    NOTE: Read the entire instruction manual before performing any service or maintenance. Index Page SAFETY CONSIDERATIONS ..................................................1-2 ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS........2 GENERAL......................................................................................2 CARE AND MAINTENANCE.......... ...

  • Bryant 4-WAY MULTIPOISE FIXED-CAPACITY CONDENSING GAS FURNACE 345MAV - page 2

    WARNING: Never store anything on, near, or in contact with the furnace, such as: 1. Spray or aerosol cans, rags, brooms, dust mops, vacuum cleaners, or other cleaning tools. 2. Soap powders, bleaches, waxes or other cleaning compounds, plastic or plastic containers, gasoline, kero- sene, cigarette lighter fluid, dry cleaning fluids, or other volati ...

  • Bryant 4-WAY MULTIPOISE FIXED-CAPACITY CONDENSING GAS FURNACE 345MAV - page 3

    7. Place filter in furnace. 8. Replace blower access panel and main furnace door. 9. Turn on electrical supply to furnace. NOTE: If the filter has cross-mesh binding, the binding must face the blower. If the filter has an air direction arrow, the arrow must point toward the blower. II. BLOWER MOTOR AND WHEEL MAINTENANCE To ensure long life, economy ...

  • Bryant 4-WAY MULTIPOISE FIXED-CAPACITY CONDENSING GAS FURNACE 345MAV - page 4

    CAUTION: Heating speed selection MUST be adjusted to provide proper temperature rise as specified on the rating plate. Failure to adjust the heating speed may shorten heat exchanger life. 14. Turn on electrical supply. Manually close blower access panel door switch. Use a piece of tape to hold switch closed. Check for proper rotation and speed chan ...

  • Bryant 4-WAY MULTIPOISE FIXED-CAPACITY CONDENSING GAS FURNACE 345MAV - page 5

    1. Turn off gas and electrical supplies to furnace. 2. Remove main furnace door. 3. Disconnect wires or connectors to rollout switch, gas valve, ignitor, and flame sensor. CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. 4. Disconnect combustion-air intake pipe from i ...

  • Bryant 4-WAY MULTIPOISE FIXED-CAPACITY CONDENSING GAS FURNACE 345MAV - page 6

    8. Flush inside of collector box with water until discharge from condensate trap is clean and runs freely. NOTE: Ensure the drain tube disconnected from the inducer housing is higher than the collector box opening or water will flow out tube. 9. Inspect inside area of collector box for any pieces of foreign materials and remove if present. CAUTION: ...

  • Bryant 4-WAY MULTIPOISE FIXED-CAPACITY CONDENSING GAS FURNACE 345MAV - page 7

    hydrocarbons or inadequate seal may occur) to inducer housing. (See Fig. 10.) Apply a small bead of G.E. RTV 162, G.E. RTV 6702, or Dow-Corning RTV 738 sealant to groove in collector box. 11. Refer to furnace wiring diagram and connect wires to inducer motor and pressure switch or connectors. 12. Reconnect pressure tubes to pressure switch. See dia ...

  • Bryant 4-WAY MULTIPOISE FIXED-CAPACITY CONDENSING GAS FURNACE 345MAV - page 8

    Fig. 11—Field Wiring A98209 115-V FIELD-SUPPLIED DISCONNECT AUXILIARY J-BOX CONTROL BOX 24-V TERMINAL BLOCK THREE-WIRE HEATING- ONLY FIVE WIRE NOTE 1 NOTE 2 FIELD-SUPPLIED DISCONNECT CONDENSING UNIT TWO WIRE FURNACE R G C WC R GY GND GND FIELD 24-V WIRING FIELD 115-, 208/230-, 460-V WIRING FACTORY 24-V WIRING FACTORY 115-V WIRING 208/230- OR 460- ...

  • Bryant 4-WAY MULTIPOISE FIXED-CAPACITY CONDENSING GAS FURNACE 345MAV - page 9

    The control center stores 1 fault code (the last fault to occur) for a period of 48 hrs or until the 115- or 24-v power is interrupted. NOTE: Removing blower access panel will open blower access panel door switch and terminate 115-v power to control center, and fault code will be erased. Look into blower access panel sight glass for current LED sta ...

  • Bryant 4-WAY MULTIPOISE FIXED-CAPACITY CONDENSING GAS FURNACE 345MAV - page 10

    2. Check for discolored heat tape insulation. If any damage or discolored insulation is evident, replace heat tape. 3. Check that heat tape power supply circuit is on. X. WINTERIZING CAUTION: Freezing condensate left in the furnace will damage the equipment. If the furnace will be off for an extended period of time in a structure where the temperat ...

  • Bryant 4-WAY MULTIPOISE FIXED-CAPACITY CONDENSING GAS FURNACE 345MAV - page 11

    PCB BLOWER OFF DELAY SELECTION CHART 90 SEC 135 SE C 180 SE C 225 SE C GVR HI / L O RE LA Y SEC-1 SEC-2 WHT PL1 32 1 6 5 4 9 87 LED TEST/TWIN BLOWER OFF DEL AY G R Y W C HUM H S IR ID R B L W R BLOWER SPEED SELECT FU1 COOL HEAT L2 PL3 PL2 VAC 120 L1 PR1 1 2 1 2 3 PR2 24 V A C -3A FUSE SPARE-2 SPARE-1 EAC-1 EAC-2 C 1.5 AMP 12 PL5 WHT BRN GR N BLK ID ...

