    PAGE 1 BIASI B/40 LINEAR 6-12 SEC TION REV. H Please Read Instructions Carefu lly Save for Futur e Refer ence Manufac tured by: Manufac tured by: Manufac tured by: Manufac tured by: Biasi S.p.A. Biasi S.p.A. Biasi S.p.A. Biasi S.p.A. Verona, Ital y Verona, Ital y Verona, Ital y Verona, Ital y Distributed By: Distributed By: Distributed By: Distribu ...

  • Linear Boiler - page 2

    BIASI B/40 PAGE 2 Dear Customer: Thank you for bu y ing a Linear comme rcial boiler. The Linear is a cast i ron, oil or gas fired hot water boil er, u sing t he famous 3-pass design. The boiler is simple, rugged a nd engineered for maximum h eating efficiency. We realize that it is not p ossible to answer all questions about the L inear series boil ...

  • Linear Boiler - page 3

    PAGE 3 BIASI B/40 BIASI B-40 L inear Series Section Page Important Information 1 4 General Information 2 6 Codes and Regulations 3 6 Combustion Ai r Supply 4 7 Boiler Location 5 7 Boiler Block Assembl y 6 8 Boiler Trim Kit Installati on 7 8 Boiler Tapping Diagram - 9 Burner Set-up 8 10 Gas Piping 9 12 Breeching and Chimne y 10 14 Piping 11 15 Boile ...

  • Linear Boiler - page 4

    BIASI B/40 PAGE 4 IMPORTANT INFOR MATION Please read this page caref ully. ALL BOILERS MUST BE INSTALLED IN ACCORDANC E WITH NAT IONAL, STATE AND LOCAL PLUMBING, H EATING AND ELECTR ICAL CODES AND ORD INANCES, AS WE LL AS THE REGULATIONS O F THE SERVING E LECTRICAL, WATER AND GAS UT ILITIES. All systems should be des igned by competent contractors, ...

  • Linear Boiler - page 5

    PAGE 5 BIASI B/40 Any appliance that burns natural gas, propane gas, fuel oil, wo od or coal is capable of producin g carbon monoxide (CO). Carbon Monoxid e (CO) is a gas which is odorless, colorless and tast eless but is very toxic. If your BIASI B-40 boil er is not working properly, or is not vented p roperly, dangerous levels of C O may accumula ...

  • Linear Boiler - page 6

    BIASI B/40 PAGE 6 The Linear series are wet base design, sectional, cast -iron boilers for forced ho t water heating systems. The Linear boil ers are designed for firing with oil and deli ver high efficiencies throu gh unique design and constructi on. The Linear series boilers are shipped f rom the factor y in assembled blo cks and each boiler can ...

  • Linear Boiler - page 7

    PAGE 7 BIASI B/40 Locate the boiler to provide sufficient cl earance for inspection, servicin g and maintenance. Minimum clearance to c onstruction or combustibl e materials shouldn't be less than six (6) inches from the top, sides and rear of un it, and eighteen (18) inches from the flu e pipe in any direction. Front clearance should be at le ...

  • Linear Boiler - page 8

    BIASI B/40 PAGE 8 All Linear series boilers are shipped either as an assemb led boiler block or a knock-down boiler block. If the block came unass embled, or if the assembled block ne eds to be spli t for installa- tion purposes, please read t he following: To assemble split blocks, m ove the sections into a li ne facing each other. Sectio ns may b ...

  • Linear Boiler - page 9

    PAGE 9 BIASI B/40 Figure 1:Diagram illustra ting the location and functi on of the front and rear boiler tappings. Boiler Model Length (L) B-40/6 34.8” B-40/7 39.5” B-40/8 4 4.5" B-40/9 49.2" B-4/10 5 3.9" B-4/11 5 8.8" B-4/12 6 3.9" 2.5” MPT Return 2.5” MPT Supply 8” Breech Control Pane l with operating aq uastat ...

  • Linear Boiler - page 10

    BIASI B/40 PAGE 10 Good, reliable op eration with a minimum of service star ts w ith attention to t he small de tails: 1. Setting the nozz le positio n and electrode s "by the book" using the manu facturer's ga uges. 2. Installing a q uality micro n filter at the burner. 3. Making care ful/tight flare connection s without coupli ngs ...

  • Linear Boiler - page 11

    PAGE 11 BIASI B/40 B U R N E R MAN U FA C TU R E R H e a t W i s e B oi l e r Mo de l B - 4 06 B - 4 07 B -40 8 B - 4 09 B - 4 10 B- 41 1 B- 4 12 B urne r M ode l S U- 3 SU -3 SU -4 S U- 5 SU -5 SU- 6 SU- 6 Fue l N atur a l N a tura l N a tura l N a tura l N atur a l N atur al N a tur al I nput 31 5 4 20 499 57 7 67 2 8 47 9 5 4 Mi n. Ga s I nl e t ...

  • Linear Boiler - page 12

    BIASI B/40 PAGE 12 To check for gas leaks, use a gas detector or apply a soap solution to the joints. DO NOT USE AN Direction of flow Manual Shutoff Valve Height of shutoff valve above ground level to conform to local codes, Pressure Gauge Port (1/8” NPT plugged) Minimum 1” X 1” X 1” Tee Male Union 1” NPT Burner Gas Pipe Cap 3” MINIMUM ...

