    Heat Controller , Inc. • 1900 Wellworth A ve. • Jackson, MI 49203 • (517)787-2100 • www .heatcontroller .com ENGINEERING DESIGN GUIDE Commercial Horizontal & V ertical Packaged W ater-Source Heat Pumps: HBH/V Compact ...

  • Heat Controller HBH/V - page 2

    Engineering Design Guide HBH/V SERIES Heat Contr oller , Inc. T able of Contents Unit Features ........................................................................................................................................ 2 Selection Procedure ................................................................................................ ...

  • Heat Controller HBH/V - page 3

    Heat Contr oller , Inc. HBH/V SERIES Engineering Design Guide HB Series The HBH/V Series exceeds ASHRAE 90.1 efciencies, and uses R-410A zero ozone depletion refrigerant, making it an extremely environmentally-friendly option. HBH/V is eligible for additional LEED™ (Leadership in Energy and Environmental Design) points because of the “green? ...

  • Heat Controller HBH/V - page 4

    Engineering Design Guide HBH/V SERIES Heat Contr oller , Inc. T o conver t Inch-Pound (English) to SI (Metric) Air Flow Correction T able 400 CFM per ton of cooling capacity is nominal rated airflow for all models (bold print) Use multipliers directly with unit data for correcting unit performance at other airflows than nominal Entering Air Correct ...

  • Heat Controller HBH/V - page 5

    Heat Contr oller , Inc. HBH/V SERIES Engineering Design Guide Selection Procedure Step 1 Determine the actual heating and cooling loads at the desired dry bulb and wet bulb conditions. Step 2 Obtain the following design parameters: Entering water temperature, water ow rate in GPM, air ow in CFM, water ow pressure drop and design wet and dr ...

  • Heat Controller HBH/V - page 6

    Engineering Design Guide HBH/V SERIES Heat Contr oller , Inc. 7 May , 2009 Page 10 HEA T CONTROLLER OEM PRICE LIST HBH & HBV Model Structure HBH & HBV COMP ACT Horizontal & V ertical HFC-410a Units The basic unit price includes sealed heat pump refrigerant cir cuit and air handler within cabinetry ,  lter , and a factory installed ha ...

  • Heat Controller HBH/V - page 7

    Heat Contr oller , Inc. HBH/V SERIES Engineering Design Guide Performance Data ARI/ASHRAE/ISO 13256-1 ASHRAE/ARI/ISO 13256-1. English (IP) Units ASHRAE/ARI/ISO 13256-1. Metric (SI) Units Model W ater Loop Heat Pump Ground W ater Heat Pump Ground Loop Heat Pump Cooling 30°C Heating 20°C Cooling 15°C Heating 10°C Cooling 25°C Heating 0°C Capaci ...

  • Heat Controller HBH/V - page 8

    20 7.0 4.5 10.3 0 0 0 0 0 0 0 710 1 1.6 1.05 8.2 85.1 3.25 20 7.0 4.5 10.3 0 0 0 0 0 0 0 825 11.7 1.02 8.4 83.2 3.38 30 3.5 1.2 2.8 620 22.2 14.0 0.63 0.58 24.1 38.3 710 13.6 1.09 10.1 87.8 3.66 30 3.5 1.2 2.8 725 22.5 14.7 0.65 0.59 24.4 38.3 825 13.8 1.06 10.3 85.5 3.81 30 5.8 2.9 6.6 620 22.4 14.0 0.63 0.57 24.3 39.2 710 14.2 1.09 10.7 88.5 3.81 ...

  • Heat Controller HBH/V - page 9

    Heat Contr oller , Inc. HBH/V SERIES Engineering Design Guide Performance capacities shown in thousands of Btuh 220 CFM Nominal (Rated) Airow Interpolation is permissible; extrapolation is not. All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. ARI/ISO certied conditions are 80.6°F DB and 66.2°F WB in ...

  • Heat Controller HBH/V - page 10

    Engineering Design Guide HBH/V SERIES Heat Contr oller , Inc. Performance capacities shown in thousands of Btuh 325 CFM Nominal (Rated) Airow Interpolation is permissible; extrapolation is not. All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. ARI/ISO certied conditions are 80.6°F DB and 66.2°F WB in ...

  • Heat Controller HBH/V - page 11

    Heat Contr oller , Inc. HBH/V SERIES Engineering Design Guide Performance Data HBH/V 012 Performance capacities shown in thousands of Btuh 400 CFM Nominal (Rated) Airow Interpolation is permissible; extrapolation is not. All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. ARI/ISO certied conditions are 8 ...

  • Heat Controller HBH/V - page 12

    Engineering Design Guide HBH/V SERIES Heat Contr oller , Inc. Performance Data HBH/V 015 Performance capacities shown in thousands of Btuh 525 CFM Nominal (Rated) Airow Interpolation is permissible; extrapolation is not. All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. ARI/ISO certied conditions are 8 ...

  • Heat Controller HBH/V - page 13

    Heat Contr oller , Inc. HBH/V SERIES Engineering Design Guide Performance Data HBH/V 018 Interpolation is permissible; extrapolation is not. All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. ARI/ISO certied conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating. T able does not ree ...

