    English INST ALLA TION MANU AL For safe and correct use, read this manual and the indoor unit installation manual thoroughly before installing the air-conditioner unit. Air-Conditioners OUTDOOR UNIT PUMY-P·NHMU (-BS) FOR INSTALLER Español MANU AL DE INST ALA CIÓN Para un uso correcto y seguro, lea detalladamente este manual y el manual de instal ...

  • Mitsubishi Electronics R410A - page 2

    2 1.2. Bef ore installation (relocation) Caution: • Be extremely careful when transporting the units. T wo or more persons are needed to handle the unit, as it weighs 20 kg [44 lbs] or more. Do not grasp the packaging bands. W ear protective gloves to remo ve the unit fr om the pac kag- ing and to move it, as you can injure your hands on the fins ...

  • Mitsubishi Electronics R410A - page 3

    3 37-13/32 13+1-3/16 53-5/32 6-7/8 23-5/8 14-9/16 1. Safety precautions 1.3. Bef ore electric work Caution: • Be sure to install circuit breaker s. If not installed, electric shock ma y result. • For the power lines, use standar d cables of sufficient capacity . Otherwise, a short circuit, overheating, or fire may result. • When installing th ...

  • Mitsubishi Electronics R410A - page 4

    4 5-29/32 11-13/16 39-3/8 Max. 19-11/16 7-7/8 11-13/16 7-7/8 39-3/8 5-29/32 39-3/8 9-27/32 9-27/32 59-1/16 19-11/16 Max. 19-11/16 11-13/16 59-1/16 19-11/16 59-1/16 Max. 11-13/16 59-1/16 59-1/16 19-11/16 39-3/8 23-5/8 78-24/32 5-29/32 59-1/16 23-5/8 118-4/32 19-11/16 59-1/16 31-1/2 5-29/32 2. Installation location Fig. 2-3 Fig. 2-7 Fig. 2-8 Fig. 2-9 ...

  • Mitsubishi Electronics R410A - page 5

    5 B Max. 1-3/16 2.4.3. Windy location installation When installing the outdoor unit on a rooftop or other location unprotected from the wind, situate the air outlet of the unit so that it is not directly e xposed to strong winds. Strong wind entering the air outlet may impede the normal airflow and a malfunction may result. The follo wing shows two ...

  • Mitsubishi Electronics R410A - page 6

    6 B A H B C L r d a h b c C C CC 4.2. Connecting pipes (Fig. 4-2) Fig. 4-1 is a sample of piping system. • When commercially av ailable copper pipes are used, wrap liquid and gas pipes with commercially av ailable insulation materials (heat-resistant to 100 ° C [212 ° F] or more, thic kness of 12 mm [1/2 inch] or more). • The indoor par ts of ...

  • Mitsubishi Electronics R410A - page 7

    7 C B A E D 4. Installing the refrigerant piping 4.3. Refrigerant piping (Fig. 4-4) Remov e the ser vice panel D (three screws) and the front piping co ver A (two screws) and rear piping cov er B (two scre ws). 1 P erform refrigerant piping connections f or the indoor/outdoor unit when the out- door unit ’ s stop v alv e is completely closed. 2 V ...

  • Mitsubishi Electronics R410A - page 8

    8 =+ – 4.6. Additional refrigerant char ge Refrigerant of 3 kg [6.6 lbs] equivalent to 50 m [165 ft] total extended piping length is already included when the outdoor unit is shipped. Thus, if the total extended piping length is 50 m [165 ft] or less, there is no need to charge with additional refrigerant. Calculation of Additional Refrigerant Ch ...

  • Mitsubishi Electronics R410A - page 9

    9 2 Wiring examples • Controller name, symbol and allo wab le number of controllers. 2. M-NET Remote control cables A : Power source B : T ransmission line Name Outdoor unit controller Indoor unit controller Remote controller Symbol OC IC RC (M-NET) MA Allowable number of controllers One to eight controllers f or one OC Maximum of 16 controllers ...

