Manuel d’utilisation Bradford-White Corp BJVT

36 pages 1.19 mb
Télécharger

Aller à la page of 36

Summary
  • Bradford-White Corp BJVT - page 1

    H2343000- FOR YOUR SAFETY : This product must be installed and serviced by a professional service technician, qualified in hot water boiler installation and maintenance. Improper installation and/or operation could create carbon monoxide gas in flue gases which could cause serious injury , property damage, or death. Improper installation and/or ope ...

  • Bradford-White Corp BJVT - page 2

    B RADFORD W HITE C ORP. Page 2 T ABLE OF CONTENTS SECTION 1. General Information 1.1 Introduction ................................................... 3 1.2 Warranty ....................................................... 3 1.3 Codes and Standards ................................... 3 1.4 Technical Assistance .................................... 3 1 ...

  • Bradford-White Corp BJVT - page 3

    Brute Mini Hydronic Boiler Page 3 SECTION 1. General Information 1.1 Introduction This manual provides information necessary for the installation, operation, and maintenance of Model BJV copper tube hydronic boilers. All application and installation procedures should be reviewed completely before proceeding with the installation. Consult the factor ...

  • Bradford-White Corp BJVT - page 4

    B RADFORD W HITE C ORP. Page 4 temperature may be less than 120°F, such as in-floor radiant systems, snow melt systems or other systems where a “cold start” is expected frequently due to thermostat setbacks, etc. See Figure 11. b. Any system where the temperature rise across the heat exchanger is above 30°F (see Section 5 and Figure 7). 2. Co ...

  • Bradford-White Corp BJVT - page 5

    Brute Mini Hydronic Boiler Page 5 2.2 Field Assembly 1. Brute Mini boilers have built-in draft diverter for natural draft operation. 2. Find the vent damper box which is located in the boiler package. 3. Install the vent damper directly to the top of the draft diverter outlet with the damper operator facing to the front of the boiler, and with the ...

  • Bradford-White Corp BJVT - page 6

    B RADFORD W HITE C ORP. Page 6 Caution Do not force motor operation when operator is fastened to the damper by moving the damper blade, turning the shaft or by turning the position indicator. Attention Ne pas tourner le registre manuellement avec ou sans courant électrique ou le moteur sera endommagé. 2.3.1 Clearances The boiler must be placed to ...

  • Bradford-White Corp BJVT - page 7

    Brute Mini Hydronic Boiler Page 7 SECTION 3. V enting 3.1 Combustion Air Supply The boiler location must provide sufficient air supply for proper combustion, and ventilation of the surrounding area as outlined in the latest edition of ANSI standard Z223.1 or in Canada, CSA-B149.1, and any local codes that may be applicable. In general, these requir ...

  • Bradford-White Corp BJVT - page 8

    B RADFORD W HITE C ORP. Page 8 WARNING Vent pipe diameter must be as required by the National fuel Gas Code Z223.1 or the Canadian Installation Codes for Gas Appliances CSA-B149.1. Undersize pipe can result in inadequate venting and oversize pipe can result in vent condensation. In either case the result can be release of combustion products to the ...

  • Bradford-White Corp BJVT - page 9

    Brute Mini Hydronic Boiler Page 9 WARNING Operation of appliances with a blocked common vent may lead to serious injury or death. Safety devices must be implemented to prevent blocked common vent operation. If safe operation of all appliances connected to a common vent cannot be assured, including prevention of spillage of flue gasses into living s ...

  • Bradford-White Corp BJVT - page 10

    B RADFORD W HITE C ORP. Page 10 SECTION 4. Gas Connections 4.1 Gas Supply and Piping Review the following general instructions before continuing the installation. WARNING The Brute Mini BJVS and BJVT boilers are designed for use with either natural gas or LP gas. Check the rating plate to be sure that the boiler is designed to use the type of gas b ...

  • Bradford-White Corp BJVT - page 11

    Brute Mini Hydronic Boiler Page 11 NOTE : The boiler and all other gas appliances sharing the boiler gas supply line must be firing at maximum capacity to properly measure the inlet supply pressure. Low gas pressure could be an indication of an undersize gas meter and/or obstructed gas supply line. 8. The correct high fire burner manifold gas press ...

  • Bradford-White Corp BJVT - page 12

    B RADFORD W HITE C ORP. Page 12 A full sized, 1¼" bypass with balancing valves is strongly recommended for all systems, and required when: 1) the boiler is installed without primary- secondary piping in a multiple zone system; 2) when the return water temperature can be expected to be lower than 120°F (44°C); or 3) whenever the system pipin ...

  • Bradford-White Corp BJVT - page 13

    Brute Mini Hydronic Boiler Page 13 Figure 6. Typical Plumbing Installations. ...

  • Bradford-White Corp BJVT - page 14

    B RADFORD W HITE C ORP. Page 14 Figure 6A. Typical Plumbing Installations. System Loop Expansion T ank Pump Air Scoop Feed W ater Single Circuit System Multi-Zone Valve System Multi-Zone Pump System Figure 6B. Typical Plumbing Installations. BJV Boiler BJV Boiler BJV Boiler ...

