    ® NetworkAIR™ 1000 Portable Air Conditioner AP7003 AP7004 User’ s Manual ...

  • APC AP7004 - page 2

    Important Safety Information Wa r n i n g • Read these instructions carefully befo re using this air conditioner . • This air conditioner is designed f or indoor use only . The temp erature range f or the cooling mode is 6 1° F to 86° F . • T o reduce the risk of fire or electr ic shock, do not expose the unit to rain or m oisture. Do not o ...

  • APC AP7004 - page 3

    i Contents General Information . . . . . . . . . . . . . . . . . . . . . . . . 1 About NetworkAIR 1000 1 Inventory 1 Front View 2 Back View 2 Contro l Panel 3 LCD Indicators 4 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Warnings 5 Set up the unit 5 Check components 6 Power the unit 6 Operation . . . . . . . . . . . ...

  • APC AP7004 - page 4

    ii Contents continued Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . 17 Try this first 17 If problems persist 19 Warranty Information . . . . . . . . . . . . . . . . . . . . . 20 Limited warranty 20 Warranty limitations 20 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 ...

  • APC AP7004 - page 5

    1 General Information About NetworkAIR 1000 APC ’ s Netwo rkAIR 1000 is a portable, com pact, air- conditioner designed for spot-cooling, em ergency-cooling, and after-hours cooling of server closets, data centers, confer ence rooms, hom e offices, or room s housing heat-sensitive equipment. The NetworkAIR 1000 pro vides 7,200 BTU (7,500 BTU for ...

  • APC AP7004 - page 6

    2 General Information continued Fr ont View Back View C ontr o l P ane l Hor izont al Air Fl ow Guides V ertical S w ing Lou ver Handle Wat e r Tan k Caster P ower C or d & Plu g W as h a bl e Ai r Fil te r D ra i n V a l ve Exha ust V ent ...

  • APC AP7004 - page 7

    3 General Information continued Contr ol Panel Power T urns the unit on and off. Mode Sets the desire d operating mode: fan, cooling, o r dehumidifying. Fan Speed Sets desired fan speed: high, medium or low . Louver Directs the air distribution. T emperature Sets the desire d temperature (61°– 86°F). Timer Programs the timer for unattended shut ...

  • APC AP7004 - page 8

    4 General Information continued LCD Indicators  T emperature  Fan Mode  Cooling Mode  Dehumidify Mode  Louver On  Ti m e r O n / O ff  T imer Setting  Fan Speed  Set T emperature Note: T emp erature i s show n in Celsius on the AP7004. ...

  • APC AP7004 - page 9

    5 Installation Wa r n i n g s Use the uni t on a flat surface where the air outlets are unobstructed. Do not place the unit less that 20 inches (50 cm ) away from any wall or obstacle. Do not install this air condition er where there are fum es or flamm able gases, or in an extrem ely humid space such as a green house. Set up the unit 1. Unpack the ...

  • APC AP7004 - page 10

    6 Installation continued Check components 1. Check that the condensate tank on the side of the unit is in place and is properly seated. If the tank is not installed properly , the unit wil l not operate. 2. Open the air filter cover on the left sid e of the unit and check that the air filter is clean. Power the unit 1. Plug the unit in to a wall ou ...

  • APC AP7004 - page 11

    7 Operation Power T urn the unit on or off by pressing the Power button. Cooling • T o select the Cooling m ode, press the Mode button until the cooling m ode indicator appears in the LCD window . • Set the fan speed by p ressing the Fan Speed button. The fan speed indicator in the LCD window wil l display what speed has been selected - high, m ...

  • APC AP7004 - page 12

    8 Operation continued Ti me r Y our portable air con ditioner has a tim er feature that allow s the unit to shut off or turn on automat ically in a preset number of hours. 1. Set Timer On mode a. Make sure mode (cool, dehum idify or fan), tempera- ture, and fan opt ions are on t he desired setting. b. T urn the unit off. c. Press the Timer button a ...

  • APC AP7004 - page 13

    9 Installing the Exhaust Kit Installing into ceiling plenum For this installation you wil l need the following: • The ceiling adapter • The holder flange • The exhaust duct • The base flange Note: There should be about 12 to 15 inches of open space above the ceiling adapter opening so that exh aust air is not blocked 1. The exhaust duct is ...

  • APC AP7004 - page 14

    10 Installing the Exhaust Kit continued Installing into ceiling plenum, continued 5. For permanen t installation, cut five inches off the ceiling tile so that the tile will l ay flat in the grid. 6. For temporar y installations, slide the ceiling ti le tight against the ceiling adapter . 7. Screw the other en d of the exhau st duct into the base fl ...

  • APC AP7004 - page 15

    11 Drainage Methods of Draining The NetworkAIR 1000 has two m ethods of disposi ng of the condensation. The first is a condensate tank that can be manually em ptied. Th e second method is to attach a drain h ose to the unit so the water will run to a floor drain. Condensate Ta n k The condensation will drain in to the condensate tank when the unit ...

