    ERV -1 LGH-F-RX3-E (Feb. 2009) Lossnay ERV LGH-F-RX3-E Performance Certied to ARI 1060 Standard LGH-F-RX 3 -E 1. COMP ARISON OF PRIMARY BUILDING VENTILA TION METHODS .................................................................... ERV -2 2 . LOSSNA Y ® PRINCIPLES............................................................................... ...

  • Mitsubishi Electronics LGH-F-RX3-E - page 2

    LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certied to ARI 1060 Standard ERV -2 There are two main ventilation methods: Centralized V entilation Method This is mainly used in large buildings, with the outside air intake being installed in one machine room. For this method, primary treatment of the outside air , such as energy recovery and du ...

  • Mitsubishi Electronics LGH-F-RX3-E - page 3

    ERV -3 LGH-F-RX3-E (Feb. 2009) Lossnay ERV LGH-F-RX3-E Performance Certied to ARI 1060 Standard 2.3. Calculation of T otal Energy Recovery Efficiency The Lossnay ® Core’s energy recovery efciency can be considered using the following three transfer rates: 1. T emperature (sensible heat) recovery efciency 2. Humidity (latent heat) recov ...

  • Mitsubishi Electronics LGH-F-RX3-E - page 4

    LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certied to ARI 1060 Standard ERV -4 2.5. Lossnay ® Operation / V entilation Modes Supply side Exhaust side T emperature t SA = t OA - (t OA - t RA ) x tt EA = t RA + (t OA - t RA ) x t Enthalpy i SA = i OA - (i OA - i RA ) x ii EA = i RA + (i OA - i RA ) x i Calculation of Supply Air Condition Aft ...

  • Mitsubishi Electronics LGH-F-RX3-E - page 5

    ERV -5 LGH-F-RX3-E (Feb. 2009) Lossnay ERV LGH-F-RX3-E Performance Certied to ARI 1060 Standard 2.6. Automatic Ventilation Switching - Bypass Damper Operation Effect of Automatic Ventilation Mode The automatic damper mode automatically provides the correct ventilation for the conditions in the room. It eliminates the need for manual switch opera ...

  • Mitsubishi Electronics LGH-F-RX3-E - page 6

    LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certied to ARI 1060 Standard ERV -6 2.72. Calculation T able for Dust Collection Efficiency of each Lossnay ® Filter 2.7.3. Pr essure Loss MERV Rating Dust Size (µm)* 6.6-8.6 6; 3.0-10.0 µm less than 49.9% * Note: ME RV rating is estimation from efficiency test data of AFI Gravitational method a ...

  • Mitsubishi Electronics LGH-F-RX3-E - page 7

    ERV -7 LGH-F-RX3-E (Feb. 2009) Lossnay ERV LGH-F-RX3-E Performance Certied to ARI 1060 Standard Outdoor Air (OA) Air drawn from outdoors - ventilation air . Pulse Input When the control signal from an external device outputs a pulse such as the one shown at right, the pulse input control is performed by the Lossnay ® unit. (Optional DIP switch ...

  • Mitsubishi Electronics LGH-F-RX3-E - page 8

    LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certied to ARI 1060 Standard ERV -8 3. LOSSNA Y ® MODELS AND SPECIFICA TIONS Model specifications and materials list for Lossnay ® units Model LGH-F300RX3-E Specifications Ta ble Model LGH-F300RX3-E Dimensions Ceiling suspension Nominal Duct connecting Duct pitch Unit fixture pitch diameter flan ...

  • Mitsubishi Electronics LGH-F-RX3-E - page 9

    ERV -9 LGH-F-RX3-E (Feb. 2009) Lossnay ERV LGH-F-RX3-E Performance Certied to ARI 1060 Standard Model LGH-F300RX3-E Characteristic Curve * Attention 1. The defrost mode must be operated at 14°F or belo w. 2. The current, power consumption, and efficiency are based on the above air flow rate. 3. The sound at the air outlets are the values at a 4 ...

  • Mitsubishi Electronics LGH-F-RX3-E - page 10

    LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certied to ARI 1060 Standard ERV -10 Model LGH-F470RX3-E Dimensions Ceiling suspension Nominal Duct connecting Duct pitch Unit fixture pitch diameter flange We ight A B C D E F G H J K inches 45-13/16 39-1/2 15-11/16 40-9/16 40-13/16 3/8 ø10 ø9-1/2 ø10-3/16 27-3/16 5 -7/8 143 lb mm 1164 1003 398 ...

