    1 COMMERCIAL ELECTRIC W A TER HEA TERS CAUTION TEXT PRINTED OR UNDERLINED IN RED CONT AINS INFORMA TION RELA TIVE TO YOUR SAFETY . PLEASE READ THOROUGHL Y BEFORE A TTEMPTING ANY CONVERSION. PRINTED IN U.S.A. 0906 P ART NO. 196674-001 A DIVISION OF A.O. SMITH CORPORA TION MCBEE, SOUTH CAROLINA ww w .hotwater .com Models DRE & DVE - 52/80/120 • ...

  • A.O. Smith DVE - page 2

    2 Rough-in-Dimensions Model Number T ank Cap acity in Gallons A B Inlet/Outlet DRE/DVE-52 50 55 1/4 21 3/4 1 1/4 DRE/DVE-80 80 59 1/2 25 1/4 1 1/4 DRE/DVE-120 1 19 62 1/4 29 1/2 1 1/4 Get to know your water heater ...

  • A.O. Smith DVE - page 3

    3 Contents Page ROUGH-IN-DIMENSIONS ....................................... 2 GET TO KNOW YOUR W ATER HEA TER ............... 2 RECOVERY CAP ACITY ........................................... 3 APPROV ALS ............................................................ 3 MODEL AND RA TING PLA TE .................................. 4 FOREWORD ............ ...

  • A.O. Smith DVE - page 4

    4 Model and Rating Foreword Detailed installation diagrams are in this manual. These diagrams will serve to provide the installer with a reference for the materials and method of piping suggested. IT IS NECESSARY THA T ALL W A TER PIPING AND THE ELECTRICAL WIRING BE INST ALLED AND CONNECTED AS SHOWN IN THE DIAGRAMS. Particular attention should be g ...

  • A.O. Smith DVE - page 5

    5 Inst allation REQUIRED ABILITY INST ALLA TION OR SERVICE OF THIS W A TER HEA TER REQUIRES ABILITY EQUIV ALENT TO THA T OF A LICENSED TRADESMAN IN THE FIELD INVOL VED. PLUMBING AND ELECTRICAL WORK ARE INVOL VED. GENERAL The installation must conform to these instructions and the local code authority having jurisdiction. Grounding and electrical wi ...

  • A.O. Smith DVE - page 6

    6 The pressure setting of the relief valve should not exceed the pressure capacity of any component in the system. The temperature setting of the relief valve should not exceed 210°F . An unplugged 3/4" relief valve opening is provided for installing temperature and pressure relief valve. TEMPERA TURE LIMITING CONTROL(S) Both the DVE and DRE ...

  • A.O. Smith DVE - page 7

    7 Piping Diagrams ONE TEMPERA TURE WITH CIRCULA TING LOOP INSERT B V ACUUM RELIEF V AL VE. INST ALL PER LOCAL CODES. CAUTION: IF BUILDING COLD W ATER SUPPL Y HAS A BACK- FLOW PREVENTER, CHECK V A L VE OR WA TER METER WITH CHECK V A L VE. PROVISIONS FOR THERMAL EXP ANSION OF W A TER IN THE HOT W A TER SYSTEM MUST BE PROVIDED. *PIPE T O OPEN DRAIN IN ...

  • A.O. Smith DVE - page 8

    8 INSER T B V ACUUM RELIEF V AL VE. INST ALL PER LOCAL CODES. DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERA TURE A T FIXTURES. SEE WA TER TEMPERA TURE CONTROL WARNING ON P AGE 6. IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY T O O BTAIN ADEQUATE BOOSTER OUTPUT , A DD AN ANTI-SCALD V AL VE FOR HOT WA TER SUPPLIED TO FIXTURES. ...

  • A.O. Smith DVE - page 9

    9 INSER T B V ACUUM RELIEF V AL VE. INST ALL PER LOCAL CODES. DANGER TEMPERA TURE SETTING SHOULD NOT EXCEED SAFE TEMPERA TURE AT FIXTURES. SEE W A TER TEMPERATURE CONTROL WARNING ON P AGE 6. IF HIGHER PREHEAT TEMPERA TURES ARE NECESSARY TO OBT AIN ADEQUA TE BOOSTER OUTPUT , ADD AN ANTI-SCALD VA LVE FOR HOT WA TER SUPPLIED T O FIXTURES. ...

