    S I T E M O N I T O R I N G RCM8CE & RCM8DO Remote Contact Module I NSTALLATION & U SER M ANUAL ...

  • Liebert RCM8DO - page 2

    ...

  • Liebert RCM8DO - page 3

    ...

  • Liebert RCM8DO - page 4

    TA BLE OF CONTENTS NOT E ........................................................................................................................... ............... 5 Section 1: INTRODUCT ION...................................................................................................... 1 Specifica tions ...................................... ...

  • Liebert RCM8DO - page 5

    NOTE This equipm ent has been tested and found to comply with the limits f or a Class A digital device, pursuant to par t 15 of the FCC r ules. These limits are designed t o provide reasonable protect ion against har mful interf erence when the equipment is operated in a commercial environment. This equipment generates, uses, and can r adiate radio ...

  • Liebert RCM8DO - page 6

    ...

  • Liebert RCM8DO - page 7

    Section 1: INTRODUCTION The Liebert RCM8CE and RCM8D O Remote Contact Monitors annunciate alarms by monitoring eight contact- closure points, each point wired directly to the RC M8. Contact Liebert Environmental Service & Support at 800-543-2778 regarding installation, operation, or warranty issues. When the RCM8 receiv es an alar m sig nal, a ...

  • Liebert RCM8DO - page 8

    2 • User Manual (7/99) Environmental Condi tions: Operating Temp: 5 ° C to 40 ° C Operating Relativ e Humidity: 0%- 95% (non-condensing) Operating A ltitude: up to 2,000 meters Pollution Degree: 2 Enclosure Type: NEMA 1 (for indoor use only) Enclosure Protection: IP 30 (pro tection against solid foreig n objects 2.5mm or greater, no protection ...

  • Liebert RCM8DO - page 9

    Section 1: INTRODUCTION Silence/Reset S w itch The Silence/Reset switch turns OFF the audible alarm . If D IP Switch SW1- 8 is ON, the comm on alarm relay output will reset with the Silence/Reset sw itch. ON/OFF Switch The RCM8 has a power ON/OFF switch located inside the enclosure. Refer to Figure 1 belo w. When wiring the dry contact connections, ...

  • Liebert RCM8DO - page 10

    4 • User Manual (7/99) Communications Ports The RCM8 has five physical connection ports: • EIA-232 (PC/Termin al) Port (DCE)— Accom modates a personal computer or VDT for setup and m essage display Refer to Chapter 2 of this manual and the section immediately following for information on installation and configuration using these communicatio ...

  • Liebert RCM8DO - page 11

    Section 2: Installation This section describes the installation procedure for monitoring system s using the RCM8. I nstallation includes: • Unpacking and Inspection • Mounting the RC M8 at the designated site • Making RCM8 phy sical connec tions based on application needs • Configuring the modem Unpacking and Inspection Inspect the pack age ...

  • Liebert RCM8DO - page 12

    6 • User Manual (7/99) • RCM8 with local, short-haul m odems • RCM8 with dial-up m odems to remote locations and pag ers • RCM8 m onitoring m ultiple remote locations from a central location Diagram s in Appendix B at the end of this manual describe possible RCM8 configurations. Dwg No. 154559, Sheet 1 of 3 8/21/97 Figure 2. Exterior a nd M ...

  • Liebert RCM8DO - page 13

    Section 2: Installation Settings and Connections To connect the RCM8: 1. Set the SW1 DIP Switches as described in the tables below: Refer to Figure 3 when making physical connections to the RCM8. Refer also to A ppendix B to define the application you wish to install. SW1 Switches 1 and 2—Address Switch 1 2 RCM8 (Input #) OFF ON OFF ON 1 (1-8 ) X ...

  • Liebert RCM8DO - page 14

    8 • User Manual (7/99) Figure 3a. Phy sical Connections and DIP Switches (RCM8CE) ...

  • Liebert RCM8DO - page 15

    Section 2: Installation Figure 3b. Phy sical Connections and DIP Switches (RCM8DO) Liebert RCM8 • 9 ...