  • Mitsubishi Electronics LGH-F-RX3-E - page 11

    ERV -1 1 LGH-F-RX3-E (Feb. 2009) Lossnay ERV LGH-F-RX3-E Performance Certied to ARI 1060 Standard Model LGH-F4 70RX 3 -E * Attention 1. The defrost mode must be operated at 14°F or belo w. 2. The current, power consumption, and efficiency are based on the above air flow rate. 3. The sound at the air outlets are the values at a 45° angle, 59 in ...

  • Mitsubishi Electronics LGH-F-RX3-E - page 12

    LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certied to ARI 1060 Standard ERV -12 Model LGH-F600RX 3 -E Model LGH-F600RX3-E Model LGH-F600RX3-E Specifications Ta ble Dimensions Ceiling suspension Nominal Duct connecting Duct pitch Unit fixture pitch diameter flange Weight A B C D E F G H J K inches 45-13/16 48-7/16 15-11/16 40-9/16 49-3/4 3/8 ...

  • Mitsubishi Electronics LGH-F-RX3-E - page 13

    ERV -13 LGH-F-RX3-E (Feb. 2009) Lossnay ERV LGH-F-RX3-E Performance Certied to ARI 1060 Standard Model LGH-F600RX 3 -E * Attention 1. The defrost mode must be operated at 14°F or belo w. 2. The current, power consumption, and efficiency are based on the above air flow rate. 3. The sound at the air outlets are the values at a 45° angle, 59 in. ...

  • Mitsubishi Electronics LGH-F-RX3-E - page 14

    LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certied to ARI 1060 Standard ERV -14 Model LGH-F1200RX 3 -E Model LGH-F1200RX3-E Model LGH-F1200RX3-E Specifications Ta ble --T wo addresses re quir ed . LGH-F1200RX 3 inches 65-7/16 48-7/16 31-1/2 40-9/16 50-1/8 8-3/4 ø 14 ø 13-3/4 29- 1/8 395 lb mm 1164 1230 8 00 1030 1273 222 ø356 ø 349 740 ...

  • Mitsubishi Electronics LGH-F-RX3-E - page 15

    ERV -15 LGH-F-RX3-E (Feb. 2009) Lossnay ERV LGH-F-RX3-E Performance Certied to ARI 1060 Standard Model LGH-F1200RX 3 -E * Attention 1. The defrost mode must be operated at 14°F or belo w. 2. The current, power consumption, and efficiency are based on the above air flow rate. 3. The sound at the air outlets are the values at a 45° angle, 59 in. ...

  • Mitsubishi Electronics LGH-F-RX3-E - page 16

    LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certied to ARI 1060 Standard ERV -16 E P L N A m 0 0 1 V 5 C D A 2 V 4 2 C D A m 0 0 1 V 0 2 2 C A A 2 V 0 4 2 C A N. I M X. A M t u p t u o r o t i n o m n o i t a r e p O A m 0 0 1 V 5 C D A 1 V 4 2 C D A m 0 0 1 V 0 2 2 C A A 1 V 0 4 2 C A N. I M X. A M t u p t u o r o t i n o m n o i t c n u f ...

  • Mitsubishi Electronics LGH-F-RX3-E - page 17

    ERV -17 LGH-F-RX3-E (Feb. 2009) Lossnay ERV LGH-F-RX3-E Performance Certied to ARI 1060 Standard LGH-F1200RX3-E • Dotted lines represent eld-supplied wire. • Be sure to connect the ground wire. • Breaker should be provided by the customer . 0 1 0 1 ) U E n i d i l a v n I ( Z H 0 6 ~ V 0 2 2 Z H 0 5 ~ V 0 4 2 - 0 2 2 Y L P P U S R E W O ...

  • Mitsubishi Electronics LGH-F-RX3-E - page 18

    LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certied to ARI 1060 Standard ERV -18 The human ear senses differently according to frequency . However , sound generated from a vibration is not limited to one frequency but in - stead various frequencies are generated at different levels. This is expressed by the NC curve, which is determined acco ...

  • Mitsubishi Electronics LGH-F-RX3-E - page 19

    ERV -19 LGH-F-RX3-E (Feb. 2009) Lossnay ERV LGH-F-RX3-E Performance Certied to ARI 1060 Standard 5.2. LGH-F-RX3-E NC Curves LGH-F300RX 3 LGH-F470RX 3 LGH-F600RX 3 : Lossnay ® ventilation : Lossnay ® ventilation : Lossnay ® ventilation : Lossnay ® ventilation : Lossnay ® ventilation : Lossnay ® ventilation 5 ft . belo w 5 ft . belo w 5 ft . ...

