    Reference Manual 00809-0100-4690, Rev EA March 2007 Rosemount 2088 and 2090 www .rosemount.com Section 3 Inst allation Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-1 Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-1 General Considerations . . . . . . . . . . . ...

  • Emerson Process Management 2088 - page 2

    Reference Manual 00809-0100-4690, Rev EA March 2007 Rosemount 2088 and 2090 3-2 W arnings Explosions could result in death or serious injury: • Do not remove the transmitter cover in explosive atmospheres when the circuit is alive. • Before connecting a HART -based commu nicator in an explosive atmosphere, make sure the instruments in the loop ...

  • Emerson Process Management 2088 - page 3

    Reference Manual 00809-0100-4690, Rev EA March 2007 3-3 Rosemount 2088 and 2090 Figure 3-1. Installation Flowchart. Check for Leaks (Process Connections) Zero T rim T ransmitter for Mounting Effect s Check Jumper or Switches Wire T ransmitter Power T ransmitter DONE Mount T ransmitter Apply Pressure Refer to T roubleshooting Section Within Specific ...

  • Emerson Process Management 2088 - page 4

    Reference Manual 00809-0100-4690, Rev EA March 2007 Rosemount 2088 and 2090 3-4 GENERAL CONSIDERATIONS The accuracy of the pressure measurement depends on proper installation of the transmitter and impulse piping. The piping between the process and transmitter must accurately transmit pr essure to the transmitter . Mount the transmitter close to th ...

  • Emerson Process Management 2088 - page 5

    Reference Manual 00809-0100-4690, Rev EA March 2007 3-5 Rosemount 2088 and 2090 MECHANICAL CONSIDERATIONS Mounting Rosemount 2088 The Rosemount 2088 Smart T ransmitter weighs approximately 2.44 lb. (1,1 1 kg). The 2088 Analog T ransmitter weighs approximately 1.9 lb. (0,86 kg). In many cases, its comp act size and light weight makes it possible to ...

  • Emerson Process Management 2088 - page 6

    Reference Manual 00809-0100-4690, Rev EA March 2007 Rosemount 2088 and 2090 3-6 Impulse Piping Impulse piping configurations depend on specific measurement conditions. Use the following information and Figur e 3-3 as a guideline when installing impulse piping. Liquids: Make the line tap on the side of the pipe to prevent sediment deposits from plug ...

  • Emerson Process Management 2088 - page 7

    Reference Manual 00809-0100-4690, Rev EA March 2007 3-7 Rosemount 2088 and 2090 Access Requirement s When choosing a mounting location and pos ition, take into account the need for access to the transmitter . Make wiring terminations through the conduit openings at the top of the electronics housing. The field terminal side of the transmitter is cl ...

  • Emerson Process Management 2088 - page 8

    Reference Manual 00809-0100-4690, Rev EA March 2007 Rosemount 2088 and 2090 3-8 Nameplate 3.9 (100) 2X 1 / 4 –20 UNC–2BX 0.60 Deep Mounting Bracket Holes 4.7 (140) T erminal Connections T ransmitter Circuitry Side Optional Meter Cover 5.0 (125) W eld Spud 1.0 (25.4) V essel W all 4.3 (110) 1.05 (26.6) 1.32 (33,4) 5.75 (146) 3X 5 / 16 –18 UNC ...

  • Emerson Process Management 2088 - page 9

    Reference Manual 00809-0100-4690, Rev EA March 2007 3-9 Rosemount 2088 and 2090 Rosemount 2090P Installing the Rosemount 2090P transmitter involves att aching a weld spud to the tapped process vessel, att aching t he transmitter to the weld spud, and making electrical connections. If you intend to use an existing weld spud, proceed to the transmitt ...

  • Emerson Process Management 2088 - page 10

    Reference Manual 00809-0100-4690, Rev EA March 2007 Rosemount 2088 and 2090 3-10 3. Hand tighten the transmitter using the knurled retaining ring, then snug an additional 1 / 8 turn with adjustable pliers. IMPORT ANT Do not over-tighten the retaining ring. A sp anner wrench (P/N 02088-0193-0001) hole is located on the knurled portion of the retaini ...