  • A.O. Smith DVE - page 10

    10 ONE TEMPERA TURE ONE HEA TER VERTICAL ST ORAGE T ANK FORCED CIRCULA TION WITHOUT BUILDING RECIRCULA TION TWO TEMPERA TURE WITH MIXING V AL VE AND CIRCULA TING LOOP INSER T B V ACUUM RELIEF V ALVE. INST ALL PER LOCAL CODES. TWO TEMPERA TURE WITH MIXING V AL VE CAUTION: IF BUILDING COLD W A TER SUPPL Y HAS A BACK-FLOW PREVENTER, CHECK V A L VE OR ...

  • A.O. Smith DVE - page 11

    11 INSER T B V ACUUM RELIEF V ALVE. INST ALL PER LOCAL CODES. DANGER TEMPERA TURE SETTING SHOULD NOT EXCEED SAFE TEMPERA TURE A T FIXTURES. SEE WA TER TEMPERA TURE CONTROL WARNING ON P AGE 6. IF HIGHER PREHEA T TEMPERA TURES ARE NECESSAR Y TO OBT AIN ADEQUA TE BOOSTER OUTPUT , ADD A N ANTI-SCALD VAL VE FOR HOT W A TER SUPPLIED TO FIXTURES. ...

  • A.O. Smith DVE - page 12

    12 DANGER TEMPERA TURE SETTING SHOULD NOT EXCEED SAFE TEMPERA TURE A T FIXTURES. SEE WA TER TEMPERA TURE CONTROL WARNING ON P AGE 6. IF HIGHER PREHEA T TEMPERA TURES ARE NECESSAR Y TO OBT AIN ADEQUA TE BOOSTER OUTPUT , ADD A N ANTI-SCALD VAL VE FOR HOT W A TER SUPPLIED TO FIXTURES. INSER T B V ACUUM RELIEF V AL VE. INST ALL PER LOCAL CODES. ...

  • A.O. Smith DVE - page 13

    13 INSER T B V ACUUM RELIEF V AL VE. INST ALL PER LOCAL CODES. DANGER TEMPERA TURE SETTING SHOULD NOT EXCEED SAFE TEMPERA TURE A T FIXTURES. SEE WA TER TEMPERA TURE CONTROL WARNING ON P AGE 6. IF HIGHER PREHEA T TEMPERA TURES ARE NECESSAR Y TO OBT AIN ADEQUA TE BOOSTER OUTPUT , ADD A N ANTI-SCALD VAL VE FOR HOT W A TER SUPPLIED TO FIXTURES. ...

  • A.O. Smith DVE - page 14

    14 MANIFOLD KITS ALL DIMENSIONS IN INCHES. TWO HEA TERS Part Model Number H W D A DRE/DVE-52 9003429 66 1/4 56 3/4 27 1/4 13 1/4 DRE/DVE-80 9003429 70 1/2 60 1/4 31 1/4 9 3/4 DRE/DVE-120 9003429 73 1/4 64 1/2 35 3/4 5 1/2 Inlet and outlet size — 1 1/2 THREE HEA TERS Part Model Number H W D A DRE/DVE-52 9003430 66 1/4 91 3/4 27 1/4 13 1/4 DRE/DVE- ...

  • A.O. Smith DVE - page 15

    15 BRANCH CIRCUIT The branch circuit wire and fuse size should be established through reference to the current version of the National Electrical Code or any other locally approved source in conjunction with the heater amperage rating. Branch circuit wires should have a temperature rating no less than 75°C. For convenience, portions of the wire si ...

  • A.O. Smith DVE - page 16

    16 Full Load Current in Amperes KW Number of Element Single Phase Three Phase No. of No. of Input Elements W attage 208V 240V 277V 480V 208V 240V 480V Thermostat s Fuses 6 2000 28.8 25.0 21.7 12.5 16.7 14.4 7.2 9 3000 43.3 37.5 32.5 18.8 25.0 21.7 10.8 12 3 4000 57.7 50.0 43.3 25.0 33.3 28.9 14.4 3 6 13.5 4500 64.9 56.3 48.7 28.1 37.5 32.5 16.2 15 ...

  • A.O. Smith DVE - page 17

    17 DVE CONTROL CIRCUIT DIAGRAMS ...

  • A.O. Smith DVE - page 18

    18 POWER CIRCUIT The power circuit wiring is 12 Awg. AWM or TEW type, rated 600 volts, 105°C. Power circuit fusing consists of three 30 amp class G fuses for each contactor . See wiring diagrams. Do not substitute fuses of a different rating. DVE POWER CIRCUIT DIAGRAMS THREE ELEMENTS - SINGLE AND THREE PHASE SIX ELEMENTS - SINGLE AND THREE PHASE ...