  • Mitsubishi Electronics LGH-F-RX3-E - page 20

    LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certied to ARI 1060 Standard ERV -20 7. INST ALLA TION 7.1. Installation Diagrams LGH-F300 · F470 · F600RX types LGH-F1200RX type Note: The double control board for the LGH-F1200RX has two M-NE T addresses. (1) The ceiling embedded type: 300, 470, 600 and 1200 CFM types are available. Select an a ...

  • Mitsubishi Electronics LGH-F-RX3-E - page 21

    ERV -21 LGH-F-RX3-E (Feb. 2009) Lossnay ERV LGH-F-RX3-E Performance Certied to ARI 1060 Standard 7.2. Alternate Installation for Lossnay T op/bottom reverse installation V ertical installation patterns Precautions Slanted installation Special Note ® ® All LGH-RX models can be installed in top/bottom reverse. Ve rtical installation is possible, ...

  • Mitsubishi Electronics LGH-F-RX3-E - page 22

    LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certied to ARI 1060 Standard ERV -22 7.3. Selecting Duct Attachment Direction Installation and maintenance Installation applications ® ®® ® ® ® Ø condensation. Choose between two directions for the outside duct (OA, EA) piping direction for optimum installation. A centralized controller can ...

  • Mitsubishi Electronics LGH-F-RX3-E - page 23

    ERV -23 LGH-F-RX3-E (Feb. 2009) Lossnay ERV LGH-F-RX3-E Performance Certied to ARI 1060 Standard 8. ELECTRICAL INST ALLA TION Names of components in control box Ground Bushing Ground Bushing Bushing With this product, the wiring installation method will vary according to the design of the system. Perform electrical installation for each of the r ...

  • Mitsubishi Electronics LGH-F-RX3-E - page 24

    LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certied to ARI 1060 Standard ERV -24 Use Lossnay ® M-NET remote controller PZ-52SF-E. (Do not use PZ-41SLB-E). Lossnay ® transmission connection terminal Two remote controller system with multiple Lossnay units It is also possible to operate two remote controller units when using multiple Lossnay ...

  • Mitsubishi Electronics LGH-F-RX3-E - page 25

    ERV -25 LGH-F-RX3-E (Feb. 2009) Lossnay ERV LGH-F-RX3-E Performance Certied to ARI 1060 Standard Use Lossnay ® M-NET remote controller PZ-52SF-E. (Do not use PZ-41SLB-E). Lossnay ® transmission connection terminal Two remote controller system with multiple Lossnay units It is also possible to operate two remote controller units when using mult ...

  • Mitsubishi Electronics LGH-F-RX3-E - page 26

    LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certied to ARI 1060 Standard ERV -26 System Selection ERV -22 LGH-F-RX3-E Lossnay operation when indoor unit is stopped Available Not available Lossnay stopping when indoor unit is operating Selecting Lossnay fan speed When interlocked with indoor unit for compatibility with R22, R407C and R410A Hi ...

  • Mitsubishi Electronics LGH-F-RX3-E - page 27

    ERV -27 LGH-F-RX3-E (Feb. 2009) Lossnay ERV LGH-F-RX3-E Performance Certied to ARI 1060 Standard Centralized Control System with CITY MUL TI ® Indoor unit Lossnay Indoor unit Outdoor unit A-control Mr. Slim P-Series outdoor unit Mr. Slim A-control PAR- 21 MAA remote controller A-control Mr. Slim indoor unit Lossnay Lossnay M-NET remote controll ...

  • Mitsubishi Electronics LGH-F-RX3-E - page 28

    LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certied to ARI 1060 Standard ERV -28 Remote controllers for CITY MULTI ® indoor unit Remote controllers for . Slim ® indoor unit Remote controllers for Lossnay ® unit ® ® ® ® ® ® PA R-21MAA ON/OFF FILTER CHECK OPERA TION CLEAR TEST TEMP . MENU BACK DAY MONITOR/SET CLOCK ON/OFF ERROR CODE A ...

  • Mitsubishi Electronics LGH-F-RX3-E - page 29

    ERV -29 LGH-F-RX3-E (Feb. 2009) Lossnay ERV LGH-F-RX3-E Performance Certied to ARI 1060 Standard Combination with CITY MULTI ® --Independent Lossnay ® System with Lossnay ® AG-150A Centralized controller ® ®® ® ® ®® ® ® Lossnay ® M-NE T r emot e Lossnay ® M-NET remote Lossnay ® M-NET remote Lossnay ® M-NET remote Lossnay ® M-NET ...