  • Linear Boiler - page 13

    PAGE 13 BIASI B/40 Piping should con sist of: 1. A shut off valve ap proximately 6’ awa y from th e unit. 2. A 1/8” plugged N PT tapping for ga s pressure measure ment preferabl y on the manual shut-off valve (as shown or anywh ere between the gas valve and th e shut off value). Note: The m anual shut of f valve and tapping a re NOT part of the ...

  • Linear Boiler - page 14

    BIASI B/40 PAGE 14 The B-40 Linear boiler is a high effici ency unit that requires proper ventin g. The boiler must be vented to the outdoors by means of a tile lined masonr y or an approved pre-fabricated chimne y of the size and height recom mended by the manufacturer or b y a listed "power venting" unit which provides draft b y mechani ...

  • Linear Boiler - page 15

    PAGE 15 BIASI B/40 All piping must co nform to state and loca l codes. The supply and return manifolds for B-40 Linear boilers are 2 1/2” m ale NPT. Be sure to provide unions and gate valves at t he manifold inlet and outlet of the boiler , so the boiler ma y be readily isolated for service. Install the provided pressure relie f valve so the disc ...

  • Linear Boiler - page 16

    BIASI B/40 PAGE 16 ...

  • Linear Boiler - page 17

    PAGE 17 BIASI B/40 NOTE : All pi ping, boiler controls, gauges and val ves must be installed before the jack et has been assembled on the boiler. R efer to the following page to clarif y these boiler jacket assembl y instructions. Insert the separate piece of insu lation (# 92) on top of boiler so the entire t op and sides of boiler are covered. Us ...

  • Linear Boiler - page 18

    BIASI B/40 PAGE 18 1 2 3 4 5 6 7 8 9 1 On/Off Swit ch 2 Min. Boiler Temp. Thermostat 3 Max Boiler Temp. Thermostat 4 Thermostat B y-Pass Button 5 Circulator S witch 6 Boiler On/O ff Signal Lamp 7 Temperature Gau ge 8 Manual Reset Hi gh Limit 9 Burner Lock Out Signal Lamp * NOTE: If th e thermostat test button is closed, the ther mostats will b e by ...

  • Linear Boiler - page 19

    PAGE 19 BIASI B/40 1 2 3 4 5 6 7 8 9 1. O n/Off Switch — Turns power to control panel on and off and will disable power to the burn er assuming the panel is wir ed correctl y . 2. Mi nimum Boiler Temperature The rmostat — Maintains a mini mum boiler temperature be- tween 50 degrees F and 170 d egrees F. 3. Maxi mum Boiler Temperature Ther mosta ...

  • Linear Boiler - page 20

    BIASI B/40 PAGE 20 B-40 Contr ol Panel W iring Diagram for Beckett/Heat W ise Oil Burner 24V CIRCUL ATOR R ELAY BURNER CON TROL ...

  • Linear Boiler - page 21

    PAGE 21 BIASI B/40 B-40 Contr ol Panel W iring Diagram for Beckett/Heat W ise Oil Burner Line V oltage CIRCULA TOR R ELAY BURNER CON TROL ...

  • Linear Boiler - page 22

    BIASI B/40 PAGE 22 B-40 Contr ol Panel W iring Diagram for Riello Oil Burner ...

  • Linear Boiler - page 23

    PAGE 23 BIASI B/40 B-40 Contr ol Panel W iring Diagram for Heat W ise Gas Burners CIRCULA TOR R ELAY Burner Prim ary Control ...

  • Linear Boiler - page 24

    BIASI B/40 PAGE 24 Check for fouling or soot b uildup in the combusti on chamber at least every twelve (12) months. Caution: Black carbon so ot in the combustion chamber can, und er certain conditions, be ignited by a spark or open flame. To prev ent this unlikel y occurrence, dampen the soot deposit s with a wet brush or a fine water spray before ...

  • Linear Boiler - page 25

    PAGE 25 BIASI B/40 System Checkout: Boiler Model No.___________ ______ Serial No.__________ Original Purchaser: Installer: _________________________ ______________________ _________________________ ______________________ _________________________ ______________________ Burner Manufacturer----------- Type of Oil Burner------------- Burner Model No.- ...

  • Linear Boiler - page 26

    BIASI B/40 PAGE 26 ...

  • Linear Boiler - page 27

    PAGE 27 BIASI B/40 ...

  • Linear Boiler - page 28

    BIASI B/40 PAGE 28 ITEM #: B40 REV. H W ar ranty For BIASI B40 Series Commercial Cast-Iron Water Boiler s FIRST YEAR through TENTH YEAR -WARRANTY FOR B4 0 SERIES COMMERCIAL HOT W ATER BOILERS: QHT warrant s that its cast-iron bo iler and casing are free from defects in material and workmansh ip for ten years from the d ate of installation at the or ...

Fabricant Linear Catégorie Boiler

Les documents que nous recevons du fabricant de l'appareilLinear Boiler peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques Linear
- manuels d’utilisations Boiler
- fiches produit Linear
- dépliants
- ou étiquettes-énergie Linear Boiler
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation Linear Boiler.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation Linear Boiler, manuels d’entretien, brefs manuels ou manuels de l’utilisateur Linear Boiler. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit Linear Boiler.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil Linear Boiler, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser Linear Boiler par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs Linear Boiler.

Le manuel d’utilisation complet Linear, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel Linear Boiler - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières Linear Boiler, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lLinear Boiler qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil Linear Boiler - qui devraient nous aider dans les premières étapes lors de l'utilisation Linear Boiler
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de Linear Boiler
5. FAQ - questions fréquemment posées