  • Carrier 19XR - page 1

    Installation Instructions SAFETY CONSIDERA TIONS Centrifugal liquid chillers are designed to provide safe and reliable service when operated within design speci- fications. When operating this equipment, use good judg- ment and safety precautions to avoid damage to equip- ment and property or injury to personnel. Be sure you understand and follow ...

  • Carrier 19XR - page 2

    CONTENTS Page SAFETY CONSIDERA TIONS ..................1 INTRODUCTION .............................2 General .....................................2 Job Data ....................................2 INST ALLA TION ............................. 2-35 Receiving the Machine .......................2 • INSPECT SHIPMENT • IDENTIFY MACHINE • PROVIDE MACH ...

  • Carrier 19XR - page 3

    Fig. 1 — Model Number Identification 3 ...

  • Carrier 19XR - page 4

    1— Oil Level Sight Glass 2— Diffuser Actuator (Hidden/19XR5 Only) 3— Discharge Isolation V alve 4— Condenser Pumpout Connection 5— Condenser Safety Relief V alves 6— Three-W ay Condenser Relief V alve 7— Hot Gas Bypass Line 8— Condenser W aterbox Nozzles 9— Cooler W aterbox Nozzles 1 0— Cooler Safety Relief V alves 11 — Cooler ...

  • Carrier 19XR - page 5

    MACHINE RIGGING GUIDE NOTES: 1. Each cable must be capable of supporting the entire weight of the machine. See chart for maximum weights. 2. Chain lengths shown are typical for 15 8 lifting height. Some minor adjustments may be required. COMPRESSOR FRAME SIZE* COOLER SIZE MAXIMUM WEIGHT (lb) VESSEL LENGTH DIM. ‘ ‘A ’’ CHAIN LENGTH DIM. ‘? ...

  • Carrier 19XR - page 6

    COMPRESSOR FRAME SIZE* COOLER SIZE MAXIMUM WEIGHT (lb) VESSEL LENGTH DIM. ‘ ‘A ’’ DIM. ‘ ‘B’ ’ DIM. ‘‘C’ ’ CHAIN LENGTH ‘ ‘D’ ’ ‘ ‘E’ ’ ‘ ‘F’ ’ 4 70-72 40,410 14 8 6 8 -6 9 3 8 -4 9 3 8 -5 9 11 8 -6 9 12 8 -5 9 12 8 -9 9 75-77 44,210 16 8 7 8 -5 9 3 8 -5 9 3 8 -5 9 12 8 -0 9 13 8 -3 9 13 8 -6 9 5 70-7 ...

  • Carrier 19XR - page 7

    T able 1 — 19XR Dimensions (Nozzle-In-Head W aterbox) HEA T EXCHANGER SIZE A (Length, with Nozzle-in-Head Waterbox) B (Width) C (Height) 2-Pass* 1 or 3 Pass† ft-in. mm ft-in. mm ft-in. mm ft-in. mm 10 to 12 11 - 3 7 ⁄ 8 3451 1 1-10 3 ⁄ 4 3626 4-1 1 3 ⁄ 4 1518 6- 1 1 ⁄ 4 1861 15 to 17 13- 7 3 ⁄ 8 4150 14- 2 1 ⁄ 4 4324 4-1 1 3 ⁄ 4 1 ...

  • Carrier 19XR - page 8

    T able 2 — 19XR Dimensions (Marine W aterbox) HEA T EXCHANGER SIZE A (Length, Marine Waterbox — not shown) 2-Pass* 1 or 3 Pass† ft-in. mm ft-in. mm 10 to 12 NA NA NA NA 15 to 17 NA NA NA NA 20 to 22 12- 6 5 ⁄ 8 3826 14- 3 4343 30 to 32 14- 9 4496 16- 4 3 ⁄ 4 4997 35 to 37 16- 5 1 ⁄ 2 5017 18- 1 1 ⁄ 4 5518 40 to 42 15- 0 1 ⁄ 4 4591 1 ...

  • Carrier 19XR - page 9

    T able 4 — 19XR Compressor Weights MOTOR CODE ENGLISH SI T otal Compressor Weight* (lb) T otal Compressor Weight* (kg) 60 Hz 50 Hz 60 Hz 50 Hz BD 3,755 3,755 1703 1703 BE 3,805 3,805 1726 1726 BF 3,870 3,870 1755 1755 BG 3,950 3,950 1792 1792 BH 3,950 3,950 1792 1792 CD 4,659 4,756 2134 2153 CE 4,685 4,771 2155 2165 CL 4,710 4,842 2137 2167 CM 4, ...