  • Mitsubishi Electronics R410A - page 10

    10 *1. A breaker with at least 3.0 mm [1/8 inch] contact separation in each poles shall be provided. Use non-fuse breaker (NF) or earth leakage breaker (NV). *2. Use copper suppl y wires. Use the electric wires o ver the rating v oltage 300 V . 1. Use a separate power supply for the outdoor unit and indoor unit. 2. Bear in mind ambient conditions ( ...

  • Mitsubishi Electronics R410A - page 11

    11 7.2. T est run 7.2.1. Using remote controller Refer to the indoor unit installation man ual. • Be sure to perform the test run for each indoor unit. Make sure each indoor unit operates properly follo wing the installation manual attached to the unit. • If you perf orm the test run for all indoor units at once, y ou cannot detect any erroneou ...

  • Mitsubishi Electronics R410A - page 12

    12 1. Medidas de Seguridad ........................................................................... 12 2. Lugar de instalación ............................................................................... 13 3. Instalación de la unidad e xterior ............................................................ 15 4. Instalación de los tubos del ...

  • Mitsubishi Electronics R410A - page 13

    13 37-13/32 13+1-3/16 53-5/32 6-7/8 23-5/8 14-9/16 2. Lugar de instalaci ó n 2.1. T uber í a de refrigerante Consulte la Fig. 4-1. 2.2. Elecci ó n del lugar de instalaci ó n de la unidad e xterior • No instale la unidad en lugares expuestos a fuentes de calor . • Escoja un lugar donde el ruido de la unidad no moleste a los vecinos. • Esco ...

  • Mitsubishi Electronics R410A - page 14

    14 59-1/16 19-11/16 59-1/16 9-27/32 9-27/32 59-1/16 19-11/16 11-13/16 39-3/8 2. Lugar de instalaci ó n 2.4. V entilaci ó n y espacio de servicio 2.4.1. Cuando se instala una unidad exterior simple Las dimensiones m í nimas son las siguientes, excepto para m á x. (dimensiones m á xi- mas), las cuales tambi é n est á n indicadas. Consulte los ...

  • Mitsubishi Electronics R410A - page 15

    15 23-5/8 23-5/8 37-13/32 63/64 13 14-9/16 6-7/8 6-7/8 B Max. 1-3/16 2.4.3. Instalaci ó n en lugares expuestos al viento Cuando instale una unidad en el tejado o en otros lugares desprotegidos del viento, la salida de aire de la unidad no debe quedar expuesta directamente al viento fuerte. Si el viento fuerte entra en la salida de aire puede imped ...

  • Mitsubishi Electronics R410A - page 16

    16 B A a b c C C C C d H h L r B A H B C L r d a h b c C C CC 4.2. T ubos de conexi ó n (Fig. 4-2) La Fig. 4-1 muestra un sistema de tuber í as de ejemplo. • Si se utilizan tubos de cobre convencionales, envuelva los tubos de gas y l í quido con materiales aislantes (resistente al calor hasta 100 ° C [212 ° F] o m á s, espesor de 12 mm [1/2 ...

  • Mitsubishi Electronics R410A - page 17

    17 C B A E D 4. Instalaci ó n de los tubos del refrigerante Fig. 4-5 Fig. 4-4 Fig. 4-7 Fig. 4-6 B G H E D I (2) 1 2 4.3. T ubos de refrig erante (Fig. 4-4) Quite el panel de servicio D (tres tornillos) y la cubierta de la tuber í a frontal A (dos tornillos) y cubierta de la tuber í a posterior B (dos tornillos). 1 Realice las conexiones de los t ...

  • Mitsubishi Electronics R410A - page 18

    18 =+ – 4.6. Carga adicional de refrigerante El refrigerante de 3 kg [6,6 lbs] equivalente a una longitud total de 50 m [165 ft] de tuber í a totalmente e xtendida ya est á incluido en el en v í o de la unidad exterior . As í , si la longitud de la tuber í a totalmente extendida es de 50 m [165 ft] o menos, no ser á necesario cargar refrige ...

