Summary
  • Siemens 350 - page 1

    1 SINVERT 350, SINVERT 420 and SINVERT 500 TL Operating Manual – 11/2009 SINVERT Answers for environment. ...

  • Siemens 350 - page 2

    Photovoltaic SINVERT SINVERT 350, SINVERT 420 and SINVERT 500 TL Introduction 1 Description 2 Hardware operation 3 Alarm and fault messages 4 Support 5 ...

  • Siemens 350 - page 3

    Safety instructions These Operating Instructions contai n information which you shou ld o bserve to ensure y our own personal safety as well as to protect the pro duct and connect ed equipment. The notices ref erring to your personal safety are highlighted in the manual by a safety alert symbol. Notices ref erring only to equipment damag e have no ...

  • Siemens 350 - page 4

    Contents 1 Introduction ................................................................................................................... 6 1.1 About this documentation ........................................................................................ 6 1.1.1 Scope of validity ................................................................ ...

  • Siemens 350 - page 5

    Tables Table 3-1 Pin assignment X 5 (SUB -D 9-pin / RS422 for PP so lar) ........................................... 13 Table 4- 1 Alarm and fa ult m essa ges ................................................................................. 27 Table 4-2 I S O fau lt ................................................................................... ...

  • Siemens 350 - page 6

    Introducti on 1.1 About thi s documentation 6 1 Introduction 1.1 About this documentation This manual will provide you with guidance in the us e of SINVERT PV inverters. It provides you with a detailed overview of all the information you n eed to know about SINVERT PV inverters. We have checked that the contents of this document correspond to t he ...

  • Siemens 350 - page 7

    Introduction 1.1 About thi s documentation 7 and their master-slave variants: • SINVERT 700 MS (two SINVERT 350 inverters in parallel) • SINVERT 1000 MS (three SINVERT 350 inverters in parallel) • SINVERT 1400 MS (four SINVERT 350 inverters in parallel) • SINVERT 850 MS (two SINVERT 420 inverters in parallel) • SINVERT 1300 MS (three SINV ...

  • Siemens 350 - page 8

    Description 2.1 Application 8 2 Description 2.1 Application The SINVERT PV inverter is a fully assembled, ready-to-connect inverter unit for PV installations. Figure 2-1 Overview of PV system The inverter transforms the DC voltage produced by the PV modules into an AC voltage. The AC output voltage is transformed to the gr id voltage by a medium-vo ...

  • Siemens 350 - page 9

    Hardware operation 3.1 Commissi oning the inverter 9 3 Hardware operation 3.1 Commissioning the inverter Commissioning an installation requires certain switching opera tions to be performed. This type of work must always be undertaken by qualified, properly trained personnel. Failure to perform switching operations correctly can result in significa ...

  • Siemens 350 - page 10

    Hardware operation 3.1 Commissi oning the inverter 10 3.1.2 Switching off and disconnecting the power supply The entire system must be disconnected from the power supply before test and maintenance work can be carried out in the containers. Carry out these tasks in the sequence given below: 1. Press the OFF key briefly on the control panel of every ...

  • Siemens 350 - page 11

    Hardware operation 3.1 Commissi oning the inverter 11 3.1.3 Switching on The inverter is switched on in the same way as it is switched off, but in th e reverse sequence. 1. Check that all connections have been made correctly (including polarity). 2. Switch on the junction boxes in the PV field. 3. Switch on the external power supply for the medium- ...

  • Siemens 350 - page 12

    Hardware operation 3.2 Operating the inverter 12 3.2 Operating the inverter 3.2.1 Operator panel Figure 3-1 Front view of control panel Grid LED indicator bar Status display Fault display Display Service interface (RS 232) Keyswitch (operating mode) OFF key 2 1 3 4 5 6 7 ...

  • Siemens 350 - page 13

    Hardware operation 3.2 Operating the inverter 13 Figure 3-2 Front view of control panel Table 3-1 Pin assignment X5 (SUB-D 9-pin/ RS422 for PPsola r) Pin Signal 1 RRS485P 5 TRS485N 6 TRS485P 9 RRS485N ...

  • Siemens 350 - page 14

    Hardware operation 3.2 Operating the inverter 14 3.2.2 Operating mode You can choose between modes "Automatic" and "Test". In Test mode, you can adjust the DC voltage manually. In Automatic mode, the inverter determines the Maximum Power Point (MPP) automatically. It also displays currently active fault messages. To select Test ...

  • Siemens 350 - page 15

    Hardware operation 3.2 Operating the inverter 15 3.2.5 Fault reset You can reset a fault by turning the keyswitch from "AUTO" to "TEST" and back to "AUTO" or vice versa. If the inverter has been disabled due to a fault, it can now be activated again. 3.2.6 Displaying currently active alarms and faults In Automatic mode ...

  • Siemens 350 - page 16

    Hardware operation 3.2 Operating the inverter 16 Maximum Power Point (LED "MPP") The power which can be generated by a PV system depends on the level of insolation and the temperature of the PV modules. The inverter control unit is equipped with a "Tracker" which automatically tracks the MPP (Maximum Power Point) of the PV field ...

