    990-7096, Rev ision 2 User’s Manual English APC Smart-UPS     1400 VA 2U Rack Mount Uninterr uptible Pow er Supply 100 Vac ...

  • American Power Conversion 100 VAC - page 2

    ...

  • American Power Conversion 100 VAC - page 3

    990-7096, Rev ision 2 T ABL E O F C ONTENTS E NGLISH Chapter 1: Safety Information ................................................................... 1 Conventions Used in this Manua l ................................................................................................ .1 Handling Safe ty ............................................... ...

  • American Power Conversion 100 VAC - page 4

    Chapter 5: Maintena nce and Troub leshooting ...................... 15 Storage ........................................................................................................................ ................ 15 Storage Condit ions ............................................................................................................. ...

  • American Power Conversion 100 VAC - page 5

    1 990-7096 Rev . 2 C HA PTER 1: S AFE T Y I NFORMA TION This Safety Guide contains important instructions th at should be followed during installation an d main tenance of th e APC equipm ent an d batteries. It is intended f or APC custom ers w ho setu p, install, relocate, or maintain A PC equipment. Con vention s Used in this Manual Thi s secti o ...

  • American Power Conversion 100 VAC - page 6

    990 -7096 Rev. 2 2 Deenergizing Safety • This UPS has an intern al energy source (the battery ), the output may be energized w hen th e unit is not connected to an A C power outlet. • To d eenergize the UPS: first press the Off button to switch th e outputs off. Next disconnect the UPS from the A C power outlet, th en, disconnect the battery an ...

  • American Power Conversion 100 VAC - page 7

    3 990-7096 Rev . 2 C HA PTER 2: B AS I C S A bout A PC Am erican Power Conversion Corporation (APC) is the leading n ational and international man ufacturer of state of th e art unint erruptible pow er supplies, redun dant sw itches, pow er man agem ent s oftw are, and related equ ipm ent. APC products protect h ardw are, softw are, and dat a from ...

  • American Power Conversion 100 VAC - page 8

    990 -7096 Rev. 2 4 C HA PTER 3: I NST A LLA TION Unp acking APC ha s taken care to desi gn robus t packagin g for y our product. How ever, accident s and dam age may occur d uring ship ment. Inspection Inspect the UPS upon receipt. Notify th e carrier and dealer if there is damage. The packag ing is recycl able; save i t for reus e or dispose of i ...

  • American Power Conversion 100 VAC - page 9

    5 990-7096 Rev . 2 Mount the UPS in the Rack Select a location with adequate air f low that is free f rom excessive dust. Ensure that the air vents on the front and rear of the UPS are not blocked. Allow at least 2.54 cm (1 inch) of space on both sides. The UPS requires two people to install due to its weight. To lighten the UPS, you m ay rem ove t ...

  • American Power Conversion 100 VAC - page 10

    990 -7096 Rev. 2 6 Two- Post Racks 1. If the rack holes are not 10-32 threaded, firs t attach the backing plate suppl ied (870-1148)  to th e rack. 2. Support t he UPS from the f ront an d back. Inse rt the four (4) ornam ent al screws supplied with the UPS thro ugh the mounting b rac kets and into the top and bottom holes in the U-space as sh o ...

  • American Power Conversion 100 VAC - page 11

    7 990-7096 Rev . 2 on the front of the u nit. You may see small sparks when connecting th e battery. 3. Tuck the w hite battery cable cord into the space above th e UPS connector. 4. Unpack the f ront panel bezel and h old it with th e cutout section on the righ t. Align the tabs on th e side of the bezel w ith the slots on the f ront of t he UPS ? ...

  • American Power Conversion 100 VAC - page 12

    990 -7096 Rev. 2 8 The UPS charg es its battery whenev er it is connected to utility pow er. The battery charges fully during the first four hours of norm al operation. Do not expect full run time during this initial charge period. • The unit perform s a self -test autom atically wh en turned on , and every two w eeks thereafter (by defau lt). In ...

  • American Power Conversion 100 VAC - page 13

    9 990-7096 Rev . 2 C HA PTER 4: O PER A TION Front Panel This rack m ount UPS has th e power con trol and operating in dicators located on the f ront panel. 0 | TES T Operation The ON and OFF buttons con trol the pow er to the outlets on the UPS. They can be u sed as a mas ter On/Off switch for the conn ected equipm ent. The charger and com m unica ...

  • American Power Conversion 100 VAC - page 14

    990 -7096 Rev. 2 10 returns to on -line operation an d lights th e replace battery L ED. The connected equipm ent is not affected by a failed test . Recharge th e battery for 24 h ours and perform anoth er self-tes t. If it fails, the battery mus t be replaced. See Replacing the Ba ttery , page 16, for deta ils. Automatic Self-T est The UPS perform ...

  • American Power Conversion 100 VAC - page 15

    11 990- 7096 Rev. 2 Battery Power If the utility power f ails, the UPS can provide power to the connected equipm ent from its in ternal battery f or a finite period. The UPS sounds an alarm, f our beeps every 30 seconds, w hile operating on battery pow er. The alarm s tops w hen th e UPS returns to on-li ne operation. On-Battery Power Indi cator Wh ...