  • Mitsubishi Electronics R410A - page 19

    19 Ejemplo de un sistema de funcionamiento en tierra con varias unidades e xteriores (Se requiere cab le blindado y ajustes de direcci ó n.) <Ejemplo de tendido de cables de transmisi ó n> ■ Controlador remoto M-NET (Fig. 6-2) ■ Controlador remoto MA (Fig. 6-3) <M é todo de tendido de cables y ajustes de direcci ó n> a. Aseg ú ...

  • Mitsubishi Electronics R410A - page 20

    20 *1. Utilice un disyuntor autom á tico sin fusible (NF) o disyuntor autom á tico de fugas a tierra (NV) con una separ aci ó n m í nima de contacto de 3,0 mm [1/8 inch] en cada uno de los polos. *2. Utilice cables de alimentaci ó n de cobre. Utilice cab les el é ctricos con una tensi ó n nominal de 300 V . 1. Utilice una fuente de alimentac ...

  • Mitsubishi Electronics R410A - page 21

    21 7.2. Prueba de funcionamiento 7.2.1. Uso del control remoto Consulte el manual de instalaci ó n de la unidad interior . • Aseg ú rese de realizar la prueba de funcionamiento en cada unidad interior. Aseg ú rese de que cada unidad interior funciona correctamente siguiendo el manual de instalaci ó n que se entrega con la unidad. • Si reali ...

  • Mitsubishi Electronics R410A - page 22

    22 Index 1. Consignes de sécurité ........................................................................... 22 2. Emplacement d’installation .................................................................... 23 3. Installation de l’appareil e xtérieur .......................................................... 25 4. Installation de la tuy ...

  • Mitsubishi Electronics R410A - page 23

    23 37-13/32 13+1-3/16 53-5/32 6-7/8 23-5/8 14-9/16 2. Emplacement d’installation 2.1. T uyaux de réfrigérant Se reporter à la Fig. 4-1. 2.2. Sélection de l’emplacement d’installation de l’appareil extérieur • Eviter les endroits expos é s au ra y onnement solaire direct ou à d ’ autres sources de chaleur. • S é lectionner un e ...

  • Mitsubishi Electronics R410A - page 24

    24 2. Emplacement d’installation 2.4. V entilation et espace de ser vice 2.4.1. Lors de l’installation d’un seul appareil extérieur Le dimensions minimales sont les suivantes, à l ’ exception des valeurs Max., indiquant les dimensions maximales. Utiliser les chiffres pour chaque cas. 1 Obstacles uniquement à l ’ arri è re (Fig. 2-2) 2 ...

  • Mitsubishi Electronics R410A - page 25

    25 23-5/8 23-5/8 Min. 14-6/32 Min. 13/32 37-13/32 63/64 13 14-9/16 6-7/8 6-7/8 B Max. 1-3/16 2.4.3. Installation à un endroit exposé au vent Lors de l ’ installation de l ’ appareil ext é rieur sur un toit ou à d ’ autres endroits non prot é g é s du vent, diriger la sortie d ’ air de l ’ appareil vers le c ô t é qui n ’ est pas ...

  • Mitsubishi Electronics R410A - page 26

    26 B A a b c C C C C d H h L r B A H B C L r d a h b c C C CC 4.2. Connexion des tuyaux (Fig. 4-2) Fig. 4-1 est un exemple de circuit de tuyauteries. • En cas d ’ utilisation de tuyaux en cuivre disponibles sur le march é , envelopper les tuyaux de liquide et de gaz avec de la mati è re isolante vendue dans le commerce sur le march é (r é s ...

