  • Greenheck Fan HRE-20 - page 1

    **W ARNING** DISCONNECT AND SECURE TO THE "OFF" POSITION ALL ELECTRICAL POWER TO THE UNITS PRIOR TO INSPECTION OR SERVICING. F AILURE TO COMPL Y WITH THIS SAFETY PRECAUTION COULD RESUL T IN SERIOUS INJUR Y OR DEA TH. **IMPORT ANT** ALL F ACTORY PROVIDED LIFTING LUGS MUST BE USED WHEN LIFTING THE UNITS. F AILURE TO COMPL Y WITH THIS SAFETY ...

  • Greenheck Fan HRE-20 - page 2

    GENERAL Greenheck Energy Recovery units with T empering are thor oughly inspected and test run at the factory . However , damage may occur during handling and shipping. Consequently , it is important to inspect the unit for visible and concealed damage before beginning installation. Report any damage to the shipper immediately . In addition, assure ...

  • Greenheck Fan HRE-20 - page 3

    INST ALLA TION The system design and installation should follow accepted industry practice, such as described in the ASHRAE Handbook. Adequate space should be left around the unit for piping coils and drains, filter replacement, and maintenance. Sufficient space should be pr ovided on the side of the unit for routine service and component re moval ...

  • Greenheck Fan HRE-20 - page 4

    4 R o t a t i o n Length of Straight Duct GOOD R o t a t i o n POOR FIGURE 4 DUCT WORK CONNECTIONS Examples of good and poor fan-to-duct connections are shown below (See FIGURE 4). Airflow out of the fan should be directed straight or curve the same dir ection as the fan wheel rotates. Poor duct installation will r esult in low airflow and other sy ...

  • Greenheck Fan HRE-20 - page 5

    5 Main Disconnect On Off Exhaust Hood Control Center Intake Hood INST ALLA TION (continued) ELECTRICAL CONNECTIONS The electrical supply must be compatible with that shown on the nameplate: voltage, phase, and amperage capacity . The electrical supply line must be properly fused and conform to local and national electrical codes. All internal elect ...

  • Greenheck Fan HRE-20 - page 6

    Wheel Cassette 2 in. filters 2 in. filters Direct Evap Section Exhaust Air Intake Electrical Box Access Panel Access Panel Access Panel Access Panel Access Panel Cassette Slides Out 52 in. Clearance with IG Heater 0 in. Clearance without IG Heater Exhaust Hood Outdoor Air Hood IG Heater *48 in. **64 in. 36 in. 36 in. TOP VIEW Indirect Evap Section ...

  • Greenheck Fan HRE-20 - page 7

    1. After the energy recovery unit is set in place, run the overflow and drain lines to the exterior fittings on the evaporative cooler (drain & overflow connections at unit are 3 ⁄ 4 -inch female pipe thread). The supply line can be attached at the downstream side of the evaporative cooler . A manual shut off valve should be mounted in the su ...

  • Greenheck Fan HRE-20 - page 8

    Auto Drain and Fill with Freeze Protection This system will automatically drain the sump tank and fill it with fresh water at the field adjustable intervals, typically once every 24 hours. This flushes mineral build-up and debris from the tank to pr omote low maintenance and increase media pad life. In addition, the system will pr otect the evapora ...

  • Greenheck Fan HRE-20 - page 9

    Symptom Solution Leaving Air Entering Air 45 ° 15 ° Insufficient water volume or recir culation pump not operating Irregular water distribution on cooling media Scale and mineral deposit formation on face of media Excessive water discharge into drain W ater Carry-Over Poor performance after cooling pad r eplacement Inadequate cooling A. Check wat ...

  • Greenheck Fan HRE-20 - page 10

    10 Regularly scheduled maintenance is the key to peak performance, minimized cost, and extended life of the evaporative cooler . The following is a checklist of items that need to be looked at on a regular basis. 1. The media should be checked for mineral and foreign material deposits that have built up. If these items are left on the media, the li ...

  • Greenheck Fan HRE-20 - page 11

    11 1. Piping should be in accordance with accepted industry standards. Pipework should be supported independently of the coils. W ater connections are male NPT iron pipe. When installing couplings, do not apply undue stress to the connection extending through the unit. Use a backup pipe wrench to avoid br eaking the weld between coil connection and ...

  • Greenheck Fan HRE-20 - page 12

    12 ELECTRIC HEA TER APPLICA TION/OPERA TION Factory installed electric heaters can be provided for pr eheat and/or post-heat (see FIGURE 11). An electric preheater warms the outdoor air prior to the energy r ecovery wheel to prevent fr osting on the wheel. An electric post-heater warms the air leaving the energy recovery wheel to a user specified d ...

  • Greenheck Fan HRE-20 - page 13

    FROST CONTROL APPLICA TION/OPERA TION DIRTY FIL TER SWITCH SETUP When outdoor air temperatures ar e extremely cold, moistur e condensation and frosting on the energy recovery wheel is possible. Frost contr ol is an optional feature that will pr event wheel frosting. T wo options are available: 1) Timed Exhaust frost contr ol and 2) Preheat fr ost c ...

  • Greenheck Fan HRE-20 - page 14

    The energy recovery wheel may be de-energized for the purpose of pr oviding economizer (free cooling) operation. This can be achieved with a signal from a T emperatur e or Enthalpy sensor mounted in the supply air inlet compartment (see FIGURE 13). This Primary sensor will de-energize the energy wheel when the outdoor air temperature (factory defau ...