  • Carrier 19XR - page 10

    T able 6 — 19XR Heat Exchanger Data CODE ENGLISH SI Dry Rigging Weight (lb) Machine Charge Dry Rigging Weight (kg) Machine Charge Cooler Only Condenser Only Refrigerant Weight W ater V olume (gal) Cooler Only Condenser Only Refrigerant Weight W ater V olume Cooler Condenser Cooler Condenser Cooler Condenser Cooler Condenser 10 2,742 2,704 290 200 ...

  • Carrier 19XR - page 11

    T able 7 — 19XR Additional Data for Marine Waterboxes* HEA T EXCHANGER FRAME, P ASS ENGLISH SI Psig Rigging Weight (lb) W ater V olume (gal) kPa Rigging Weight (kg) W ater V olume (L) FRAME 2, 1 AND 2 P ASS 150 730 84 1034 331 318 FRAME 2, 2 P ASS 150 365 42 1034 166 159 FRAME 3, 1 AND 2 P ASS 150 730 84 1034 331 317 FRAME 3, 2 P ASS 150 365 42 1 ...

  • Carrier 19XR - page 12

    T able 8A — 19XR Waterbox Cover W eights ENGLISH (lb) HEA T EXCHANGER W A TERBOX DESCRIPTION FRAME 1 FRAME 2 FRAME 3 Standard Nozzles Flanged Standard Nozzles Flanged Standard Nozzles Flanged COOLER/ CONDENSER NIH, 1 Pass Cover , 150 psig 177 204 320 350 320 350 NIH, 2 Pass Cover , 150 psig 185 218 320 350 320 350 NIH, 3 Pass Cover , 150 psig 180 ...

  • Carrier 19XR - page 13

    T able 8B — 19XR W aterbox Cover Weights SI (kg) HEA T EXCHANGER W A TERBOX DESCRIPTION FRAME 1 FRAME 2 FRAME 3 Standard Nozzles Flanged Standard Nozzles Flanged Standard Nozzles Flanged COOLER/ CONDENSER NIH, 1 Pass Cover , 150 psig 80 93 145 159 145 159 NIH, 2 Pass Cover , 150 psig 84 99 145 159 145 159 NIH, 3 Pass Cover , 150 psig 82 89 136 15 ...

  • Carrier 19XR - page 14

    3. Disconnect the compressor dischar ge elbow at the com- pressor (Fig. 7, Item 3). 4. Cut the hot gas bypass line at the location shown (Fig. 6, Item 1). 5. Unbolt the cooler liquid feed line at the location shown (Fig. 6, Item 10). 6. Cover all openings. 7. Disconnect all wires and cables that cross from the cooler side of the machine to the cond ...

  • Carrier 19XR - page 15

    1— Guide V ane Actuator Cable 2— Power Panel to Starter Cables (Oil Pump Power , Control Power , and Communication) Fig. 7 — 19XR Chiller T op View 3— Compressor Discharge Elbow Joints 4— Condenser T ransducer Cable 1— Motor T emperature Sensor Cable 2— Bearing T emperature Sensor Cable Connection (Inside Box) 3— Compressor Oil Sump ...

  • Carrier 19XR - page 16

    1— Guide V ane Actuator 2— Diffuser Actuator 3— W ater T emperature Sensor Cables Fig. 9 — Chiller End View 16 ...

  • Carrier 19XR - page 17

    T o Rig Compressor NOTE: The motor end of the 19XR compressor is heavy and will tip backwards unless these directions are followed: 1. Cut two 4 in. × 6 in. wooden beams to the same length as the compressor . 2. Drill holes into the beams and bolt them to the base of the compressor . Additional Notes 1. Use silicon grease on new O-rings when refi ...

  • Carrier 19XR - page 18

    INST ALL SPRING ISOLA TION — Spring isolation may be purchased as an accessory from Carrier for field instal- lation. It may also be field supplied and installed. Spring iso- lators may be placed directly under machine support plates or located under machine soleplates. See Fig. 13. Consult job data for specific arrangement. Low profile sprin ...

  • Carrier 19XR - page 19

    Connect Piping INST ALL W A TER PIPING T O HEA T EXCHANGERS — Install piping using job data, piping drawings, and proce- dures outlined below . A typical piping installation is shown in Fig. 14. Factory-supplied insulation is not flammable but can be damaged by welding sparks and open flame. Protect in- sulation with a wet canvas cover. Remove ...

  • Carrier 19XR - page 20

    NOZZLE-IN HEAD W A TERBOXES FRAMES 1, 2, AND 3 FRAMES 4, 5, AND 6 NOZZLE ARRANGEMENT CODES FOR ALL 19XR NOZZLE-IN-HEAD W A TERBOXES P ASS COOLER WA TERBOXES In Out Arrangement Code* 1 85 A 58 B 2 79 C 46 D 3 76 E 49 F *Refer to certified drawings. P ASS CONDENSER W A TERBOXES In Out Arrangement Code* 1 11 2 P 21 1 Q 2 10 12 R 13 S 3 10 3 T 11 2 U ...