  • Heat Controller HBH/V - page 14

    Engineering Design Guide HBH/V SERIES Heat Contr oller , Inc. Performance Data HBH/V 024 Performance capacities shown in thousands of Btuh Interpolation is permissible; extrapolation is not. All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. ARI/ISO certied conditions are 80.6°F DB and 66.2°F WB in cooli ...

  • Heat Controller HBH/V - page 15

    Heat Contr oller , Inc. HBH/V SERIES Engineering Design Guide Performance Data HBH/V 030 Performance capacities shown in thousands of Btuh Interpolation is permissible; extrapolation is not. All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. ARI/ISO certied conditions are 80.6°F DB and 66.2°F WB in cooli ...

  • Heat Controller HBH/V - page 16

    Engineering Design Guide HBH/V SERIES Heat Contr oller , Inc. Performance Data HBH/V 036 Performance capacities shown in thousands of Btuh Interpolation is permissible; extrapolation is not. All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. ARI/ISO certied conditions are 80.6°F DB and 66.2°F WB in cooli ...

  • Heat Controller HBH/V - page 17

    Heat Contr oller , Inc. HBH/V SERIES Engineering Design Guide Performance Data HBH/V 042 Performance capacities shown in thousands of Btuh Interpolation is permissible; extrapolation is not. All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. ARI/ISO certied conditions are 80.6°F DB and 66.2°F WB in cooli ...

  • Heat Controller HBH/V - page 18

    Engineering Design Guide HBH/V SERIES Heat Contr oller , Inc. Performance Data HBH/V 048 Performance capacities shown in thousands of Btuh Interpolation is permissible; extrapolation is not. All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. ARI/ISO certied conditions are 80.6°F DB and 66.2°F WB in cooli ...

  • Heat Controller HBH/V - page 19

    Heat Contr oller , Inc. HBH/V SERIES Engineering Design Guide Performance Data HBH/V 060 Performance capacities shown in thousands of Btuh Interpolation is permissible; extrapolation is not. All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. ARI/ISO certied conditions are 80.6°F DB and 66.2°F WB in cooli ...

  • Heat Controller HBH/V - page 20

    Engineering Design Guide HBH/V SERIES Heat Contr oller , Inc. Air Flow Correction T able Air Flow Correction T able Cooling Corrections Ent Air WB º F T otal Clg Cap Sens Clg Cap Multipliers - Entering DB º F Power Heat of Rej 65 70 75 80 80.6 85 90 95 50 0.7800 0.9778 * * * * * * * 0.9972 0.8243 55 0.8327 0.8966 1.0556 * * * * * * 0.9980 0.8667 ...

  • Heat Controller HBH/V - page 21

    Heat Contr oller , Inc. HBH/V SERIES Engineering Design Guide Antifreeze Correction T able Antifreeze T ype Antifreeze % Cooling Heating WPD Corr . Fct. EWT 30°F EWT 90°F EWT 30°F T otal Cap Sens Cap Power Htg Cap Power W ater 0 1.000 1.000 1.000 1.000 1.000 1.000 Propylene Glycol 5 0.995 0.995 1.003 0.989 0.997 1.070 15 0.986 0.986 1.009 0.968 ...

  • Heat Controller HBH/V - page 22

    Engineering Design Guide HBH/V SERIES Heat Contr oller , Inc. Blower Performance Data Standard Unit Airow in CFM with wet coil and clean air lter Model Fan Speed Rated Airow Min CFM Airow (cfm) at External Static Pressure (in. wg) 0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.60 0.70 0.80 0.90 1.00 HBH/V 006 HI 220 150 310 30 ...

  • Heat Controller HBH/V - page 23

    Heat Contr oller , Inc. HBH/V SERIES Engineering Design Guide Model Fan Speed Rated Airow Min CFM Airow (cfm) at External Static Pressure (in. wg) 0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.60 0.70 0.80 0.90 1.00 HBH/V 015 HS HI 525 375 774 764 755 745 735 715 696 676 637 519 HS MED 735 725 706 696 686 676 657 657 647 637 617 58 ...

  • Heat Controller HBH/V - page 24

    Engineering Design Guide HBH/V SERIES Heat Contr oller , Inc. Physical Data HB Series 006 009 012 015 018 024 030 036 042 048 060 Compressor (1 Each) Rotary Scroll Factory Charge R410A (oz) 17 18.5 23 32 43 43 47 50 70 74 82 PSC Fan Motor & Blower Fan Motor T ype/Speeds PSC/3 PSC/3 PSC-3 PSC/3 PSC/3 PSC/3 PSC/3 PSC/3 PSC/3 PSC/3 PSC/3 Fan Motor ...

  • Heat Controller HBH/V - page 25

    Heat Contr oller , Inc. HBH/V SERIES Engineering Design Guide HB - Horizontal Dimensional Data Horizontal Model Overall Cabinet A Width B Length C Height 006 - 012 in cm 19.1 48.5 34.1 86.6 1 1.1 28.2 015 - 018 in cm 20.1 51.1 43.1 109.5 17.0 43.2 024 - 030 in cm 20.1 51.1 43.1 109.5 18.3 46.5 036 - 042 in cm 20.1 51.1 47.1 1 19.6 21.0 53.3 048 - 0 ...

