Manuel d’utilisation SPX Cooling Technologies 1000

32 pages 1.58 mb
Télécharger

Aller à la page of 32

Summary
  • SPX Cooling Technologies 1000 - page 1

    / Mar le y Sigma 1 0 00/120 0 Cooling T ower / Engineer ing Data & Specifications ...

  • SPX Cooling Technologies 1000 - page 2

    Mar ley / Sigma 1 00 0/120 0 Cooling T ower / T able of Contents Engineer ing Data 1 0 0 0 S c hematic 4 1 0 0 0 Piping 5 1 0 0 0 Suppor t 6 1200 Sc hematic 8 1200 Piping 9 1200 Support 1 0 Energy Management 12 Environmental 13 Specifications / Base Base 1 4 Thermal P erformance 15 Construction 16 Fan Dec k and F an Cylinder 17 Mec hanical Equipmen ...

  • SPX Cooling Technologies 1000 - page 3

    Mar ley / Sigma 1 0 00/120 0 Cooling T ower / 3 S igma 1000/1200 towers are field-erected, general purpose crossflow wood cooling towers, designed to serve normal air conditioning and refrigeration systems as well as medium sized industrial loads. They evolve from the crossflow concept of towers pioneered by Marley in 1938, and incorporate over ...

  • SPX Cooling Technologies 1000 - page 4

    Mar ley / Sigma 1 0 00 Cooling T ower / Engineer ing Data : Schematic 4 B H TOP OF FAN CYLINDER BASE OF TOWER COLUMNS TOP OF FAN DECK W OUT TO OUT OF T OWER 5" C L COL. A BA YS @ 4'-0 = L C L COL. C L COL. 5" C DIA. FA N PLAN ENdw ALL ELEv A tioN NotE 1 Last number of model indicates number of cells. Change as appropriate for y our s ...

  • SPX Cooling Technologies 1000 - page 5

    Mar ley / Sigma 1 0 00 Cooling T ower / Engineer ing Data : Piping 5 F MINIMUM C L INLET C L COL. C C L INLET D TYP . MUL TI-CELL PIPING SHOWN WITH DASHED LINES IS BY OTHERS E F ACE OF A DIA. INLET PIPING C L TOWER F AN C L TOWER F AN B DIA. FLOW CONTROL VA LV E AND CROSS OVER PIPING PLAN G BASE OF TO WER COLUMNS C L INLET ENdw ALL ELEv A tioN NotE ...

  • SPX Cooling Technologies 1000 - page 6

    Mar ley / Sigma 1 0 00 Cooling T ower / Engineer ing Data : Support 6 W OVERALL WIDTH OF BASIN C BA YS @ 4'-0 = L EACH ADDITIONAL CELL = L 7 1/2 " 7 1/2 " AIR INLET F ACE 11 1/2 " A C L C L OVERALL LENGTH OF BASIN C L C L B A B C L TOWER C L C L AIR INLET F ACE ENDW ALL F ACE ENDW ALL F ACE OVERFLOW SUMP ADDITIONAL SUMP WHEN REQ ...

  • SPX Cooling Technologies 1000 - page 7

    Mar ley / Sigma 1 0 00 Cooling T ower / Engineer ing Data : Concret e Basin 7 NotE 1 Use this bulletin for preliminary layouts only . Do not use for construction. Obtain current dra wings from your Marley sales representative. Concrete basin design and construction are b y other contractors or purc haser . 2 Operating weight is total wet operating ...

  • SPX Cooling Technologies 1000 - page 8

    Mar ley / Sigma 120 0 Cooling T ower / Engineer ing Data : Schematic 8 NotE 1 Last number of model indicates number of cells. Change as appropriate for y our selection. Primar y engineering data is per cell. 2 Fan hp is usually less than sho wn here. 3 Height shown is from base of to wer columns to fan dec k. W ood basin, if used, elev ates tower 6 ...

  • SPX Cooling Technologies 1000 - page 9

    Mar ley / Sigma 120 0 Cooling T ower / Engineer ing Data : Piping 9 NotE 1 Use this bulletin for preliminary layouts only . Obtain current drawings from y our Marley sales representative. 2 Pumping head contributed b y the tower is static lif t shown on page 9. A ctual pumping head will vary according to tower circulating GPM. T otal pumping head w ...

  • SPX Cooling Technologies 1000 - page 10

    Mar ley / Sigma 120 0 Cooling T ower / Engineer ing Data : Support 10 NotE 1 Use this bulletin for preliminary layouts only . All dimensions show anc hor bolt locations. Obt ain current drawings from y our Marley sales representative before designing supports. 2 Note carefully anc hor bolt location relative to beam orientation. See plan abov e. 3 O ...

  • SPX Cooling Technologies 1000 - page 11

    Mar ley / Sigma 120 0 Cooling T ower / Engineer ing Data : Concret e Basin 11 NotE 1 Use this bulletin for preliminary layouts only . Do not use for construction. Obtain current dra wings from your Marley sales representative. Concrete basin design and construction are b y other contractors or purc haser . 2 Operating weight is total wet operating ...

