G AS A PP LI AN CE S I F I NS T AL LE D 18 INCHES OR MORE ABOVE THE FLOOR. THIS MA Y REDUCE THE RISK IF LOCA TION IN SUCH AN AREA CANNOT BE A VOIDED. W ARNING FLAMMABLE ITEMS, PRESSURIZED CONT AINERS OR ANY OTHER POTENTIAL FIRE HAZARDOUS ARTICLES MUST NEVER BE PLACED ON OR ADJACENT TO THE BOILER. OPEN CONT AINERS OF FL ...

  • A.O. Smith HW 610 - page 14

    14 INST ALLA TION CLEARANCES These boilers are approved for installation on combustible ooring in an alcove with minimum clearance to combustibles of: T ABLE 4 HW 300 HW 399 HW 420 HW 520 HW 610 & 670 TOP 28" (71 1.2) 32" (812.8) 24" (609.6) 24" (609.6) 24" (609.6) SIDES 6" (152.4) 6" (152.4) 24" (609. ...

  • A.O. Smith HW 610 - page 15

    15 Building materials must not come in contact with combustion products from stack or chimney , due to the degradating properties of ue products. Flue products must have a minimum clearance of 4 feet (1.22m) horizontally from, and in no case above or below , unless a 4-foot (1.22m) horizontal distance is maintained, from electric meters, gas met ...

  • A.O. Smith HW 610 - page 16

    16 4. MUL TIPLE VENT T ABLE T able 5 on page 17 has been compiled to show the material sizes in a T ype B doublewall combined vent system. Refer to CAN/CSA B149 .1 (current edition), or the ASHRAE 1983 Equipmen t V olume for further information. A combined vent system is one in which two or more boilers at one level are attached to a common vent. I ...

  • A.O. Smith HW 610 - page 17

    17 T ABLE 5, COMBINED VENT SIZING T ABLES MODEL HW-300 BOILER Input: 300,000 Btuh Draft Hood Outlet 8" Required Connector or Smoke Pipe Diameter Connector Rise in Feet T otal Vent Height (Measured in Feet Above Draft Hood) 10 15 20 30 40 50 60 80 100 Connector Diameter (in Inches) 1 10 10 10 10 10 10 10 10 10 2 10 10 10 10 10 10 10 10 10 3 10 ...

  • A.O. Smith HW 610 - page 18

    18 1. CONVENTIONAL INST ALLA TIONS All modern hydronic type boilers are exceptionally fast heating units. The low water volumes in relation to ring rates require special attention to water ow rates for smooth, efcient operation. These considerations for the A. O. Smith copper heat exchanger boilers are covered below . Conventional 20 0 F ( ...

  • A.O. Smith HW 610 - page 19

    19 NO. SUGGESTED ITEMS FOR INST ALLA TION 1 Short pipe nipple and pair of boiler loop tees in piping between system supply and return. One set per each group of boilers. 2 Boiler pipe loop. See piping sizing data. 3 Boiler circulator . See pump sizing data. 4 Thermometer . 5 Theraltimeter . 6 Plug cock to control ow rate. 7 Safety ow switches ...

  • A.O. Smith HW 610 - page 20

    20 5. VENT V AL VES It is recommended that automatic, loose key or screwdriver type vent valves be installed at each convector or radiator . 6. MANIFOLD HEADERS Split systems with individual supply and return lines from the boiler room should normally have this piping connected to supply and return manifold headers near the boiler . T o achieve goo ...

  • A.O. Smith HW 610 - page 21

    21 U s e t a b l e 7, o r C A N / C S A B 1 4 9 .1 ( c u r r e n t e d i t i o n ) t o s i z e i r o n p i p e o r e q u i v a l e n t g a s s u p p l y l i n e . Ta b l e 7 i s b a s e d o n a p r e s s u r e d r o p o f 0 . 3 i n c h e s o f w a t e r a n d a s p e c i f i c g r a v i t y o f 0 . 6 0 a p p r o x i m a t e l y t h a t o f n a t u ...