  • Carrier 19XR - page 21

    NOZZLE-IN-HEAD W A TERBOXES FRAMES 7 AND 8 NOZZLE ARRANGEMENT CODES FOR ALL 19XR NOZZLE-IN-HEAD W A TERBOXES P ASS COOLER WA TERBOXES In Out Arrangement Code* 1 85 A 58 B 2 79 C 46 D 3 76 E 49 F *Refer to certified drawings. P ASS CONDENSER WA TERBOXES In Out Arrangement Code* 1 11 2 P 21 1 Q 2 10 12 R 13 S 3 10 3 T 11 2 U Fig. 16 — Piping Flow ...

  • Carrier 19XR - page 22

    MARINE W A TERBOXES FRAMES 2 AND 3* *There is no Frame 1 marine waterbox. NOZZLE ARRANGEMENT CODES P ASS COOLER WA TERBOXES CONDENSER W A TERBOXES In Out Arrangement Code In Out Arrangement Code 1 85 A — — — 58 B — — — 2 79 C 1 0 1 2 R 46 D 1 3 S 3 76 E — — — 49 F — — — Fig. 17 — Piping Flow Data (MWB, Frames 2 and 3) 22 ...

  • Carrier 19XR - page 23

    MARINE W A TERBOXES (cont) FRAMES 4, 5, AND 6 NOZZLE ARRANGEMENT CODES P ASS COOLER WA TERBOXES CONDENSER W A TERBOXES In Out Arrangement Code In Out Arrangement Code 1 96 A — — — 69 B — — — 2 79 C 1 0 1 2 R 46 D 1 3 S 3 76 E — — — 49 F — — — FRAMES 7 AND 8 NOZZLE ARRANGEMENT CODES P ASS COOLER WA TERBOXES CONDENSER W A TERB ...

  • Carrier 19XR - page 24

    T able 9 — 19XR W aterbox Nozzle Sizes FRAME SIZE PRESSURE psig (kPa) P ASS NOMINAL PIPE SIZE (in.) ACTUAL PIPE ID (in.) Cooler Condenser Cooler Condenser 1 150/300 (1034/2068) 1 8 8 7.981 7.981 2 6 6 6.065 6.065 3 6 6 6.065 6.065 2 150/300 (1034/2068) 1 10 10 10.020 10.020 2 8 8 7.981 7.981 3 6 6 6.065 6.065 3 150/300 (1034/2068) 1 10 10 10.020 ...

  • Carrier 19XR - page 25

    DIMENSIONS ENGLISH (ft-in.) T ANK SIZE AB C D E F G H J K L M N P R S T 0428 10- 5 9-10 4-9 2-4 3 ⁄ 4 1-2 3 ⁄ 8 3-1 3 ⁄ 16 4-1 1 3-8 1 ⁄ 8 3- 8 2-9 7 ⁄ 16 3-2 0-3 1 ⁄ 2 4-8 3 ⁄ 4 1-7 7 ⁄ 8 1-7 5 ⁄ 16 3-7 3 ⁄ 4 5-0 1 ⁄ 4 0452 14-1 1 1 ⁄ 4 14- 4 1 ⁄ 2 5-0 7 ⁄ 8 2-8 1 ⁄ 2 1-4 1 ⁄ 4 3-4 7 ⁄ 16 7- 2 1 ⁄ 4 4-0 3-1 1 7 ...

  • Carrier 19XR - page 26

    RA TED DRY WEIGHT AND REFRIGERANT CAP ACITY ENGLISH (lb) T ANK SIZE T ANK OD (in.) DR Y WEIGHT* (lb) MAXIMUM REFRIGERANT CAP ACITY (lb) ANSI/ASHRAE 15 UL 1963 0428 24.00 2380 1860 1716 0452 27.25 3460 3563 3286 SI (kg) T ANK SIZE T ANK OD (mm) DR Y WEIGHT* (kg) MAXIMUM REFRIGERANT CAP ACITY (kg) ANSI/ASHRAE 15 UL 1963 0428 610 1080 844 778 0452 592 ...

  • Carrier 19XR - page 27

    Fig. 20 — Optional Pumpout System Piping Schematic with Storage T ank Fig. 21 — Optional Pumpout System Piping Schematic without Storage T ank 27 ...

  • Carrier 19XR - page 28

    INST ALL VENT PIPING TO RELIEF V AL VES — The 19XR chiller is factory equipped with relief devices on the cooler and condenser shells. Refer to Fig. 23 and T able 10 for size and location of relief devices. V ent relief devices to the outdoors in accordance with ANSI/ASHRAE 15 (latest edition) Safety Code for Mechanical Refrigeration and all othe ...