  • Liebert RCM8DO - page 16

    10 • User Manual (7/99) • Terminal Baud Rate (7)—1200 or 2400 baud selectable. 7 data bits, even parity, 1 stop bit are fixed. • Common Alarm R elay (Silence/Reset) (8)— The com mon alarm relay energize s with any input alarm or received alarm. I f Silence Reset is ON, the relay de-energiz es when the audible alarm is silenced. I f OFF, t ...

  • Liebert RCM8DO - page 17

    Section 2: Installation Proprietary EIA-485 The EIA- 485 port is a proprietary connection that allows you to network multiple R CM8 units in a "daisy- chain" configuration. Multiple unit config urations must include a "master" unit to w hich three or four "slave" units can be connected; repeaters may also be daisy- cha ...

  • Liebert RCM8DO - page 18

    12 • User Manual (7/99) Modem Settings Data compression needs to be disabled on external m odems used with RCM8. On U.S. Robotics Sportster® modem s, the modem comm and to disable data compression is AT&K0. Error correction may or may not n eed to be disabled, depending on your application and prem ise equipment. The m odem comm and AT&M ...

  • Liebert RCM8DO - page 19

    Section 2: Installation 4. Click on the Configure button. Select the corresponding baud rate as set on RCM8 DIP Switch 1- 7; select 7 data bits; Even parity ; 1 stop bit; No flow control. Click on OK to confirm entry and return to previous dialog box. Liebert RCM8 • 13 5. Click on the Settings tab, and the ASCII Setup button. Ensure the Send line ...

  • Liebert RCM8DO - page 20

    ...

  • Liebert RCM8DO - page 21

    Section 3: RCM8 Menus The RCM8 Main Menu has 12 options that let you set configuration param eters. Accessing the Setup Menus After you hav e installed your RCM8 system you must set the software parameters using the RCM8 Main Menu and Sub- menus. The diag ram on the following pag e describes the RCM8 menu sy stem. You can access the Main Menu from ...

  • Liebert RCM8DO - page 22

    Figure 4. Menu Structure 16 • User Manual (7/99) ...

  • Liebert RCM8DO - page 23

    Chapter 3: Main Menu and SubMenus To access the RCM8 Main Menu V IA MODEM: 1. Make sure RCM8 and attached m odem are turned on and properly config ured. 2. On the remote PC, set up term inal emulation session for dial-out access – Connect Using an attached modem , rather than direct connect to a com port. 3. Once a connection has been established ...

  • Liebert RCM8DO - page 24

    Setup Input Options Menu The Setup Input Options item lets you configure RCM8 information g overning alarm delay s , contact status , dial codes, alarm m essages, site and pager I Ds. To configure i nput options: 1. From the Main Menu, press 2 to display the RCM8 Setup menu: RCM8 SETUP MENU 1. Set Delays 2. Set NO or NC or BAT 3. Set Dial Code A 4. ...

  • Liebert RCM8DO - page 25

    Chapter 3: Main Menu and SubMenus Set Dial Code A (3) Select an alarm option for tr ansmission throug h the modem port. • 0=Disabled, do not transmit v ia modem • R=Transmit alarm to another RCM8 • 1=Tran sm it al arm to remote device via PHONE NUMBER 1 • 2=Tran sm it al arm to remote device via PHONE NUMBER 2 Remote dev ices connected to P ...

  • Liebert RCM8DO - page 26

    Set Alarm Messages (6) Enter a custom alarm message to display each time its associated input alarm is tr iggered. You can enter up to 25 characters. For example, you might wish to enter the alarm text for input 01 as "Call M aint. Jim at x9999". Each time an alarm occurs on contact point 01, the RCM 8 displays the message to call Jim. Pr ...