  • SPX Cooling Technologies 1000 - page 12

    Mar ley / Sigma 1 0 00/120 0 Cooling T ower / Engineer ing D ata: Energ y Management 12 Cooling tow ers are usually selected to produce a specific cold water temperat ure at the higher summer -time wet-bulb temperatures. During the remainder of the y ear , the cooling tow er is capable of producing much colder w ater . Unless your system will bene ...

  • SPX Cooling Technologies 1000 - page 13

    Mar ley / Sigma 1 0 00/120 0 Cooling T ower / Engineer ing D ata: Envir onmental 13 Enclosur es Occasionally , cooling towers are located inside arc hitectural enclosures for aesthetic reasons. Although Sigma towers adapt well to enclosures, a poorly designed enclosure can impair proper operation. An ef fectiv e design includes gener - ous air inle ...

  • SPX Cooling Technologies 1000 - page 14

    Specifications Specification V alue Mar ley / Sigma 1 0 00/120 0 Cooling T ower / Specifications: Base 14 1.0 Base: 1.1 F urnish and inst all an induced-draf t, crossflow -type, field-erected, wood- framed, PVC fill, industrial-dut y cooling tow er of _____ cell(s), as sho wn on Plans. The limiting ov erall dimensions of the tower shall be _____ ...

  • SPX Cooling Technologies 1000 - page 15

    Specifications Specification V alue Mar ley / Sigma 1 0 00/120 0 Cooling T ower / Specifications: Base 15 2.0 Ther mal P erfor mance: 2.1 The tow er shall be capable of cooling _____ GPM of water from ____ °F to _____ °F at a design entering air wet- bulb temperature of _____ °F . The cool- ing tower manufacturer shall guarantee that the tower s ...

  • SPX Cooling Technologies 1000 - page 16

    Specifications Specification V alue Mar ley / Sigma 1 0 00/120 0 Cooling T ower / Specifications: Base 16 3.0 Constr uction: 3.1 The tow er shall be capable of with- standing water having a pH of 6.5 to 8.0; a c hloride content (NaCl) up to 750 ppm; a sulfate content (SO 4 ) up to 1 20 0 ppm; a sodium bicarbonate con- tent (NaHCO 3 ) up to 20 0 ppm ...

  • SPX Cooling Technologies 1000 - page 17

    Specifications Specification V alue Mar ley / Sigma 1 0 00/120 0 Cooling T ower / Specifications: Base 17 4.0 F an Deck and F an Cylinder: 4.1 The fan dec k shall act as a working platform for maintenance personnel. It shall be fabricated of no less than 1" thick, 7 ply , exterior grade, treated Douglas Fir plywood, and shall be designed for a ...

  • SPX Cooling Technologies 1000 - page 18

    Specifications Specification V alue Mar ley / Sigma 1 0 00/120 0 Cooling T ower / Specifications: Base 18 5.0 Mechanical Equipment: 5.1 Fan(s) shall be propeller -t ype, incorpo- rating heavy dut y blades of cast alumi- num or high strength, inert composite material. Blades shall be individually adjustable and replaceable. Fan(s) shall be driven th ...

  • SPX Cooling Technologies 1000 - page 19

    Specifications Specification V alue Mar ley / Sigma 1 0 00/120 0 Cooling T ower / Specifications: Base 19 6.0 Fill, Louv ers and Drif t Eliminators: 6.1 Fill shall be film-type, 1 5 mil thick, thermoformed PV C, with louvers formed as part of eac h fill sheet. Fill shall be suspended from st ainless steel structural tubing supported from the uppe ...

  • SPX Cooling Technologies 1000 - page 20

    Specifications Specification V alue Mar ley / Sigma 1 0 00/120 0 Cooling T ower / Specifications: Base 20 7.0 Hot W ater Distr ibution System: 7.1 The mec hanical equipment support/ crossov er pipe shall deliver water to two open hot water basins per cell at the fan deck elev ation. W ater shall exit these basins to the fill by gravity through met ...

  • SPX Cooling Technologies 1000 - page 21

    Specifications Specification V alue Mar ley / Sigma 1 0 00/120 0 Cooling T ower / Specifications: Base 21 9.3 Eac h endwall of the tower shall be equipped with a 20" wide aluminum vertical ladder , through-bolted to the endwall struct ure. Ladder shall rise from the cold water basin lev el to the top of the fan dec k guardrail, and shall be de ...

  • SPX Cooling Technologies 1000 - page 22

    Specifications Mar ley / Sigma 1 0 00/120 0 Cooling T ower / Specifications: Options 22 Specification V alue Control Options Control Syst em: 5.7 Add the following paragraph in the Mechanical Equipment section: Eac h cell of the cooling tower shall be equipped with a UL listed control system in a NEMA 3R or 4X outdoor enclosure capable of controlli ...