  • Siemens 350 - page 17

    Hardware operation 3.3 Communi cation with the invert er 17 3.3 Communication with the inverter Various possible methods of communicating with the inverter are presented below. 3.3.1 WEB’log WEB’log is generally used to log inverter data, i’checker data and meteorological data which has been recorded while the inverter is in operation. This d ...

  • Siemens 350 - page 18

    Hardware operation 3.3 Communicati on with the inverter 18 Gray: No information available about the system components Blue: System components are ready; no energy flowing Green: System components are running; energy is flowing Red: System components are malfunctioning Figure 3-5 System Diagram PPsolar The System Diagram contains the electrical data ...

  • Siemens 350 - page 19

    Hardware operation 3.3 Communi cation with the invert er 19 The Control Panel (Figure 3-6) contains the same display and control elements as the control panel of the SINVERT PV inverter. Figure 3-6 Control Panel PPsola r ...

  • Siemens 350 - page 20

    Hardware operation 3.3 Communicati on with the inverter 20 The Oscilloscope function (Figure 3-7) enables you to record data in two channels and to print output voltages, output currents, inverter currents and the PV generator voltage. The right to use this special function is reserved for Siemens customer service personnel. The trigger control fun ...

  • Siemens 350 - page 21

    Hardware operation 3.3 Communi cation with the invert er 21 The Process Data window (Figure 3-8) displays information about the inverter. For the sake of better clarity, the window is divided into a number of panes. You can specify the number of panes and their content in a configuration file. In the default configuration, the content of t he indiv ...

  • Siemens 350 - page 22

    Hardware operation 3.3 Communicati on with the inverter 22 Actual Value Summary The window with the overview of actual values displays a summary of key data of the PV system. You can alter data (e.g. reactive power transfer from SINVERT to the three-phase AC grid) in this window when it is active. Actual values The Actual Values window displays all ...

  • Siemens 350 - page 23

    Hardware operation 3.3 Communi cation with the invert er 23 The Data Storage window (Figure 3-9) is used to start, stop and configure the data archiving function of the PowerProtect solar system. The data to be archived, the scan rate, the data length and archiving path are specified in this window. The scan rate (t scan > xxs) and the data leng ...

  • Siemens 350 - page 24

    Hardware operation 3.3 Communicati on with the inverter 24 Energy The Energy window displays all the available energy data of the PV system. Check the boxes for the values that you want PowerProtect solar to archive. You can select the following data (* provided the relevant sensors are installed in the PV system): • Energy - day • Energy - mon ...

  • Siemens 350 - page 25

    Hardware operation 3.3 Communi cation with the invert er 25 The Analysis window (Figure 3-10) displays the data archived by PowerProtect solar. The data are saved in Microsoft Access database format by the data storage function. You can access this information at any time, even while the archiving function is active. The A nalysis window also provi ...

  • Siemens 350 - page 26

    Alarm and fault messages 4.1 Fault handling 26 4 Alarm and fault messages 4.1 Fault handling 4.1.1 Fault types There are two different types of fault, i.e. plant faults and operational faults. Plant faults are cau sed by malfunctioning of an inverter component, while operational faults occur as a result of unexpected external influences or logical ...

  • Siemens 350 - page 27

    Alarm and fault messages 4.2 Alarm and fault messages 27 4.2 Alarm and fault messages The table below provides an overview of alarm and fault messages supplied on the inverter. Table 4-1 Alarm and fault messages No. Meaning Category Main cause 0 Manual Off Fault 1 Inverter power unit is signaling overtemperature, stage 1 Alarm Ambient temperature t ...

  • Siemens 350 - page 28

    Alarm and fault messages 4.2 Alarm and fault messagesAlarm and fault messagesAlarm and fault messages 28 92 DC overvoltage protection has responded (or fuse (if insta lled) has tripped) Fault Overvoltage (lightni ng strike) has occurred 93 Fast Stop activated or overvoltage on medium-voltage transform er Fault Fast Stop button pressed, fault in coo ...

  • Siemens 350 - page 29

    Alarm and fault messages 4.2 Alarm and fault messages 29 4.2.1 Faults – Causes/diagnostics/remedial measures First acknowledge the fault with the keyswitch o n the control panel. Check the following if the inverter has not been in operation: • Polarity of the PV field input • Polarity of the DC link connection • AC phase sequence • AC vol ...

  • Siemens 350 - page 30

    Alarm and fault messages 4.2 Alarm and fault messages 30 Table 4-2 ISO fault ISO fault Damaged, worn-through cable s (loose, buffeted by wind) Cables damaged by animals Water in junction box Damaged insulation and ingre ss of water to cable duct Defective power unit Bending device defective Defect in PV module (damaged) Causes High air humidity (ca ...

  • Siemens 350 - page 31

    Alarm and fault messages 4.2 Alarm and fault messages 31 Table 4-3 Fault 0 (Alarm) General fault on transformer Condition The hardware contact in the power unit has tripp ed. Causes There is a defect in the inverter. Measures Replace the affected components. Replace the drive. Table 4-4 Faults 1 and 33 Message 1 (alarm): Inverter is signalin g over ...