  • Mitsubishi Electronics R410A - page 27

    27 C B A E D 4. Installation de la tuyauterie du réfrigérant Fig. 4-5 Fig. 4-4 Fig. 4-7 Fig. 4-6 B G H E D I (2) 1 2 4.3. Mise en place des tuyaux de réfrigérant (Fig. 4-4) Retirer le panneau de service D (trois vis), le cache-tuyaux avant A (deux vis) et le cache- tuyaux arri è re B (deux vis). 1 Effectuer les raccordements des tuy aux de r ? ...

  • Mitsubishi Electronics R410A - page 28

    28 4.6. Charge supplémentaire de réfrigérant A la sortie d ’ usine, l ’ appareil ext é rieur contient d é j à 3 kg [6,6 lbs] de r é frig é rant correspon- dant à une longueur totale de tuyaux de 50 m [165 ft]. De ce fait, si la longueur totale des tuyaux ne d é passe pas 50 m [165 ft], il n ’ est pas n é cessaire de rajouter du r ? ...

  • Mitsubishi Electronics R410A - page 29

    29 A : Alimentation B : Ligne de transmission Fig. 6-1 M1 S M2 A B M1 S M2 L1 L2 GR TB3 TB7 6.2. Boîtier de commande et emplacement pour le rac- cordement des câbles (Fig. 6-1) 1. Connectez la ligne de transmission de l ’ appareil int é rieur au bloc de sorties de la ligne de transmission (TB3) ou connectez les fils entre les appareils ext é ...

  • Mitsubishi Electronics R410A - page 30

    30 *1. Utiliser un disjoncteur sans fusible (NF) ou un disjoncteur de fuite à la terre (NV) a vec un é cartement de 3,0 mm [1/8 inch] minimum entre les contacts de chaque p ô le. *2. Utiliser des câbles électriques en cuivre. Utiliser des câb les électriques correspondant à une tension de 300 V . 1. Utiliser une alimentation séparée pour ...

  • Mitsubishi Electronics R410A - page 31

    31 7.2. Marche d’essai 7.2.1. Utilisation de la télécommande Se repor ter au manuel d ’ installation de l ’ appareil int é rieur . • V eiller à effectuer un essai pour chaque appareil int é rieur . V é rifier que chaque appareil int é rieur fonctionne correctement et conform é ment aux instructions du manuel d ’ installation fourn ...

  • Mitsubishi Electronics R410A - page 32

    Please be sure to put the contact address/telephone number on this manual before handing it to the customer. This product is designed and intended for use in the residential, commercial and light-industrial environment. HEAD OFFICE: T OK Y O BLDG., 2-7-3, MAR UNOUCHI, CHIY OD A-KU , T OKY O 100-8310, J AP AN Printed in Japan BG79U872H02 ...

Fabricant Mitsubishi Electronics Catégorie Air Conditioner

Les documents que nous recevons du fabricant de l'appareilMitsubishi Electronics R410A peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques Mitsubishi Electronics
- manuels d’utilisations R410A
- fiches produit Mitsubishi Electronics
- dépliants
- ou étiquettes-énergie Mitsubishi Electronics R410A
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation Mitsubishi Electronics R410A.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation Mitsubishi Electronics R410A, manuels d’entretien, brefs manuels ou manuels de l’utilisateur Mitsubishi Electronics R410A. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit Mitsubishi Electronics R410A.

Manuel d’utilisation complet de l’appareil Mitsubishi Electronics R410A, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser Mitsubishi Electronics R410A par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs Mitsubishi Electronics R410A.

Le manuel d’utilisation complet Mitsubishi Electronics, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel Mitsubishi Electronics R410A - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières Mitsubishi Electronics R410A, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lMitsubishi Electronics R410A qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil Mitsubishi Electronics R410A - qui devraient nous aider dans les premières étapes lors de l'utilisation Mitsubishi Electronics R410A
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de Mitsubishi Electronics R410A
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service Mitsubishi Electronics R410A dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de Mitsubishi Electronics R410A?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec Mitsubishi Electronics R410A, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec Mitsubishi Electronics R410A il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)