  • SPX Cooling Technologies 1000 - page 23

    Specifications Mar ley / Sigma 1 0 00/120 0 Cooling T ower / Specifications: Options 23 Specification V alue Basin Heater: 10.2 Add the following paragraph in the Cold W ater Basin section: Provide a system of electric immersion heat- ers and controls for eac h cell of the tow er to prev ent freezing of water in the collection basin during periods ...

  • SPX Cooling Technologies 1000 - page 24

    Specifications Mar ley / Sigma 1 0 00/120 0 Cooling T ower / Specifications: Options 24 Specification V alue to modulate fan speed maintaining set point temperature. The drive's panel dis- play shall be able to display the set-point temperature and cold-fluid temperature on t wo separate lines. The bypass shall include a complete magnetic byp ...

  • SPX Cooling Technologies 1000 - page 25

    Specifications Mar ley / Sigma 1 0 00/120 0 Cooling T ower / Specifications: Options 25 Specification V alue set point shall be displayed on the door of the control panel. The bypass shall include a complete magnetic bypass circuit with capabilit y to isolate the VFD when in the bypass mode. T ransf er to the bypass mode shall be automatic in the e ...

  • SPX Cooling Technologies 1000 - page 26

    Specifications Mar ley / Sigma 1 0 00/120 0 Cooling T ower / Specifications: Options 26 Specification V alue Conv enience and Saf ety Options Stairwa y: 9.3 Replace paragraph 9.3 with the fol- lowing: A 30" wide, column supported, 45° st air way with 8" rise and r un of treated Douglas Fir shall be provided at the tower endwall rising fr ...

  • SPX Cooling Technologies 1000 - page 27

    Specifications Mar ley / Sigma 1 0 00/120 0 Cooling T ower / Specifications: Options 27 Specification V alue Oil Level Sight Glass: 5.4 Replace paragraph 5.4 with the fol- lowing: A galv anized oil gauge and drain line shall extend from the gear reducer to the vicinity of the motor , and shall be equipped with a bronze- bodied oil level sight glass ...

  • SPX Cooling Technologies 1000 - page 28

    Specifications Mar ley / Sigma 1 0 00/120 0 Cooling T ower / Specifications: Options 28 Specification V alue Low Noise T ow er: 1.1 Add the following at the end of this paragraph: The cooling tow er shall be quiet operating , and shall produce an ov erall level of sound no higher than ____ dBA at the critical location indicated on the Plans. ■ So ...

  • SPX Cooling Technologies 1000 - page 29

    Specifications Mar ley / Sigma 1 0 00/120 0 Cooling T ower / Specifications: Options 29 Specification V alue W ater tight Par titions Between Cells: 3.5 Replace the last sentence in this paragraph with the following: P artitions shall be 3/4" x 5-ply , factor y- fabricated, groov ed and splined treated Douglas Fir plywood sheets, installed and ...

  • SPX Cooling Technologies 1000 - page 30

    ...

  • SPX Cooling Technologies 1000 - page 31

    ...

  • SPX Cooling Technologies 1000 - page 32

    7 4 01 WEST 1 29 STRE ET OVER LAN D P AR K, KANSAS 6 621 3 U N ITE D ST A TES 913 6 64 7 400 spxcooling@spx.com spxcooling.com In the interest of techno logical progr ess, all products are subject to design and/or material change without notice. ©2008 SPX Cooling T ech nologies, Inc. Printed in USA | SIG-T S -08A ...

Fabricant SPX Cooling Technologies Catégorie Humidifier

Les documents que nous recevons du fabricant de l'appareilSPX Cooling Technologies 1000 peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques SPX Cooling Technologies
- manuels d’utilisations 1000
- fiches produit SPX Cooling Technologies
- dépliants
- ou étiquettes-énergie SPX Cooling Technologies 1000
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation SPX Cooling Technologies 1000.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation SPX Cooling Technologies 1000, manuels d’entretien, brefs manuels ou manuels de l’utilisateur SPX Cooling Technologies 1000. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit SPX Cooling Technologies 1000.

Manuel d’utilisation complet de l’appareil SPX Cooling Technologies 1000, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser SPX Cooling Technologies 1000 par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs SPX Cooling Technologies 1000.

Le manuel d’utilisation complet SPX Cooling Technologies, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel SPX Cooling Technologies 1000 - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières SPX Cooling Technologies 1000, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lSPX Cooling Technologies 1000 qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil SPX Cooling Technologies 1000 - qui devraient nous aider dans les premières étapes lors de l'utilisation SPX Cooling Technologies 1000
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de SPX Cooling Technologies 1000
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service SPX Cooling Technologies 1000 dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de SPX Cooling Technologies 1000?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec SPX Cooling Technologies 1000, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec SPX Cooling Technologies 1000 il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)