  • Emerson Process Management 2088 - page 11

    Reference Manual 00809-0100-4690, Rev EA March 2007 3-1 1 Rosemount 2088 and 2090 Rosemount 2090F The Rosemount 2090F sanitary pressu re transmitter is designed to be installed directly to a sanit ary fitting. T he transmitter is available with either a 1.5- or 2-inch clamp connection. When installing the transmitter to the sanit ary fitting it is ...

  • Emerson Process Management 2088 - page 12

    Reference Manual 00809-0100-4690, Rev EA March 2007 Rosemount 2088 and 2090 3-12 Figure 3-9. T ransmitter Load Limitations Field Wiring All power to the transmitter is supplie d over the signal wiring. Signal wiring need not be shielded, but use twisted pairs for best results. Do not run unshielded signal wiring in conduit or open trays with power ...

  • Emerson Process Management 2088 - page 13

    Reference Manual 00809-0100-4690, Rev EA March 2007 3-13 Rosemount 2088 and 2090 Figure 3-10. Rosemount 2088 Smart Signal Wiring T erminals. FAILURE MODE AND SECURITY JUMPERS Failure Mode As part of normal operation, the Rosemount 2088/2090 Smart Pressure T ransmitter continuously monitors its own operation. This automatic diagnostic routine is a t ...

  • Emerson Process Management 2088 - page 14

    Reference Manual 00809-0100-4690, Rev EA March 2007 Rosemount 2088 and 2090 3-14 With a meter inst alled The failure mode alarm jumper is located on the LCD faceplate in the electronics module side of the transm itter housing and is labeled ALARM (See Figure 3-1 1). Do not remove the transmitter cover in explosive atmospheres when the circuit is al ...

  • Emerson Process Management 2088 - page 15

    Reference Manual 00809-0100-4690, Rev EA March 2007 3-15 Rosemount 2088 and 2090 NOTE If either the alarm or security jumper is dislodged or removed from its position the transmitter reverts to default alarm or security settings of: Alarm: Output high; Security: Off ZERO AND SP AN ADJUSTMENT S The smart Rosemount 2088 is equipped with local zero an ...

  • Emerson Process Management 2088 - page 16

    Reference Manual 00809-0100-4690, Rev EA March 2007 Rosemount 2088 and 2090 3-16 Disabling the Zero and Sp an Adjustment s After you rerange the transmitter usi ng the sp an and zero adjustments, you may wish to disable the adjustments to prevent further reranging. T o disable the span and zero adjustment s, activate the transmitter security jumper ...

Fabricant Emerson Process Management Catégorie Satellite Radio

Les documents que nous recevons du fabricant de l'appareilEmerson Process Management 2088 peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques Emerson Process Management
- manuels d’utilisations 2088
- fiches produit Emerson Process Management
- dépliants
- ou étiquettes-énergie Emerson Process Management 2088
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation Emerson Process Management 2088.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation Emerson Process Management 2088, manuels d’entretien, brefs manuels ou manuels de l’utilisateur Emerson Process Management 2088. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit Emerson Process Management 2088.

Manuel d’utilisation complet de l’appareil Emerson Process Management 2088, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser Emerson Process Management 2088 par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs Emerson Process Management 2088.

Le manuel d’utilisation complet Emerson Process Management, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel Emerson Process Management 2088 - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières Emerson Process Management 2088, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lEmerson Process Management 2088 qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil Emerson Process Management 2088 - qui devraient nous aider dans les premières étapes lors de l'utilisation Emerson Process Management 2088
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de Emerson Process Management 2088
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service Emerson Process Management 2088 dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de Emerson Process Management 2088?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec Emerson Process Management 2088, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec Emerson Process Management 2088 il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)