  • Mitsubishi Electronics LGH-F-RX3-E - page 30

    LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certied to ARI 1060 Standard ERV -30 Item Details Centralized contr oller MA r emote contr oller ME remote contr oller Lossnay ® M- NET r emote contr oller Local Remote Model ® O O O O O O O O O O O O o O o O o O o O o O O O O O O O O O Number of Lossnay ® remote controllers that can be connecte ...

  • Mitsubishi Electronics LGH-F-RX3-E - page 31

    ERV -31 LGH-F-RX3-E (Feb. 2009) Lossnay ERV LGH-F-RX3-E Performance Certied to ARI 1060 Standard CITY MULTI ® and Lossnay ® Interlocked System ® ® ® ®® ® ® ® ® ® ® ® ® ® ® Lossnay® remote controller PZ-41SLB-E cannot be used with any group on the M-NET . ...

  • Mitsubishi Electronics LGH-F-RX3-E - page 32

    LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certied to ARI 1060 Standard ERV -32 Item Details MA re mote controller ME re mote controller Lossnay M-NET re mote controller O Local Remote Model O 8 8 x 7 min. increments O O O O O O O O O O O O O O O O O O O O O O O O O ...

  • Mitsubishi Electronics LGH-F-RX3-E - page 33

    ERV -33 LGH-F-RX3-E (Feb. 2009) Lossnay ERV LGH-F-RX3-E Performance Certied to ARI 1060 Standard MA Remote Contr oller/ME Remote Contr oller in Combination with Lossnay M-NET Remote Contr oller Indoor Unit Lossnay LGH-RX type O O CENTRALI ZED CONT RO LLER AG -150 A z AG-150A z ...

  • Mitsubishi Electronics LGH-F-RX3-E - page 34

    LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certied to ARI 1060 Standard ERV -34 A mixed system including the CITY MUL TI can also be configured. CENTRALIZED CONT RO LLER AG -150 A z AG-150A CENTRALIZED CONT RO LLER AG -150 A z AG-150A ...

  • Mitsubishi Electronics LGH-F-RX3-E - page 35

    ERV -35 LGH-F-RX3-E (Feb. 2009) Lossnay ERV LGH-F-RX3-E Performance Certied to ARI 1060 Standard O Contents Individual Lossnay (Lossnay not set for interlocked operation) Interlocked Lossnay (Lossnay set for interlocked opera- tion with City Multi) When Using the LonWorks ® Compatible Adaptor (LMAP03U) to Connect to LonWorks ® By using the LON ...

  • Mitsubishi Electronics LGH-F-RX3-E - page 36

    LGH-F-RX3-E (Feb. 2009) LGH-F-RX3-E Performance Certied to ARI 1060 Standard ERV -36 ...

Fabricant Mitsubishi Electronics Catégorie Ventilation Hood

Les documents que nous recevons du fabricant de l'appareilMitsubishi Electronics LGH-F-RX3-E peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques Mitsubishi Electronics
- manuels d’utilisations LGH-F-RX3-E
- fiches produit Mitsubishi Electronics
- dépliants
- ou étiquettes-énergie Mitsubishi Electronics LGH-F-RX3-E
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation Mitsubishi Electronics LGH-F-RX3-E.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation Mitsubishi Electronics LGH-F-RX3-E, manuels d’entretien, brefs manuels ou manuels de l’utilisateur Mitsubishi Electronics LGH-F-RX3-E. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit Mitsubishi Electronics LGH-F-RX3-E.

Manuel d’utilisation complet de l’appareil Mitsubishi Electronics LGH-F-RX3-E, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser Mitsubishi Electronics LGH-F-RX3-E par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs Mitsubishi Electronics LGH-F-RX3-E.

Le manuel d’utilisation complet Mitsubishi Electronics, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel Mitsubishi Electronics LGH-F-RX3-E - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières Mitsubishi Electronics LGH-F-RX3-E, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lMitsubishi Electronics LGH-F-RX3-E qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil Mitsubishi Electronics LGH-F-RX3-E - qui devraient nous aider dans les premières étapes lors de l'utilisation Mitsubishi Electronics LGH-F-RX3-E
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de Mitsubishi Electronics LGH-F-RX3-E
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service Mitsubishi Electronics LGH-F-RX3-E dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de Mitsubishi Electronics LGH-F-RX3-E?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec Mitsubishi Electronics LGH-F-RX3-E, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec Mitsubishi Electronics LGH-F-RX3-E il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)