  • A.O. Smith DVE - page 19

    19 CONVERSION TO SINGLE PHASE When the heater is shipped for connection to a three-phase electrical service, it may be connected to a single-phase electrical service of the same voltage by: 1. Disconnect blue wires and yellow wires from terminal L3. 2. Reconnect all blue wires to terminal L1 (with black wires). 3. Reconnect all yellow wires to term ...

  • A.O. Smith DVE - page 20

    20 HEA TER CIRCUITS—DRE MODELS The water heater's electrical components are pictured and identified on pa ge 2. The following describes the heater circuits and includes wiring diagrams. All heater circuits are designed for 60/50 hertz alternating current. The DRE circuit wiring is 12 A WG , AWM, or TEW type, rated 600 volts, 105°C. FUSING F ...

  • A.O. Smith DVE - page 21

    21 CONVERSION TO SINGLE PHASE When the heater is shipped for connection to a three-phase electrical service, it may be connected to a single-phase electrical service of the same voltage by: 1. Disconnect blue wires and yellow wires from terminal L3. 2. Reconnect all blue wires to terminal L1 (with black wires). 3. Reconnect all yellow wires to term ...

  • A.O. Smith DVE - page 22

    22 Operation GENERAL Never turn on power to the water heater without being certain the water heater is filled with water , and a temperature and pressure relief valve is installed in the relief valve opening. DO NOT TEST ELECTRICAL SYSTEM BEFORE HEA TER IS FILLED WITH W A TER. FOLLOW FILLING AND ST AR T -UP INSTRUCTIONS IN OPERA TION SECTION. FILLI ...

  • A.O. Smith DVE - page 23

    23 MAINTENANCE SCHEDULE Component Operation Interval Required T ank Flushing Periodically Un•Lime ® Element s Lime Scale As needed delimer & Removal element gaskets, Part Anode Inspect As needed T ank flushing should be performed in accordance with the above schedule. T ank sediment removal and element lime scale removal must be performed as ...

  • A.O. Smith DVE - page 24

    24 12. Attach element wires to connection point s from which they were removed. 13. Follow FILLING instructions to restore hot water service. • Check for water leaks around elements and proper operation when heater is filled. • Close the front panel. CHECKLIST Before calling for service, check the following points to see if the cause of trouble ...

  • A.O. Smith DVE - page 25

    25 Leakage Checkpoint s INSTRUCTIONS: USE THIS ILLUSTRA TION AS A GUIDE WHEN CHECKING FOR SOURCES OF W A TER LEAKAGE. YOU OR YOUR DEALER MA Y BE ABLE TO CORRECT WHA T APPEARS TO BE A PROBLEM. Where possible, remove or lift top cover to examine threads of fittings installed into tank for evidence of leakage. Correct fitting leaks as necessary . Reli ...

  • A.O. Smith DVE - page 26

    26 A. O. Smith Corporation, the warrantor, extends the following LIMITED W ARRANTY to the owner of this water heater: 1. THE T ANK If the glass-lined tank in this water heater shall prove upon examination by the warrantor to have leaked due to natural corros ion from potable water therein, during the first THREE years after initial installation, th ...

  • A.O. Smith DVE - page 27

    27 ...

  • A.O. Smith DVE - page 28

    28 McBee, South Carolina 29101 Phone: 1-800-527-1953 Fax: 800-433-2515 w w w .hotwater .com e-mail: p ar ts@hotwater .com ...

Fabricant A.O. Smith Catégorie Water Heater

Les documents que nous recevons du fabricant de l'appareilA.O. Smith DVE peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques A.O. Smith
- manuels d’utilisations DVE
- fiches produit A.O. Smith
- dépliants
- ou étiquettes-énergie A.O. Smith DVE
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation A.O. Smith DVE.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation A.O. Smith DVE, manuels d’entretien, brefs manuels ou manuels de l’utilisateur A.O. Smith DVE. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit A.O. Smith DVE.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil A.O. Smith DVE, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser A.O. Smith DVE par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs A.O. Smith DVE.

Le manuel d’utilisation complet A.O. Smith, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel A.O. Smith DVE - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières A.O. Smith DVE, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lA.O. Smith DVE qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil A.O. Smith DVE - qui devraient nous aider dans les premières étapes lors de l'utilisation A.O. Smith DVE
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de A.O. Smith DVE
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service A.O. Smith DVE dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de A.O. Smith DVE?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec A.O. Smith DVE, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec A.O. Smith DVE il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)