    GB200-IM-5 42-9184 GB200 SERIES INST ALLA TION, OPERA TION & MAINTENANCE MANU AL WITH REPLA CEMENT P AR TS LIST GAS-FIRED STEAM CAST IR ON BOILERS 85,000 T O 165,000 BTUH INPUT INTERMITTENT PILO T/VENT D AMPER & ST ANDING PILO T/VENT D AMPER SECTION 1: INTRODUCTION Code Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...

  • Smith Cast Iron Boilers GB200 SERIES - page 2

    2 SECTION 1: INTR ODUCTION The f ollowing terms are used throughout this manual to bring attention to the presence of potential hazards or to impor tant inf or mation concerning the product: CA UTION: Indicates a potentially hazardous situation which, if not av oided, may result in minor injury or prop- erty damage . NO TE: Used to notify of specia ...

  • Smith Cast Iron Boilers GB200 SERIES - page 3

    CHIMNEY REQUIREMENTS D ANGER: A chimne y which does not meet modern safety standar ds will result in a fire or deadly carbon mono xide poisoning of the building residents. Chimney condition is of par amount impor tance for a saf e and efficient boiler installation. All new and replacement installa- tions must include a chimne y inspection by a qual ...

  • Smith Cast Iron Boilers GB200 SERIES - page 4

    4 FIGURE 2.1: MODEL GB200 BOILER DIMENSIONS PRESS. RELIEF V AL VE B W A TER LEVEL INDICA TOR 2" RETURN FRONT MINIMUM CLEARANCES TO COMB USTIBLES T op: 28" Rear: 18" Left & Right: 18" Front: ALCOVE BOILER MODEL GB200-S-4H GB200-S-4L GB200-S-3 GB200-S-5 DIMENSIONS A 15 3/8" 18 7/8" 18 7/8" 22 3/8" 5" 6 ...

  • Smith Cast Iron Boilers GB200 SERIES - page 5

    5 STEP 2: INST ALLING STEAM PIPING T ypical piping connections are shown in Figure 2.3. All e xter- nal piping must be suppor ted by hangers, not b y the boiler or its accessories. Supply outlet must run full size from the boiler to a header at least 24" abov e top of boiler . Condensate retur n piping should be connected to boiler through a & ...

  • Smith Cast Iron Boilers GB200 SERIES - page 6

    6 STEP 4: VENTING BOILER A f actor y-mounted spill s witch is provided on all GB200 boil- ers (see Figures 2.4 & 2.4A). The flue or vent connectors m ust be installed flush with the inside chimney liner surf ace and sealed in place with fur nace cement. Horizontal positions of the single wall and type B venting systems shall be supported by use ...

  • Smith Cast Iron Boilers GB200 SERIES - page 7

    7 FIGURE 2.5: A TT ACHING VENT D AMPER T O DRAFT DIVERTER & FLUE PIPE FLOW DIRECTION ARRO W POINTS UP (REAR VIEW) MAKE SURE MO T OR IS LOCA TED ON FRONT SIDE CLOSED OPEN FLOW DIRECTION MOUNT VENT D AMPER O VER DRAFT DIVER TER INST ALL SWITCH IN OPENING ON DRAFT DIVERTER ADDITIONAL CHIMNEY REQUIREMENTS Chimney condition is of par amount impor ta ...

  • Smith Cast Iron Boilers GB200 SERIES - page 8

    Maximum Capacity of Pipe in Cubic Feet of Natural Gas per Hour for Gas Pressures of 0.5 Psig or Less and a Pressure Drop of 0.3 Inch Water Column (Based on a 0.60 Specific Gravity Gas) Nominal Iron Pipe Size, Inches Internal Diameter, Inches Length of Pipe, Feet 10 32 72 132 278 520 1,050 1,600 3,050 4,800 8,500 17,500 20 22 49 92 190 350 730 1,100 ...

  • Smith Cast Iron Boilers GB200 SERIES - page 9

    9 STEP 6: WIRING BOILER All electrical and control wir ing must be installed in accor- dance with the codes listed in Section 1 of this manual. F ol- low the wiring diagram f or your par ticular installation as shown in Figures 2.8, 2.9, 2.10, and 2.11. F or vent damper-equipped models , connect thermostat to blue leads (see Figures 2.4 & 2.4A) ...

  • Smith Cast Iron Boilers GB200 SERIES - page 10

    10 FIGURE 2.10: Wiring Diagram & Operation Sequence f or Boilers Equipped with Intermittent Pilot, V ent Damper and 400 Series or M & M PS804 L WCO FIGURE 2.11: Wiring Diagram & Operation Sequence f or Boilers Equipped with Standing Pilot, V ent Damper and 400 Series or M & M PS804 L WCO ...

  • Smith Cast Iron Boilers GB200 SERIES - page 11

    SECTION 3: ST AR T -UP & OPERA TION SEQUENCE OF OPERA TION F or sequence of operation of the par ticular boiler being installed, ref er to Figures 2.8, 2.9, 2.10 and 2.11 in Section 2 of this manual. Spill and rollout s witches are mounted on all GB200 boilers. The spill s witch detects the escape of combustion products through the draft div er ...