  • Siemens 350 - page 32

    Alarm and fault messages 4.2 Alarm and fault messages 32 Causes Inlet air temperature too high o Air inlet to switchroom is blocked o Air outlet from switchr oom is restri cted o Ambient temperature is too high Replace the defective components Check the parameter settings Measures Clean or enlarge the air inl et Table 4-5 Faults 4 and 47 Fault 4 (a ...

  • Siemens 350 - page 33

    Alarm and fault messages 4.2 Alarm and fault messages 33 Table 4-9 Fault 36 (Alarm) AC contactor defective (no ch eckba ck), or Fast Stop button pressed Condition There is no signal at i nput 11/12 of the CU (green connector); transferred via Prof ibus to the S7; drive has received an ON command. No power supply for Fast OFF o Fast Stop button has ...

  • Siemens 350 - page 34

    Alarm and fault messages 4.2 Alarm and fault messages 34 Table 4-11 Fault 39 (Alarm) DC link overvoltage Condition The CU has detected a DC voltage in excess of the permissible value Causes The measured DC voltage is too high o The available DC voltage is too high ⇒ The PV field has been connected incorrectly (the voltage rises too sharply at hig ...

  • Siemens 350 - page 35

    Alarm and fault messages 4.2 Alarm and fault messages 35 Table 4-13 Fault 43 (Alarm) Vce monitor has respond ed Condition The CU has detected an inadmissible circuit voltage (voltage on semiconductor module between emitter and collector). Power unit is defective (variou s components could be the source of the problem) Transformer is defective Cause ...

  • Siemens 350 - page 36

    Alarm and fault messages 4.2 Alarm and fault messages 36 Table 4-16 Fault 63 (Alarm) Direct current too high Condition The CU / S7 has detected a direct current in excess of the set permissible limit Parameter setting error (S7 software) Parameter setting error ( CU software) Open circuit (detected by the S7 and i ndicated by this fault code) Cause ...

  • Siemens 350 - page 37

    Alarm and fault messages 4.2 Alarm and fault messages 37 Table 4-19 Fault 91 (Alarm) Fuse has trip ped Condition No power supply available for signali ng circuit A contact in the signaling circuit is open o A fuse has tripped o Fuse is not inserted, or not corre ctly inserted o Other contacts (AC cabi net, medium voltage) are open No power supply f ...

  • Siemens 350 - page 38

    Alarm and fault messages 4.2 Alarm and fault messages 38 Table 4-22 Fault 94 (Alarm) Profibus system h as failed Condition The S7 has detected serious erro rs on the Profibus Equalizing current on the Profibus ca ble shield The Profibus cable shield is not prope rly connected Terminating resistors are not correctly set No power supply available at ...

  • Siemens 350 - page 39

    Alarm and fault messages 4.2 Alarm and fault messages 39 Table 4-24 Fault 96 (Alarm) Grid voltage outside tolera nce Condition The CU has detected that the grid voltage is outside the set tolerance limits Grid voltage outside tolerance o No power supply o Unstable power supply o Medium-voltage breaker has tripp ed (if installed) o Control oscillati ...

  • Siemens 350 - page 40

    Alarm and fault messages 4.2 Alarm and fault messages 40 (Alarm) Symmetry fault Condition The S7 routine for monitoring symmetry has detecte d an imbalance Alarm in the PV field o Automatic fuse or fusible link in the junction box has tripped o Fuse at the DC input has tripped o PV module is defective o Defect in the PV field cabling Causes Alarm a ...

  • Siemens 350 - page 41

    Support 5.1 Contact addresses 41 5 Support 5.1 Contact addresses The support hotline for SINVERT can be reached via the contact methods listed b elow from Monday to Friday between 8 am and 5 pm CET: Phone: +49 911 750-2211 Fax: +49 911 750-2246 E-mail: sinvert-service.i-ia@siemens.com Internet: www.siemens.de/sinvert www.siemens.com/sinvert ...

  • Siemens 350 - page 42

    42 Siemens AG Indus try Sect or, I A SE S P V P.O. Box 2355 90766 Fuerth GERMANY Subject to change © Siemens AG 2009 www.siemens.com ...

Fabricant Siemens Catégorie Yard Vacuum

Les documents que nous recevons du fabricant de l'appareilSiemens 350 peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques Siemens
- manuels d’utilisations 350
- fiches produit Siemens
- dépliants
- ou étiquettes-énergie Siemens 350
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation Siemens 350.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation Siemens 350, manuels d’entretien, brefs manuels ou manuels de l’utilisateur Siemens 350. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit Siemens 350.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil Siemens 350, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser Siemens 350 par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs Siemens 350.

Le manuel d’utilisation complet Siemens, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel Siemens 350 - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières Siemens 350, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lSiemens 350 qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil Siemens 350 - qui devraient nous aider dans les premières étapes lors de l'utilisation Siemens 350
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de Siemens 350
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service Siemens 350 dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de Siemens 350?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec Siemens 350, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec Siemens 350 il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)