  • Bradford-White Corp BJVT - page 15

    Brute Mini Hydronic Boiler Page 15 5.3 Flow Requirements All high recovery, low volume water boilers must have adequate flow for efficient operation. Pump selection is critical to this goal, and pumps should be selected to provide for system design water temperature rise. Table 6 details temperature rise and water flow (GPM) for the Brute Mini boil ...

  • Bradford-White Corp BJVT - page 16

    B RADFORD W HITE C ORP. Page 16 5.4 Chilled Water Systems If the boiler is installed in conjunction with refrigeration systems, it shall be installed so that the chilled medium is piped in parallel with the heating boiler with appropriate valves to prevent the chilled medium from entering the heating boiler. When boiler piping is connected to heati ...

  • Bradford-White Corp BJVT - page 17

    Brute Mini Hydronic Boiler Page 17 Figure 9a. Wiring Diagram, Spark Ignition System (BJVS 50 & 75). Switch Safety Roll-Out Blocked V ent Safety Switch Sp ace Heating Pump (Field Supplied) Receptacle Damper V ent Receptacle V enter Power Jumper R W R A Zone Pump Relay Zone Pump Relay Field Thermostat Supplied Limit High Optional Aquastat T ermin ...

  • Bradford-White Corp BJVT - page 18

    B RADFORD W HITE C ORP. Page 18 Figure 9c. Wiring Diagram, Standing Pilot System (BJVT). Figure 9d. Schematic, Standing Pilot System (BJVT). ...

  • Bradford-White Corp BJVT - page 19

    Brute Mini Hydronic Boiler Page 19 SP ARK MV MV/PV PV GND 24V (GR) 24V TH-W MV SP ARK 1 2 3 4 5 6 7 8 9 W W B B R R LO HI MV C PV HI Pilot Burner With Sp ark Electrode Sensor Remote Flame Sensor High Altitude (Optional) T wo-Stage Aquastat Tw o- St a g e Gas V alve HW VR8304 Switch Safety Roll-Out Blocked V ent Safety Switch Sp ace Heating Pump (Fi ...

  • Bradford-White Corp BJVT - page 20

    B RADFORD W HITE C ORP. Page 20 Figure 10. Multiple Zone Wiring. For primary/secondary pumping: Connect to "W" in lieu of "A." Boiler relay is used for boiler pump and connection to "W" will energize boiler pump when any zone is calling for heat. Wiring with T aco Zone V alves Wiring with Honeywell Zone V alves Wiring ...

  • Bradford-White Corp BJVT - page 21

    Brute Mini Hydronic Boiler Page 21 6. 3 Grounding WARNING The boiler must be electrically grounded in accordance with the requirements of the authority having jurisdiction or, in the absence of such requirements, with the latest edition of the National Electrical Code, ANSI/NFPA 70, in the U.S. and with latest edition of CSA C22.1 Canadian Electric ...

  • Bradford-White Corp BJVT - page 22

    B RADFORD W HITE C ORP. Page 22 On continuous pilot ignition models (BJVT), if the water temperature is below the limit setting, the ignition module opens the main gas valve, and the main burners ignite. Operation will continue on all ignition systems until either the wall setting thermostat is satisfied or the high-limit thermostat opens. The burn ...

  • Bradford-White Corp BJVT - page 23

    Brute Mini Hydronic Boiler Page 23 Caution Should overheating occur or the gas supply fail to shut off, do not turn off or disconnect the electrical supply to the pump. Instead, shut off the gas supply at a location external to the appliance. Attention En cas de surchauffe ou si l’admission de gaz ne peut être coupée, ne pas couper ni débranch ...

  • Bradford-White Corp BJVT - page 24

    B RADFORD W HITE C ORP. Page 24 14. Turn gas control knob counterclockwise to ON. 15. Replace control box cover. 16. Restore power to the boiler and adjust the thermostat high enough to call for heat to verify the boiler is operating properly. 17. BJVS 100-225 ONLY - Adjust two-stage operating control setting to maximum, verify high fire operation. ...

  • Bradford-White Corp BJVT - page 25

    Brute Mini Hydronic Boiler Page 25 DANGER Read and understand this entire procedure prior to proceeding. Improper adjustment of high altitude shutters may result in a fire, explosion, and/or high levels of toxic gases which may cause property damage, personal injury, or loss of life. DANGER Lisez la manière de procéder dans sa totalité et compre ...

  • Bradford-White Corp BJVT - page 26

    B RADFORD W HITE C ORP. Page 26 1. Lubricate the water circulating pump per the instructions on the pump. 2. If a strainer is employed in a pressure reducing valve or the piping, clean it every six months. 3. At start-up, and periodically thereafter, the burner flame should be observed. If the flame has the appearance of ‘sooting’ tips, check f ...

  • Bradford-White Corp BJVT - page 27

    Brute Mini Hydronic Boiler Page 27 Caution Two-stage Operating Control (BJV100-225 ONLY): Factory setting is 140°F (60°C). This setting is correct for most hydronic heating applications. Adjustments to this setting must be made by an authorized service technician. 2. Two-stage Temperature Control - BJVS 100- 225 are equipped with a two-stage temp ...