  • Smith Cast Iron Boilers GB200 SERIES - page 12

    12 Example: A GB200-4L boiler takes 5 min utes, 27 seconds to use 10 cubic f eet of natural gas. The local utility indicated the heating value of the natur al gas being supplied is 1000 Btu/cu ft. Theref ore: 5 minutes, 27 seconds = 327 seconds . 36,000 x 1000 = 110,000 Btu/hr 327 Theref ore, the boiler input is correct. NO TE: Before calculating t ...

  • Smith Cast Iron Boilers GB200 SERIES - page 13

    13 W ARNING: If you do not f ollow these instructions exactly , a fire or explosion ma y result with property damage, personal injury , or loss of life . LIGHTING CONTINUOUS PILO T INSTRUCTIONS Honeywell VR8200 Natural or Propane Gas A. BEFORE OPERA TING smell all around the appliance area f or gas. Be sure to smell ne xt to the floor because some ...

  • Smith Cast Iron Boilers GB200 SERIES - page 14

    14 T O TURN OFF APPLIANCE INLET GAS CONTROL KNOB SHOWN IN "OFF" POSITION GAS ON OFF INTERMITTENT PILO T - HONEYWELL VR8204 1. Set the thermostat to lowest setting. 2. T urn off all electr ic power to the appliance if service is to be perf or med. OPERA TING INSTRUCTIONS Intermittent Pilot - Honeywell VR8204 Natural or Propane Gas 1. ST OP ...

  • Smith Cast Iron Boilers GB200 SERIES - page 15

    15 4. Check gas manif old for proper position and reassemble burners to the manifold. Line up holes in b urners with the or i- fices, and slide assemb ly back into position. Be sure to rein- stall burner s with burner ports on the top surface (upright). 5. When a low w ater cut-off has been utilized, f ollow the manuf acturer ’ s maintenance inst ...

  • Smith Cast Iron Boilers GB200 SERIES - page 16

    1 Jac k et - Complete 59248 1 Jac k et - Complete 59249 1 1 Jac k et - Complete 59250 1 2 Bur ner - N.G./L.P . 59089 2334 3 Bur ner w/Pilot Brac ket - N.G./L.P . 59091 1111 4 Base Door Ass'y 59092 1 Base Door Ass'y 59093 1 1 Base Door Ass'y 59094 1 6 Base P an 59056 1 Base P an 59057 1 1 Base P an 59058 1 8 Manif old 59119 1 Manif ol ...

  • Smith Cast Iron Boilers GB200 SERIES - page 17

    Standing Pilot 5 Pilot Ass'y NG- Q314ALB, Q309A 72364 1 1 1 Pilot Ass'y NG- Q314ALB, Q309A 72365 1 Pilot Ass'y LP- Q314ALB, Q309A 72370 1111 Pilot Ass'y LP- Q314ALB, Q309D 72371 1 — Ther mocouple K16RA-30D 59109 1 1 1 Ther mocouple K16RA-36D 51006 1 9 Gas V alv e - NG VR8200H-1129 NG/LP* 59129 1111 28 T ransformer 115/24 V , 4 ...

  • Smith Cast Iron Boilers GB200 SERIES - page 18

    18 27 13 12 11 16 17 26 8 5 3 10 4 6 30 14 9 2 15 32 33 20 25 22 23 24 21 FIGURE 1: GB200 GENERAL ASSEMBL Y 1 28 31 30 34 ...

  • Smith Cast Iron Boilers GB200 SERIES - page 19

    19 ...

  • Smith Cast Iron Boilers GB200 SERIES - page 20

    20 Any appliance that b urns natural gas, propane gas, fuel oil, wood or coal is capab le of producing carbon mono xide (CO). Carbon mono xide (CO) is a gas which is odorless, colorless and tasteless but is very toxic. If your Smith boiler is not w orking proper ly , or is not vented properly , dangerous levels of CO ma y accumulate. CO is lighter ...

Fabricant Smith Cast Iron Boilers Catégorie Boiler

Les documents que nous recevons du fabricant de l'appareilSmith Cast Iron Boilers GB200 SERIES peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques Smith Cast Iron Boilers
- manuels d’utilisations GB200 SERIES
- fiches produit Smith Cast Iron Boilers
- dépliants
- ou étiquettes-énergie Smith Cast Iron Boilers GB200 SERIES
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation Smith Cast Iron Boilers GB200 SERIES.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation Smith Cast Iron Boilers GB200 SERIES, manuels d’entretien, brefs manuels ou manuels de l’utilisateur Smith Cast Iron Boilers GB200 SERIES. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit Smith Cast Iron Boilers GB200 SERIES.

Manuel d’utilisation complet de l’appareil Smith Cast Iron Boilers GB200 SERIES, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser Smith Cast Iron Boilers GB200 SERIES par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs Smith Cast Iron Boilers GB200 SERIES.

Le manuel d’utilisation complet Smith Cast Iron Boilers, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel Smith Cast Iron Boilers GB200 SERIES - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières Smith Cast Iron Boilers GB200 SERIES, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lSmith Cast Iron Boilers GB200 SERIES qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil Smith Cast Iron Boilers GB200 SERIES - qui devraient nous aider dans les premières étapes lors de l'utilisation Smith Cast Iron Boilers GB200 SERIES
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de Smith Cast Iron Boilers GB200 SERIES
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service Smith Cast Iron Boilers GB200 SERIES dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de Smith Cast Iron Boilers GB200 SERIES?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec Smith Cast Iron Boilers GB200 SERIES, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec Smith Cast Iron Boilers GB200 SERIES il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)