  • A.O. Smith HW 610 - page 22

    22 • In table 7 on page 21, select the row showing the distance to the most remote outlet or the next longer distance if the table does not give the exact length. This is the only distance used in determining the size of any section of gas piping. If the gravity factor is to be applied, the values in the selected row of table 7 are multiplied by ...

  • A.O. Smith HW 610 - page 23

    23 Adjustment, if required, is performed as follows: 1. Set primary system temperature control dial (thermostat) at lowest setting so that boiler will not call for heat. 2. Attach a pressure gauge to the tapping in the control string elbow . 3. Reset primary system temperature control dial (thermostat) to highest setting. Main burner will now ignit ...

  • A.O. Smith HW 610 - page 24

    24 120 VA C 60 HZ L1 (HOT) L2 (NEUTRAL) L1 (HOT) L2 (NEUTRAL) 120 VA C 60 HZ 120V 24V HIGH LIMIT IGNITION MODULE CHASSIS GROUND IGNITOR WIRE TO PILOT NOTE: IF REPLACING AN Y FA CTOR Y WIRING, USE TYPE 105°C WIRE OR EQUI VA LENT , EXCEPT FOR THE IGNITION WIRE WHICH USES 250°C WIRE AND THE COIL LIMI T WHICH USES 200°C WIRE. 192359-000 Rev . 3 %%UW ...

  • A.O. Smith HW 610 - page 25

    25 2. LINEAR-TEMP INST ALLA TIONS Cont rol for t hese systems i s de cided mainly by t he t ype of b uilding system co ntrolling t hat is desired. A sing le boiler ins tallati on might b e c o nt r o ll e d d i re c t ly f r o m s p ac e t em p e ra tu r e t h er m o s ta t (s ) . Mult iple b oiler installat ions a re mo re ef fect ive when the boi ...

  • A.O. Smith HW 610 - page 26

    26 NOTE: 1. Building temperature controls supply electric power to building circulator . 2. Main ow switch proves main water ow before energizing sequencing and resetting controls. 3. Outdoor thermostat required if building controls do not provide automatic shutdown of reset controls during warm weather . Boilers and Secondary Circulator are ...

  • A.O. Smith HW 610 - page 27

    27 NOTE: 1. Building temperature controls supply electric power to building circulator . 2. Main ow switch proves main water ow before energizing sequencing and resetting controls. 3. Out door the rmostat require d if build ing control s do not provide automatic shutdown of reset controls during warm weather . Boilers and Secondary Circulator ...

  • A.O. Smith HW 610 - page 28

    28 CER-TEMP 80 - 1 UNIT INST ALLA TION - FOR HOT W A TER SUPPL Y APPLICA TION CANADIAN MODELS, JUNCTION BOX W/6 TERMINALS FIGURE 21. FIGURE 23. CER-TEMP 80 - 1 UNIT INST ALLA TION - FOR HOT W A TER SUPPL Y APPLICA TION U.S. MODELS, JUCNTION BOX W/4 TERMINALS FIGURE 22. ...

  • A.O. Smith HW 610 - page 29

    29 CER-TEMP 80 - 2 OR 3 UNIT INST ALLA TION - FOR HOT W A TER SUPPL Y APPLICA TION CANADIAN MODELS, JUNCTION BOX W/6 TERMINALS FIGURE 24. ...

  • A.O. Smith HW 610 - page 30

    30 SCHEMA TIC CANADIAN MODELS, JUNCTION BOX W/6 TERMINALS FIGURE 25. ...

  • A.O. Smith HW 610 - page 31

    31 CER-TEMP 80 - 2 OR 3 UNIT INST ALLA TION CONNECTION DIAGRAM (FOR HOT W A TER SUPPL Y APPLICA TION) U.S. MODELS, JUNCTION BOX W/4 TERMINALS FIGURE 26. ...

  • A.O. Smith HW 610 - page 32

    32 CER-TEMP 80 - 2 OR 3 UNIT INST ALLA TION SCHEMA TIC DIAGRAM (FOR HOT W A TER SUPPL Y APPLICA TION) U.S. MODELS, JUNCTION BOX W/4 TERMINALS FIGURE 27. ...