  • Heat Controller HBH/V - page 26

    Engineering Design Guide HBH/V SERIES Heat Contr oller , Inc. HB - Horizontal Dimensional Data F Right Return Straight Discharge Front L N O M Right Return Front Straight Discharge CSP Back Discharge Condensate 3 / 4" IPT 3.3" [83.8mm] 0.7" [17.8mm] Front-View E D K J 2 1 1.1 [27.9mm] A CAP BSP Right Return Right View - Air Coil Open ...

  • Heat Controller HBH/V - page 27

    Heat Contr oller , Inc. HBH/V SERIES Engineering Design Guide HB - V ertical Upow Dimensional Data Notes: 1. While clear access to all removable panels is not required, installer should take care to comply with all building codes and allow adequate clearance for future eld service. 2. Front & Side access is preferred for service access. H ...

  • Heat Controller HBH/V - page 28

    Engineering Design Guide HBH/V SERIES Heat Contr oller , Inc. HB - V ertical Upow Dimensional Data Access Panels T op View-Left Return U R S Isometric View Left Return Left View - Air Coil Opening T C Power Supply 3/4" [19.1 mm] HV Knockout Low V oltage 1/2" [12.7 mm] L V Knockout Low V oltage 1/2" [12.7 mm] L V Knockout Condensat ...

  • Heat Controller HBH/V - page 29

    Heat Contr oller , Inc. HBH/V SERIES Engineering Design Guide Corner Weights for HBH Series Units Model T otal Left-Front* Right-Front* Left-Back* Right-Back* HBH006 Lbs 103 37 24 23 19 kg 46.72 16.78 10.89 10.43 8.62 HBH009 Lbs 105 38 24 23 20 kg 47.63 17.24 10.89 10.43 9.07 HBH012 Lbs 1 14 42 26 25 21 kg 51.71 19.05 1 1.79 1 1.34 9.53 HBH015 Lbs ...

  • Heat Controller HBH/V - page 30

    Engineering Design Guide HBH/V SERIES Heat Contr oller , Inc. Electrical Data - Standard Unit HB Model V oltage Code Rated V oltage V oltage Min/ Max Compressor Fan Motor FLA T otal Unit FLA Min Circuit Amp Max Fuse/ HACR QTY RLA LRA 006 1 208-230/60/1 197/254 1 3.3 17.7 0.40 3.7 4.5 15 009 1 208-230/60/1 197/254 1 5.6 22.2 0.80 6.4 7.8 15 012 1 20 ...

  • Heat Controller HBH/V - page 31

    Heat Contr oller , Inc. HBH/V SERIES Engineering Design Guide Electrical Data High Static Blower HB Model V oltage Code Rated V oltage V oltage Min/ Max Compressor Fan Motor FLA T otal Unit FLA Min Circuit Amp Max Fuse/ HACR QTY RLA LRA 015 1 208-230/60/1 197/254 1 6.0 29.0 1.00 7.0 8.5 15 8 265/60/1 239/292 1 5.4 28.0 0.86 6.3 7.6 15 018 1 208-230 ...

  • Heat Controller HBH/V - page 32

    Engineering Design Guide HBH/V SERIES Heat Contr oller , Inc. T ypical Wiring Diagram Single Phase HB Units With CXM Controller 31 ...

  • Heat Controller HBH/V - page 33

    Heat Contr oller , Inc. HBH/V SERIES Engineering Design Guide T ypical Wiring Diagram Three Phase 208/230V HB Units With CXM Controller 32 ...

  • Heat Controller HBH/V - page 34

    Engineering Design Guide HBH/V SERIES Heat Contr oller , Inc. T ypical Wiring Diagram Three Phase 460/575V HB Units With CXM Controller 33 ...

  • Heat Controller HBH/V - page 35

    04/2009 1 1/2010 ...

Fabricant Heat Controller Catégorie Heat Pump

Les documents que nous recevons du fabricant de l'appareilHeat Controller HBH/V peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques Heat Controller
- manuels d’utilisations HBH/V
- fiches produit Heat Controller
- dépliants
- ou étiquettes-énergie Heat Controller HBH/V
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation Heat Controller HBH/V.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation Heat Controller HBH/V, manuels d’entretien, brefs manuels ou manuels de l’utilisateur Heat Controller HBH/V. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit Heat Controller HBH/V.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil Heat Controller HBH/V, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser Heat Controller HBH/V par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs Heat Controller HBH/V.

Le manuel d’utilisation complet Heat Controller, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel Heat Controller HBH/V - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières Heat Controller HBH/V, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lHeat Controller HBH/V qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil Heat Controller HBH/V - qui devraient nous aider dans les premières étapes lors de l'utilisation Heat Controller HBH/V
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de Heat Controller HBH/V
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service Heat Controller HBH/V dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de Heat Controller HBH/V?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec Heat Controller HBH/V, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec Heat Controller HBH/V il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)