  • Liebert RCM8DO - page 27

    Chapter 3: Main Menu and SubMenus Liebert RCM8 • 21 To view the alarm history: 1. From the Main Menu, press 3 to display the alarm history. Alarms Last Cleared at 08-15-97 13:41:37 07-05-99 13:05:21 WATER UNDER FLOOR 07-04-99 05:45:32 HIGH HUMIDITY 07-03-99 23:57:16 HIGH HUMIDITY End - Press Space Bar for Menu This is a view- only screen indicati ...

  • Liebert RCM8DO - page 28

    Set Modem Options The Set Modem Options item from the Main Menu lets y ou configure the telephone num bers and dialing param eters for modem connected to the unit. You can also perform a test on the comm unications port where the modem and phone are connected to verify proper operation. Modem options are not available for slave or repeater units. T ...

  • Liebert RCM8DO - page 29

    Chapter 3: Main Menu and SubMenus Liebert RCM8 • 23 Set Modem Phone Number 2 (3) Enter a phone number for another receiv ing m odem (if applicable). Press Enter to return to the Modem Setup m enu. Modem Phone Number 2 is not a leased-line option. Using an Alpha-Numeric Pager When using an alpha- numeric pag er, you m ust enter the letter "A& ...

  • Liebert RCM8DO - page 30

    Set Redial Interval (7) Enter a number (0- 99) representing the number of m inutes between redial attempts. Press Enter to return to the Modem Setup menu. Set Modem Messages (8) Type Y (es) to enable, or N (o) to disable m odem m essages. I f enabled, all comm unications to the RCM8 are echoed to the computer m onitor, printer, or terminal connecte ...

  • Liebert RCM8DO - page 31

    Chapter 3: Main Menu and SubMenus Set Terminal Options The Set Terminal Options Main Menu item lets you configure the audible beep characteristics that are annunciated when an alarm occurs and term inal/modem parity . This option also lets you enable a com munications check that sends a date and time messag e at a specified hour each day. To set te ...

  • Liebert RCM8DO - page 32

    Set 485 Options The Set 485 Options item from the Main Menu lets you address slave units connected to a m aster through the EI A-485 port. I f a connected slave unit loses com munication, the m aster RCM8 dials out to report the comm unication loss. To set EIA-485 port parameters: 1. From the Main Menu, press 8 to display the Terminal Options Sub-m ...

  • Liebert RCM8DO - page 33

    Chapter 3: Main Menu and SubMenus Liebert RCM8 • 27 Display SS Alarm Block The Di splay SS Alarm Block op tion from the Main Menu sends RCM8 inform ation to a SiteScan alarm block . Alarm information on up to 4 RCM8 units can be display ed by the SiteScan. To display the SiteScan alarm block: 1. From the Main Menu, press A to display the SiteScan ...

  • Liebert RCM8DO - page 34

    ...

  • Liebert RCM8DO - page 35

    Liebert RCM8 • 29 Section 4: Operation When the RCM8 is installed and config ured correctly, the unit basically operates on its own receiv ing and responding to incoming alarms. While the RCM8 is fully functional on its own, it is more conv enient to connect a computer or m onitor to facilitate operator interaction. This section describes the RCM ...

  • Liebert RCM8DO - page 36

    Review Alarms The RCM8 m aintains a history of alarm s that have been receiv ed by the unit. This alarm history can be accessed through the RCM8 Terminal m enu, or by accessing the RCM8 log on screen and pressing A. The alarm history log stores up to 100 local alarm s transmitted from non- repeater units or 16 al arm s transmitted from connected re ...

  • Liebert RCM8DO - page 37

    Section 5: RCM8 Equipment Maintenance Safety Instructions CAUTION: D EV ICE MUST BE ISOLATED OR DIS CONNECTED FROM THE HAZARDOUS LI VE V OLTAGE BEFORE ACCESS . NOTE: C IRCUIT B REAKER / SWITCH DOES NOT OPEN BATTERY CIRCUIT . O PEN CIRCUIT BREA KER / SWITCH AND DISCONNECT BATTERY PACK BE FORE SERV ICING DEVICE . NOTE: W HEN THE FOLLOWING SYMB OLS AR ...