  • A.O. Smith HW 610 - page 33

    33 FIGURE 28. IMPORT ANT THE INST ALL A TION OF SAFET Y FLOW SWIT CH AS SH OWN IS REQUI RED TO PROT ECT THE BOIL ER IN CASE OF W A TE R SER VIC E INTERRUPTION OR CIRCULA TOR F AILURE. + P IPIN G AND FITT INGS BET WEEN GA TE V AL VES A ND B OILE RS SHO ULD BE BRAS S O R BR ONZE . OTHE R P IPI NG SHOU LD CONFORM T O LOCAL CODES. GA TE V AL VES ARE SH ...

  • A.O. Smith HW 610 - page 34

    34 FIGURE 29. ONE HW-300, HW -399, HW-420, HW-520, HW -610 OR ONE HW-670 UP-FLOW MODEL COMMERCIAL BOILER WITH HORIZONT AL T ANK WIRING - FIGURES 16 and 17 on pages 24 and 25. INST ALL IN ACCORDANCE WITH ALL LOCAL CODES IMPORT ANT THE INST ALLA TION OF SAFETY FLOW SWITCH AS SHOWN IS REQUIRED T O PROTECT THE BOILER IN CASE OF W A TER SERVICE INTERRUP ...

  • A.O. Smith HW 610 - page 35

    35 TWO HW-399's, HW -420's, HW-520's, HW-610's or HW -670's UP-FLOW MODEL COMMERCIAL BOILER WITH VERTICAL T ANK, CER-TEMP 80 IMPORT ANT THE INST ALLA TION OF SAFETY FLOW SWITCH AS SHOWN IS REQU IRED TO PRO TECT THE BOILER IN CASE OF W A TER SER VICE INTERRUPTION OR CIRCULA TOR F AILURE. + PIPING AND FITTINGS BETWEEN GA TE V ...

  • A.O. Smith HW 610 - page 36

    36 FIGURE 31. TWO HW-300's, HW -399's, HW-420's, HW-520's, HW -610's OR HW-670's UP-FLOW MODEL COMMERCIAL BOILER WITH HORIZONT AL T ANK IMPORT ANT THE INST ALLA TION OF SAFETY FLOW SWITCH AS SHOWN IS REQUIRED T O PROTECT THE BOILER IN CASE OF W A TER SERVICE INTERRUPTION OR CIRCULA T OR F AILURE. + PIPING AND FITTINGS ...

  • A.O. Smith HW 610 - page 37

    37 THREE HW-520's, HW -610's OR HW-670's UP-FLOW MODEL COMMERCIAL BOILER WITH VERTICAL T ANK, CER-TEMP 80 IMPORT ANT THE INST ALLA TION OF SAFETY FLOW SWITCH AS SHOWN IS REQUIRED TO PROTECT THE BOILER IN CASE OF WA TER SERVICE INTERRUPTION OR CIRCULA TOR F AILURE. + PI PING A ND FI TTIN GS BE TWE EN GA TE V AL VES AN D BOI LER S SHO ...

  • A.O. Smith HW 610 - page 38

    38 THREE HW-520's, HW -610's OR HW-670's UP-FLOW MODEL COMMERCIAL BOILER WITH HORIZONT AL T ANK, CER-TEMP 80 IMPORT ANT THE INST ALLA TION OF SAFETY FLOW SWITCH AS SHOWN IS REQUIRED TO PROTECT THE BOILER IN CASE OF WA TER SERVICE INTERRUPTION OR CIRCULA TOR F AILURE. + PIPING AND FITTINGS BETWEEN GA TE V AL VES AND BOILERS SHOULD BE ...

  • A.O. Smith HW 610 - page 39

    39 W ARNING After placing boiler into operation, the ignition system safety shutoff device must be tested by the following test method. 1 . Reset High Limit T emperature Control to lowest setting. (See gure 2 on page 8). 2. Reset System Controller to maximum setting, causing a call for heat and allowing unit to run until High Limit T emperature ...