  • Bryant 4-WAY MULTIPOISE FIXED-CAPACITY CONDENSING GAS FURNACE 345MAV - page 12

    → Fig. 16—Service Label A99107 SER VICE COMP ON ENT TE ST To in iti a te th e co m po n ent test se que nc e, sh u t OF F th e r oom the rm o st at o r disconnect t he "R" t hermostat lead. Brie fly short the TEST ter minal to t he "Com 24V " ter mi nal . S tat us L ED wi ll fl ash code an d th en t urn O N t he in du cer m ...

  • Bryant 4-WAY MULTIPOISE FIXED-CAPACITY CONDENSING GAS FURNACE 345MAV - page 13

    Is circuit breaker closed? Close door switch and go to start. Is red LED status light on? Is door switch closed? Is red LED status light blinking rapidly without a pause? Is there 1 15v going to switch? Replace door switch. Replace control center . Replace transformer . Is red LED status light blinking ON/OFF slowly with a combination of short and ...

  • Bryant 4-WAY MULTIPOISE FIXED-CAPACITY CONDENSING GAS FURNACE 345MAV - page 14

    11 NO PREVIOUS F A UL T - Faults are erased after 48 hrs or whenever power (1 15v or 24v) is interrupted. Run system through a heating or cooling cycle to check system. 12 BLO WER ON AFTER PO WER UP (115V OR 24V) - Normal operation. Blower will run for 90 sec when furnace power is interrupted during a call for heat, R-W closed. 13 LIMIT OR FLAME RO ...

  • Bryant 4-WAY MULTIPOISE FIXED-CAPACITY CONDENSING GAS FURNACE 345MAV - page 15

    —15— ...

  • Bryant 4-WAY MULTIPOISE FIXED-CAPACITY CONDENSING GAS FURNACE 345MAV - page 16

    A94328 SERVICE TRAINING Packaged Service Training programs are an excellent way to increase your knowledge of the equipment discussed in this manual, including:  • Unit Familiarization • Maintenance  • Installation Overview • Operating Sequence A large selection of product, theory, and skills programs is availa ...

Fabricant Bryant Catégorie Furnace

Les documents que nous recevons du fabricant de l'appareilBryant 4-WAY MULTIPOISE FIXED-CAPACITY CONDENSING GAS FURNACE 345MAV peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques Bryant
- manuels d’utilisations 4-WAY MULTIPOISE FIXED-CAPACITY CONDENSING GAS FURNACE 345MAV
- fiches produit Bryant
- dépliants
- ou étiquettes-énergie Bryant 4-WAY MULTIPOISE FIXED-CAPACITY CONDENSING GAS FURNACE 345MAV
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation Bryant 4-WAY MULTIPOISE FIXED-CAPACITY CONDENSING GAS FURNACE 345MAV.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation Bryant 4-WAY MULTIPOISE FIXED-CAPACITY CONDENSING GAS FURNACE 345MAV, manuels d’entretien, brefs manuels ou manuels de l’utilisateur Bryant 4-WAY MULTIPOISE FIXED-CAPACITY CONDENSING GAS FURNACE 345MAV. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit Bryant 4-WAY MULTIPOISE FIXED-CAPACITY CONDENSING GAS FURNACE 345MAV.

Manuel d’utilisation complet de l’appareil Bryant 4-WAY MULTIPOISE FIXED-CAPACITY CONDENSING GAS FURNACE 345MAV, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser Bryant 4-WAY MULTIPOISE FIXED-CAPACITY CONDENSING GAS FURNACE 345MAV par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs Bryant 4-WAY MULTIPOISE FIXED-CAPACITY CONDENSING GAS FURNACE 345MAV.

Le manuel d’utilisation complet Bryant, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel Bryant 4-WAY MULTIPOISE FIXED-CAPACITY CONDENSING GAS FURNACE 345MAV - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières Bryant 4-WAY MULTIPOISE FIXED-CAPACITY CONDENSING GAS FURNACE 345MAV, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lBryant 4-WAY MULTIPOISE FIXED-CAPACITY CONDENSING GAS FURNACE 345MAV qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil Bryant 4-WAY MULTIPOISE FIXED-CAPACITY CONDENSING GAS FURNACE 345MAV - qui devraient nous aider dans les premières étapes lors de l'utilisation Bryant 4-WAY MULTIPOISE FIXED-CAPACITY CONDENSING GAS FURNACE 345MAV
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de Bryant 4-WAY MULTIPOISE FIXED-CAPACITY CONDENSING GAS FURNACE 345MAV
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service Bryant 4-WAY MULTIPOISE FIXED-CAPACITY CONDENSING GAS FURNACE 345MAV dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de Bryant 4-WAY MULTIPOISE FIXED-CAPACITY CONDENSING GAS FURNACE 345MAV?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec Bryant 4-WAY MULTIPOISE FIXED-CAPACITY CONDENSING GAS FURNACE 345MAV, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec Bryant 4-WAY MULTIPOISE FIXED-CAPACITY CONDENSING GAS FURNACE 345MAV il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)