  • Carrier 19XR - page 29

    Fig. 24 — Carrier Comfort Network Communication Bus Wiring LEGEND Factory Wiring Field Wiring *Field supplied terminal strip must be located in control panel. Fig. 25 — COMM1 CCN Communication Wiring For Multiple Chillers (T ypical) 29 ...

  • Carrier 19XR - page 30

    CONNECT CONTROL OUTPUTS — Connect auxiliary equipment, chilled and condenser water pumps, and spare alarms as required and indicated on job wiring drawings. CONNECT ST AR TER — The 19XR is available with either a unit-mounted, factory-installed starter or a free-standing, field-installed starter (Fig. 28 and 29). Unit Mounted, Factory-Installe ...

  • Carrier 19XR - page 31

    Free-Standing, Field-Installed Starter — Assemble and in- stall compressor terminal box in desired orientation, and cut necessary conduit openings in conduit support plates. See Fig. 27 and 29. Attach power leads to compressor terminals in accordance with job wiring drawings, observing caution label in terminal box. Use only copper conductors. Th ...

  • Carrier 19XR - page 32

    IMPORT ANT : Wiring shown is typical and not intended to show detail for a specific installation. Refer to certified field wiring diagrams. NOTES: I. GENERAL 1.0 Starters shall be designed and manufactured in accordance with Carrier Engineering Requirement Z-375. 1.1 All field-supplied conductors, devices, field-installation wiring, and ter- m ...

  • Carrier 19XR - page 33

    LEGEND NOTES: I. GENERAL 1.0 Starters shall be designed and manufactured in accordance with Carrier Engineering Requirement Z-375. 1.1 All field-supplied conductors, devices, field-installation wiring, and ter- mination of conductors and devices must be in compliance with all ap- plicable codes and job specifications. 1.2 The routing of field-i ...

  • Carrier 19XR - page 34

    Connect Power W ir es to Oil Heater Contactor — Connect control power wiring between the oil heater contactor ter- minals and terminals LL1 and LL2 on the field wiring strip in the compressor motor starter . Refer to Fig. 31 and wiring label on the machine power panel. Voltage to terminals LL1 and LL2 comes from a con- trol transformer in a star ...

  • Carrier 19XR - page 35

    Install Field Insulation Protect insulation from weld heat damage and weld splatter. Cover with wet canvas cover during water piping installation. When installing insulation at the jobsite, insulate the fol- lowing components: • compressor motor • cooler shell • cooler tube sheets • suction piping • motor cooling drain • oil reclaim pip ...

  • Carrier 19XR - page 36

    ...

  • Carrier 19XR - page 37

    ...

  • Carrier 19XR - page 38

    Copyright 1997 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 2 Ta b 5 a PC 21 1 Catalog No. 531-940 Printed in U.S.A. Form 19XR-2SI Pg 38 10-97 Replaces: 19XR-1SI ...

  • Carrier 19XR - page 39

    INST ALLA TION ST ART -UP REQUEST CHECKLIST Machine Model Number: 19XR Serial Number: To : Attn: Date Project Name Carrier Job Number The following information provides the status of the chiller installation. YES/NO (N/A) DA TE TO BE COMPLETED 1. The machine is level. 2. The machine components are installed and connected in accordance with the inst ...

  • Carrier 19XR - page 40

    TESTING YES/NO DA TE TO BE COMPLETED 1. The cooling tower fan has been checked for blade pitch and proper operation. 2. The chilled water and condenser water lines have been: a. Filled b. T ested c. Flushed d. V ented e. Strainers cleaned 3. The chilled water and condenser water pumps have been checked for proper rotation and flow . 4. The followi ...

Fabricant Carrier Catégorie Fan

Les documents que nous recevons du fabricant de l'appareilCarrier 19XR peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques Carrier
- manuels d’utilisations 19XR
- fiches produit Carrier
- dépliants
- ou étiquettes-énergie Carrier 19XR
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation Carrier 19XR.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation Carrier 19XR, manuels d’entretien, brefs manuels ou manuels de l’utilisateur Carrier 19XR. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit Carrier 19XR.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil Carrier 19XR, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser Carrier 19XR par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs Carrier 19XR.

Le manuel d’utilisation complet Carrier, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel Carrier 19XR - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières Carrier 19XR, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lCarrier 19XR qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil Carrier 19XR - qui devraient nous aider dans les premières étapes lors de l'utilisation Carrier 19XR
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de Carrier 19XR
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service Carrier 19XR dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de Carrier 19XR?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec Carrier 19XR, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec Carrier 19XR il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)