  • A.O. Smith HW 610 - page 40

    40 4. Reinstall the burner manifold assembly on boiler . 5. Restore electrical power and gas supply to boiler . • Put the boiler back in operation by following the lighting instructions in this manual or on the lighting and operating label on the boiler . See pages 43 - 44. • Check for gas leaks and proper boiler and vent operation. 2. PILOT BU ...

  • A.O. Smith HW 610 - page 41

    41 CHECKING AND ADJUSTING THE INPUT 1. Follow steps 1 thru 6 of the OPERA TING INSTRUCTIONS. 2 . At t ac h a p re ss ur e g au ge o r a m an o met er to t he m an if ol d p re ss ur e t ap pi ng an d r ef er to ta bl e 10 fo r c or r ec t ma ni fo l d pressure. 3. Follow step s 7 thru 1 1 of the OPER A TI NG INSTRU CTIONS . 4. Use this formula to ? ...

  • A.O. Smith HW 610 - page 42

    42 ST ART ST AGE 1 TRIAL FOR IGNITION ST AGE 2 MAIN BURNER OPERA TION END THERMOST A T (CONTROLLER) CALLS FOR HEA T SP ARK GENERA TOR POWERED First valve (pilot) operator opens PILOT BURNER OPERA TION Pilot burner lights. Pilot burner does not light Module senses Module Response ame current. S-8600M After 15 sec. ignition shut-down. 5 minute tim ...

  • A.O. Smith HW 610 - page 43

    43 FOR YOUR SAFETY READ BEFORE LIGHTING W ARNING : FLAMMABL E If you do not fo ll ow these instr uctions e xactly , a fire or e xplosion may result causing prope rt y damag e, personal inju ry or loss of li fe . C. D. WHA T TO DO IF Y OU SMELL GAS DO NOT T RY TO LIGHT A NY APPLIANCE. DO NOT TOUCH A NY ELECTRIC SWITCH; DO NOT USE A NY PHONE IN YOUR ...

  • A.O. Smith HW 610 - page 44

    44 FOR YOUR SAFETY READ BEFORE OPER AT ING W ARNING: FLAMMABLE If you do not fo ll ow these instr uctions e xactly , a fire or ex plosion ma y result causing prope rt y damag e, personal inju ry or loss of li fe . A. B. THIS APPLIANCE IS EQUIPPED WIT H AN IGNITION DEVICE WHICH A UT OM AT ICAL LY LIGHTS THE PILO T. DO NOT T RY TO LIGHT THE PILOT BY ...

  • A.O. Smith HW 610 - page 45

    45 At the time of removal of an existing boiler , the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation. Seal any unused openings in the common venting system. Visually inspect th ...

  • A.O. Smith HW 610 - page 46

    46 CLEANING AND FLUSHING INSTRUCTIONS INTERNAL CONT AMINANTS T he h yd r on i c s ys te m m u st b e i n te r na l ly c l e an e d a nd f l us h ed a f te r a n e w o r r ep l ac e m en t b o i le r h a s b e en in st a l le d to r e m ove contaminants t hat may have ac cumulated during installati on. T hi s is do u bl y i m po r t a nt wh e n a r ...

  • A.O. Smith HW 610 - page 47

    47 TROUBLESHOOTING CER-TEMP 80 RECOVER Y SYSTEM CHECKOUT PROCEDURE Use this checkout for Cer-T emp 80 Recovery Systems. (For hot water supply application only) Checkout Sequence System Operation Cause Remedy Contact Incorrect Set tank temperature control (thermostat) 20°F (10°C) below tank water temperature. Circulating pump and burner shut off. ...

  • A.O. Smith HW 610 - page 48

    48 CHECKING HONEYWELL S-8600H OR S-8610M INTERMITTENT IGNITION CONTROLS T urn off gas supply . Is voltage (24 V ac) across the 24 V terminals on module during “Call for heat”? T urn off power supply . Is ignition cable rmly plugged into pilot assembly and module? Is gro und wire rm ly a tta ch ed t o pi lot asse mbl y and GND term inal on ...