  • Bradford-White Corp BJVT - page 28

    B RADFORD W HITE C ORP. Page 28 Table 8. Troubleshooting Guide. # Symptom Cause Remedy 1. Pump not A. No power A. Check circuit breakers and power source. operating B. Pump defective B. Replace. C. Incorrectly wired C. Recheck wiring diagrams. 2. Pilot outage A. Inlet gas pressure too low A. Consult gas utility company. Inlet gas pressure to boiler ...

  • Bradford-White Corp BJVT - page 29

    Brute Mini Hydronic Boiler Page 29 T T T T T T T TT T T T Note: Before troubleshooting, familiarize yourself with the start-up and checkout procedure. Check line voltage power, low voltage transformer, hi- limit switch, thermostat (controller) and wiring. Pull ignition lead and check spark at module. Spark okay? • Check ignition cable ground wiri ...

  • Bradford-White Corp BJVT - page 30

    B RADFORD W HITE C ORP. Page 30 9.4 Electrical Troubleshooting 1. Remove the control box cover on the front of the boiler. 2. Verify that 115V is reaching the boiler by testing across the black wire on the pump relay and the white wire on the transformer. 3. Verify 24V transformer output by placing the meter leads on the yellow and red wires. If 24 ...

  • Bradford-White Corp BJVT - page 31

    Brute Mini Hydronic Boiler Page 31 Heat Distribution Units Transfers heat from the water supplied by the boiler to the area to be heated through the use of baseboard, convector, radiator, finned tube. Also known as "radiation." Isolation Valve Used to isolate the boiler from the circuit. It minimizes the amount of water drained from the s ...

  • Bradford-White Corp BJVT - page 32

    B RADFORD W HITE C ORP. Page 32 Description Model, Size BJVS-50 BJVT-50 BJVS-75 BJVT-75 BJVS-100 BJVT-100 BJVS-125 BJVT-125 BJVS-160 BJVT-160 BJVS-225 BJVT-225 Pilot Gas System Pilot Assy (Nat.) W0030600 W0040900 W0030600 W0040900 W0030600 W0040900 W0030600 W0040900 W0030600 W0040900 W0030600 W0040900 Pilot Assy (LP) W0039600 W0040901 W0039600 W004 ...

  • Bradford-White Corp BJVT - page 33

    Brute Mini Hydronic Boiler Page 33 Description Model, Size BJVS-50 BJVT-50 BJVS-75 BJVT-75 BJVS-100 BJVT-100 BJVS-125 BJVT-125 BJVS-160 BJVT-160 BJVS-225 BJVT-225 Water System Heat Exchanger 11046001 11046001 11046002 11046002 11046003 11046003 11046004 11046004 11046005 11046005 11046006 11046006 Temperature/Pressure Gauge A0000100 A0000100 A00001 ...

  • Bradford-White Corp BJVT - page 34

    B RADFORD W HITE C ORP. Page 34 Figure 15. Parts Identification. 11.3 Exploded View V ent Damper Draft Diverter To p Rear Panel Burner with Pilot Bracket Pilot Assembly Gas Manifold Base Assembly Refractory , Rear Refractory , Front Gap Closure HX Access Panel Heat Exchanger Flue Collector     1-1/4” Hold 1-1/8” Hold 1-1/4” Hold 1 ...

  • Bradford-White Corp BJVT - page 35

    Brute Mini Hydronic Boiler Page 35 ...

  • Bradford-White Corp BJVT - page 36

    Dimensions and specifications subject to change without notice in accordance with our policy of continuous product improvement. H2343000- Ambler , P A 19002 T ech. Service (800) 334-3393 Service Parts (800) 538-2020 www .BradfordWhite.com W arranty Service (800) 531-21 1 1 Litho in U.S.A. © Bradford White 1 101 Document 1242 ...

Fabricant Bradford-White Corp Catégorie Boiler

Les documents que nous recevons du fabricant de l'appareilBradford-White Corp BJVT peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques Bradford-White Corp
- manuels d’utilisations BJVT
- fiches produit Bradford-White Corp
- dépliants
- ou étiquettes-énergie Bradford-White Corp BJVT
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation Bradford-White Corp BJVT.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation Bradford-White Corp BJVT, manuels d’entretien, brefs manuels ou manuels de l’utilisateur Bradford-White Corp BJVT. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit Bradford-White Corp BJVT.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil Bradford-White Corp BJVT, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser Bradford-White Corp BJVT par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs Bradford-White Corp BJVT.

Le manuel d’utilisation complet Bradford-White Corp, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel Bradford-White Corp BJVT - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières Bradford-White Corp BJVT, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lBradford-White Corp BJVT qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil Bradford-White Corp BJVT - qui devraient nous aider dans les premières étapes lors de l'utilisation Bradford-White Corp BJVT
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de Bradford-White Corp BJVT
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service Bradford-White Corp BJVT dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de Bradford-White Corp BJVT?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec Bradford-White Corp BJVT, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec Bradford-White Corp BJVT il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)