  • Liebert RCM8DO - page 38

    ...

  • Liebert RCM8DO - page 39

    A ppendix A : Pager Special Characters The following characters are v alid for most pag ers. Refer to the documentation that cam e with your pag er for additional information. Table A–1 Telephone Number Characters Remote Modem and/or Pager Characters Character Description 0–9 Are the actual digits of the telephone num ber. ! Forces the modem to ...

  • Liebert RCM8DO - page 40

    ...

  • Liebert RCM8DO - page 41

    B-1 A ppendix B: Typical Configurations The RCM8 can be configured with trem endous flexibility, in order to accom modate v arious applications. The following diag rams illustrate som e typical sy stem config urations. Refer to Chapter 2 for complete explanation of DI P Switch setting s. Standalone Oper ation with Op tional Pager Dial-out and Op ti ...

  • Liebert RCM8DO - page 42

    Local String with Optional PC/Terminal Interf ace and Op tional SiteScan Interf ace B-2 Input s 25-32 Optional Slave #4 Input s 17-24 Optional Slave #3 Input s 1-8 Master #1 Input s 9-16 Slave #2 SiteScan SiteLink Module PC with Terminal Emu lation Application Or Video Displ ay Term inal ...

  • Liebert RCM8DO - page 43

    Local Strin g with Master Repeater, and Optional Pager Dial-out B-3 Master #1 Optional Slave #4 Optional Slave #3 Slave #2 Input s 25-32 Input s 17-24 Input s 1-8 Master Repeater Input s 9-16 “24-Hour Attend ed Security Station” “Main Com puter Room ” ...

  • Liebert RCM8DO - page 44

    Liebert Gl obal Services Remote Monitoring Master #1 Liebert Global Services 24 x 7 x 365 Cus tomer R esponse Center Optional Additional Slave Units Input s 1-8 SiteScan R emot e Dial-Up Mo nitoring Master Repeater Master #1 B-4 Optional Additional Slave Units Inputs 1- 8 SiteScan SiteLink Module “Central M onitoring Site” “Remote Facility” ...

  • Liebert RCM8DO - page 45

    Multipl e Rem ote Sites Moni tored from Central Location Location #1 B-5 Location #2 Location #3 Location #4 Master Repeater SiteScan SiteLink Module ...

  • Liebert RCM8DO - page 46

    Remote Contact Module RCM8CE & RCM8DO L IEBERT C ORPORATION 1050 D EARBORN D RIV E P.O. B OX 29186 C OLUMBUS , O HIO 43229 800.877.9222 P HONE 614.841.6022 F AX L IEBERT E UROPE L IEBERT A SIA G LOBE P ARK 19/F, C AUSEWAY B AY P LAZA 1 M ARLOW 489 H ENNESSY R OAD B UCKINGHAMSHI RE SL7 1YG C AUSEWAY B AY U NITED K INGDOM H ONG K ONG +44.1628.403 ...

Fabricant Liebert Catégorie Automobile Alarm

Les documents que nous recevons du fabricant de l'appareilLiebert RCM8DO peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques Liebert
- manuels d’utilisations RCM8DO
- fiches produit Liebert
- dépliants
- ou étiquettes-énergie Liebert RCM8DO
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation Liebert RCM8DO.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation Liebert RCM8DO, manuels d’entretien, brefs manuels ou manuels de l’utilisateur Liebert RCM8DO. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit Liebert RCM8DO.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil Liebert RCM8DO, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser Liebert RCM8DO par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs Liebert RCM8DO.

Le manuel d’utilisation complet Liebert, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel Liebert RCM8DO - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières Liebert RCM8DO, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lLiebert RCM8DO qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil Liebert RCM8DO - qui devraient nous aider dans les premières étapes lors de l'utilisation Liebert RCM8DO
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de Liebert RCM8DO
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service Liebert RCM8DO dans un pays donné, si le problème ne peut être résolu par nous-mêmes.