  • APC AP7004 - page 16

    12 Drainage continued Emptying the tank T o manuall y drain the tank: 1. T urn off the unit . 2. Using the handle, slowly rem ove the tank from the side of the unit. 3. Pour out any condensation accum ulated in the tank. 4. W i pe up any condensation that m ay have drained off the evaporator coil. 5. Replace the tank in the unit. 6. T urn the power ...

  • APC AP7004 - page 17

    13 Drainage continued The drainage tube 1. Slide out the drain valve from the left side of th e unit. 2. Attach the drainage tube to the drain valv e. 3. Route the tubing downward so that con densate flows prop- erly into a floor drain or cond ensate line below the unit. Note: Condensation will drip through the drain valve if it is open. Make sure ...

  • APC AP7004 - page 18

    14 Maintaining the Unit Clean the air filter APC recom mends cl eaning your air filter at least af ter every two weeks of use. Keeping your air filter clean wi ll maxim ize the perform ance and life of this product. 1. T urn off the unit and unplug it fro m its electrical ou tlet. 2. Open the air filter on the left side of th e unit. 3. Remove the ...

  • APC AP7004 - page 19

    15 Maintaining the Unit continued Clean the condensate tank r egularly 1. T urn off the unit and unplug it fro m its electrical ou tlet 2. Using the handle, slowl y remo ve the condensate tank from the side of the unit. 3. Pour out any condensation accum ulated in the tank. 4. Clean the inside of the tank with a solution of warm water and mild dete ...

  • APC AP7004 - page 20

    16 Maintaining the Unit continued Storing the Unit The following precauti ons must be taken when storing the unit for extended periods of tim e: 1. T urn off unit. 2. Clean the air filter and allow to air dr y before replacing in unit. 3. Empty the con densate tank. 4. Remove the stopper fr om the water drain pipe and drain until empty . Reinsert t ...

  • APC AP7004 - page 21

    17 T r oubleshooting T ry th is first Problem Cause Suggestion Unit does not work Unit is not plugged in. Securely plug receptacle into the wall. Main power is off. Check fuse or circuit breaker Condensate tank is full. Indicator light is on. Empty tank. Poor cooling perfo rmanc e. Air exhaust or intake blocked. Clear all obje cts away from air gri ...

  • APC AP7004 - page 22

    18 T r oubleshooting continued T ry th is first, continued Problem Cause Suggestion W ater is leaking from unit. Drain tube is clogged. Remove blockage. Condensate tank is improperly seated. Reposition t ank. Surface not level. Place unit on a level surface away from obstructions. Damaged condensate tank. Replace tank. Stopper on water drain pipe i ...

  • APC AP7004 - page 23

    19 T r oubleshooting continued If pr oblems persist For problem s not covered in the troubleshooting char t, or if the problem persi sts, follow this procedure: 1. Note the serial number and date of purchase of the NetworkAIR 1000. Contact Custom er Supp ort at a phone number or addr ess on the back cover of this manual. 2. Be prepared to provide a ...

  • APC AP7004 - page 24

    20 W arranty Information Limited warranty American Power Conversion (APC) war rants the NetworkAir 1000 to be free from d efects in m aterials and workmanship for a period of one year from the date of purchase. Its obligation under thi s warranty is lim ited to repairing or replacing, at its own sole opt ion, any such defec- tive products. Thi s wa ...

  • APC AP7004 - page 25

    21 Specifications Item Specification AP7003 AP7004 Electric al Power source 1 15 V ; 60 Hz 230 V ; 50 Hz Rated current 6.2 A 3.6 A Rated input Cooling 692 W Dehumidify 660 W Cooling 860 W Dehumidify 820 W Physica l Condensate T ank capacity 3.5 qt (3 .3 L) 3.5 qt (3.3 L) Physical di mensions 12.85 × 16.250 × 30.75 in (326 × 415 × 788 mm) 12.85 ...

  • APC AP7004 - page 26

    ...

  • APC AP7004 - page 27

    ...

  • APC AP7004 - page 28

    APC W orldwide Customer Support Customer support for this or any other APC product is available at no charge in an y of the following ways: • V isit the APC W eb site to find answers to frequently asked questions (F AQs), to access documents in the APC knowledge base, and to submit cus- tomer support requests. – http://www .apc.com (Corporate H ...

Fabricant APC Catégorie Air Conditioner

Les documents que nous recevons du fabricant de l'appareilAPC AP7004 peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques APC
- manuels d’utilisations AP7004
- fiches produit APC
- dépliants
- ou étiquettes-énergie APC AP7004
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation APC AP7004.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation APC AP7004, manuels d’entretien, brefs manuels ou manuels de l’utilisateur APC AP7004. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit APC AP7004.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil APC AP7004, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser APC AP7004 par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs APC AP7004.

Le manuel d’utilisation complet APC, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel APC AP7004 - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières APC AP7004, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lAPC AP7004 qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil APC AP7004 - qui devraient nous aider dans les premières étapes lors de l'utilisation APC AP7004
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de APC AP7004
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service APC AP7004 dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de APC AP7004?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec APC AP7004, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec APC AP7004 il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)