  • Greenheck Fan HRE-20 - page 15

    15 GENERAL Check all fasteners and set screws for tightness. This is especially important for bearings and fan wheels. Also, if dampers are not motorized, check that they open and close without binding. F AN WHEEL ROT A TION Hand rotate the blower to ensur e that the wheel is not rubbing against the scroll. If the blower is r otating in the wrong d ...

  • Greenheck Fan HRE-20 - page 16

    16 ENERGY RECOVERY WHEEL CAUTION: See **W ARNING** on page 1 and 15 For the HRE-20 and HRE-45, open the access door marked "Energy Wheel Cassette Access". UNPLUG the wheel drive motor and remove the metal spacer . Then pull the cassette out halfway as seen in FIGURE 17. Note: For the HRE-55 and HRE-90, the energy recovery wheel does not s ...

  • Greenheck Fan HRE-20 - page 17

    17 ROUTINE MAINTENANCE CAUTION: See **W ARNING** on Page 1 and 15 Once the unit has been put into operation, a periodic maintenance program should be set up to pr eserve the r eliability and performance. Items to be included in this pr ogram are: • BEL TS • MOTORS • WHEEL AND F ASTENERS • VIBRA TION • FIL TER MAINTENANCE • COIL MAINTENA ...

  • Greenheck Fan HRE-20 - page 18

    18 EXTERNAL FIL TER MAINTENANCE Aluminum mesh 2 in. filters are located in the supply weatherhood (if the weatherhood option was purchased). Filters should be checked and cleaned on a regular basis for best ef ficiency . The frequency of cleaning depends upon the cleanliness of the incoming air . To r emove these filters, remove bottom bolt in the ...

  • Greenheck Fan HRE-20 - page 19

    19 WA TER COIL MAINTENANCE CAUTION: See **W ARNING** on Page 1 and 15 FIL TERS Filters upstream of the coil should be checked r egularly . If the filters ar e dirty , they should be cleaned or r eplaced. It is important that the coils stay clean to maintain desir ed airflow . See page 18 for more information on filter maintenance. COIL MAINTENANCE ...

  • Greenheck Fan HRE-20 - page 20

    FIGURE 20 For the HRE-20 and HRE-45, open the access door marked "Energy Wheel Cassette Access" (FIGURE 20). UNPLUG the wheel drive motor and remove the metal spacer . Then pull the cassette out halfway (FIGURE 21). The energy recovery wheel cassettes for model HRE-55 and HRE-90 do not slide out due to their size and weight. Service to th ...

  • Greenheck Fan HRE-20 - page 21

    CLEANING ENERGY RECOVERY WHEEL SEGMENTS If the wheel appears excessively dirty , it should be cleaned to ensure maximum operating efficiency . Only excessive buildup of foreign material needs to be r emoved. DISCOLORA TION AND ST AINING OF ENERGY RECOVERY WHEEL DOES NOT AFFECT ITS PERFORMANCE. Thoroughly spray wheel matrix with household cleaner su ...

  • Greenheck Fan HRE-20 - page 22

    PA R TS LIST 1 2 3 4 8 5 6 7 7 9 Model HRE (shown with indirect evaporative cooler , optional direct evaporative cooler , and indirect gas heater) 10 22 1. Supply blower - Forward curved fan - Adjustable motor mount for belt tensioning - Adjustable sheaves for speed control 2. Vibrations isolators (quantity 4 per blower) - Neoprene 3. Energy recove ...

  • Greenheck Fan HRE-20 - page 23

    * Always provide the unit model and serial number when requesting parts or service information. * Always check motor amps and compare to nameplate rating. 23 Control power (24 V ac) wiring run is too long (resistance should not exceed 0.75 ohms). Shorten wiring run to mechanical room or install a r elay which will turn unit on/off (C/F for relay in ...

  • Greenheck Fan HRE-20 - page 24

    IOM HRE FS Rev . 2, July 2002 W arranty Greenheck warrants this equipment to be fr ee from defects in material and workmanship for a period of one year from the purchase date. The energy r ecovery wheel is warranted to be free from defects in material and workmanship for a period of five years from the pur chase date. Any units or parts which prove ...

Fabricant Greenheck Fan Catégorie Humidifier

Les documents que nous recevons du fabricant de l'appareilGreenheck Fan HRE-20 peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques Greenheck Fan
- manuels d’utilisations HRE-20
- fiches produit Greenheck Fan
- dépliants
- ou étiquettes-énergie Greenheck Fan HRE-20
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation Greenheck Fan HRE-20.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation Greenheck Fan HRE-20, manuels d’entretien, brefs manuels ou manuels de l’utilisateur Greenheck Fan HRE-20. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit Greenheck Fan HRE-20.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil Greenheck Fan HRE-20, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser Greenheck Fan HRE-20 par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs Greenheck Fan HRE-20.

Le manuel d’utilisation complet Greenheck Fan, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel Greenheck Fan HRE-20 - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières Greenheck Fan HRE-20, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lGreenheck Fan HRE-20 qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil Greenheck Fan HRE-20 - qui devraient nous aider dans les premières étapes lors de l'utilisation Greenheck Fan HRE-20
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de Greenheck Fan HRE-20
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service Greenheck Fan HRE-20 dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de Greenheck Fan HRE-20?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec Greenheck Fan HRE-20, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec Greenheck Fan HRE-20 il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)