  • A.O. Smith HW 610 - page 49

    49 CHECKING HONEYWELL S8600H OR S-8610M INTERMITTENT IGNITION CONTROLS SP ARK A T PILOT BURNER BUT PILOT WILL NOT LIGHT Ensure all manual shutoff valves are fully open; all lters are clean; all gas connections are gas tight; pilot tubing is not damaged, obstructed or kinked; and pilot orice is unclogged. Check for air in gas line, purge (blee ...

  • A.O. Smith HW 610 - page 50

    50 CHECKING HONEYWELL S-8600H OR S8610M INTERMITTENT IGNITION CONTROLS PILOT BURNER LIGHTS BUT MAIN BURNER DOES NOT LIGHT Does the pilot ame cover 3/8” to 1/2” of ingniter/sensor rod? Does spark stay on for more than 15 seconds after the pilot is “proven” (lit)? Ensure the ground wire and ignition cable are separate from each other (prev ...

  • A.O. Smith HW 610 - page 51

    51 CHECKING HONEYWELL S8600H OR S-8610M INTERMITTENT IGNITION CONTROLS NO SP ARK A T PILOT BURNER BUT PILOT WILL NOT LIGHT T urn off gas supply . Is there a good connection between terminals? Is module securely attached to appliance for good ground connection? Is voltage (24V AC) across transformer positive terminal and GND with "call for heat ...

  • A.O. Smith HW 610 - page 52

    52 The following procedures are provided as a general guide. Any module should be replaced if it does not perform properly on checkout or troubleshooting. In addition, replace any module if it is wet or looks like it has ever been wet. LED ST A TUS AND TROUBLESHOOTING The control has two LEDs; one for ame sensing and one for system status: FIGUR ...

  • A.O. Smith HW 610 - page 53

    53 T able 12. Continuous Retry Models C, M, E, and K Only - Green LED Status Codes Green LED Flash Code (X+Y) a Indicates Next System Action Recommended Service Action OFF No "Call for Heat" not applicable none Flash Fast Startup - Flame sense calibration not applicable none Heartbeat Normal operation not applicable none 2 5 minute Retry ...

  • A.O. Smith HW 610 - page 54

    54 T able 13. Lockout Models B, H, D and J Only - Green LED Status Codes Green LED Flash Code (X+Y) a Indicates Next System Action Recommended Service Action OFF No "Call for Heat" not applicable none Flash Fast Startup - Flame sense calibration not applicable none Heartbeat Normal operation not applicable none 3 Recycle - Flame failed du ...

  • A.O. Smith HW 610 - page 55

    55 A. O. Smith Corporation, the warrantor , extends the following LIMITED WARRANTY to the owner of this boiler . 1. If within TEN years after initial installation of the boiler, a heat exchanger , coil or gas burner shall prove upon examination by the warrantor to be defective in material or workmanship, the warrantor , at his option will exchange ...

  • A.O. Smith HW 610 - page 56

    500 T ennessee W altz Parkway , Ashland City , TN 37015 T echnical Support: 800-527-1953 • Parts: 800-433-2545 • Fax: 800-644-9306 www .hotwater.com ...

Fabricant A.O. Smith Catégorie Boiler

Les documents que nous recevons du fabricant de l'appareilA.O. Smith HW 610 peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques A.O. Smith
- manuels d’utilisations HW 610
- fiches produit A.O. Smith
- dépliants
- ou étiquettes-énergie A.O. Smith HW 610
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation A.O. Smith HW 610.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation A.O. Smith HW 610, manuels d’entretien, brefs manuels ou manuels de l’utilisateur A.O. Smith HW 610. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit A.O. Smith HW 610.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil A.O. Smith HW 610, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser A.O. Smith HW 610 par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs A.O. Smith HW 610.

Le manuel d’utilisation complet A.O. Smith, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel A.O. Smith HW 610 - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières A.O. Smith HW 610, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lA.O. Smith HW 610 qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil A.O. Smith HW 610 - qui devraient nous aider dans les premières étapes lors de l'utilisation A.O. Smith HW 610
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de A.O. Smith HW 610
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service A.O. Smith HW 610 dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de A.O. Smith HW 610?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec A.O. Smith HW 610, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec A.O. Smith HW 610 il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)