  • American Power Conversion 100 VAC - page 16

    990 -7096 Rev. 2 12 Rear Panel The rear panel has the input and output conn ectors, computer interface port, and m anual settings for the low battery w arning level an d voltage sensitivity indicator. x MADE IN USA (WEST KINGST ON, RI) SU1400R M2U XX01234 56789 Computer Interfac e Port Optional power m anagem ent s oftw are and interface k its can ...

  • American Power Conversion 100 VAC - page 17

    13 990- 7096 Rev. 2 Low Battery W arning Level By def ault, the low battery w arnin g occurs w hen there are approxim ately tw o m inutes of on-battery run time remaining. This may not be enough time to gracefully shut down some protected compu ter sys tems . To change the w arning interv al, press the rear panel Sensitivity bu tton while pressing ...

  • American Power Conversion 100 VAC - page 18

    990 -7096 Rev. 2 14 User Configur ation Items Note: Setting these item s requires software or optional hardware. Function Factory Default User Selectable Choices Description Autom atic Self- Tes t Every 14 days (336 hours ) Every 7 days (168 hours) , On Star tup Only, No Self -Test Sets the interval at w hich th e UPS will execute a self-t est. Ref ...

  • American Power Conversion 100 VAC - page 19

    15 990- 7096 Rev. 2 C HA PTER 5: M A INTENANCE A ND T ROUBLE SHOOTING Storage This section describes how to store the UPS while it is not in u se. To remove the UPS from the rack, see Removing the UPS from the Rack , page 6. Storage Conditions Store the UPS covered and flat (rack m ount orientation) in a cool, dry location, w ith its battery fully ...

  • American Power Conversion 100 VAC - page 20

    990 -7096 Rev. 2 16 1. Face the front of the UPS and, usin g both hands , insert each index fin ger behind the lip of the curv ed section of the front panel bezel and pu ll towards y ou. The fron t panel bezel will u nsnap. 2. Set the bezel aside. 3. Take out the w hite cord, w hich is tu cked into the space above the battery connector  . Gras p ...

  • American Power Conversion 100 VAC - page 21

    17 990- 7096 Rev. 2 T roubleshooti ng Use the ch art below to solve m inor UPS ins tallation probl ems. C ontact A PC Technical Support Staff (see How to Contac t APC , page 3) for assis tance w ith com plex UPS problems. Problem and Possible Cause Solut ion UPS will not turn on. • ON b utton not pushed. Press the ON button once to pow er the UPS ...

  • American Power Conversion 100 VAC - page 22

    990 -7096 Rev. 2 18 UPS is plugged into wall o utlet and only the battery cha rge bar g raph is lit. • T he UPS is shut dow n an d the battery is disc harged f rom an extended outag e. None. The UPS will return to normal operation w hen the pow er is restored and th e battery h as a suff icient charg e. Replace battery light is lit and the UPS be ...

  • American Power Conversion 100 VAC - page 23

    19 990- 7096 Rev. 2 Service and T ransport If the UPS requires service do not return it to the dealer! Follow these steps: 1. Revi ew th e problem s discu ssed in Troubleshoot ing , page 17, to eli min ate comm on problem s. 2. Verify that no circuit breakers are tripped – this is the m ost com mon UPS problem! 3. If the problem persists, call cu ...

  • American Power Conversion 100 VAC - page 24

    990 -7096 Rev. 2 20 Regulatory A gency A ppr ovals ® LI STED 4 2C 2 E9 54 63 This is a Class A product based on the standard of the Voluntary Control Council for Interference by In formation Technology Equipment (VCCI ). If this equipm ent is used in a domestic environm ent, radio disturbance may occur, in which case, the user may be required to t ...

  • American Power Conversion 100 VAC - page 25

    21 990- 7096 Rev. 2 Limited War ranty Am erican Pow er Conversion (APC) w arrants its products to be free f rom defects in m aterials and w orkma nshi p for a period of tw o years from the dat e of purch ase. Its obli gation u nder thi s warran ty is lim ited to repairing or replacing, at its own sole option, any such defective products. To obtain ...

Fabricant American Power Conversion Catégorie Power Supply

Les documents que nous recevons du fabricant de l'appareilAmerican Power Conversion 100 VAC peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques American Power Conversion
- manuels d’utilisations 100 VAC
- fiches produit American Power Conversion
- dépliants
- ou étiquettes-énergie American Power Conversion 100 VAC
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation American Power Conversion 100 VAC.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation American Power Conversion 100 VAC, manuels d’entretien, brefs manuels ou manuels de l’utilisateur American Power Conversion 100 VAC. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit American Power Conversion 100 VAC.

Manuel d’utilisation complet de l’appareil American Power Conversion 100 VAC, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser American Power Conversion 100 VAC par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs American Power Conversion 100 VAC.

Le manuel d’utilisation complet American Power Conversion, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel American Power Conversion 100 VAC - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières American Power Conversion 100 VAC, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lAmerican Power Conversion 100 VAC qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil American Power Conversion 100 VAC - qui devraient nous aider dans les premières étapes lors de l'utilisation American Power Conversion 100 VAC
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de American Power Conversion 100 VAC
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service American Power Conversion 100 VAC dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de American Power Conversion 100 VAC?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec American Power Conversion 100 VAC, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec American Power Conversion 100 VAC il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)