Manuel d’utilisation MGE UPS Systems 800 Tower

36 pages 0.66 mb
Télécharger

Aller à la page of 36

Summary
  • MGE UPS Systems 800 Tower - page 1

    Installation and user manual www .mgeups.com MGE UPS SYSTEMS Pulsar Evolution 1500 T ower/1500 Rack 1100 T ower/1100 Rack 800 T ower/800 Rack 500 Rack ...

  • MGE UPS Systems 800 Tower - page 2

    Page 2 - 3400723200/AC MGE UPS Systems 1660 Scenic A venue Costa Mesa, CA 92626 (714) 557-1636 For service call 1-800-438-7373 www .mgeups.com SA VE THESE INSTRUCTIONS. This manual contains important instructions for 89340-89346 that should be followed during installation and maintenance of the UPS and batteries. Thank you for selecting an MGE UPS ...

  • MGE UPS Systems 800 Tower - page 3

    3400723200/AC - Page 3 Introduction CAUTION: Safety of persons ◗ The UPS has its own internal power source (the battery). Consequently , the power outlets may be energized even if the UPS is disconnected from the AC-power source. ◗ Dangerous voltage levels are present within the UPS. It should be opened exclusively by qualified service personne ...

  • MGE UPS Systems 800 Tower - page 4

    Page 4 - 3400723200/AC Foreword Using this document Important instructions that must always be followed. Information, advice, help. Visual indication. Action. Audio indication. In the illustrations on the following pages, the symbols below are used: LED off. LED on. LED flashing. Information may be found in two ways, using: ◗ the contents; ◗ th ...

  • MGE UPS Systems 800 Tower - page 5

    3400723200/AC - Page 5 Contents 1. Presentation 1.1 Overall view .................................................................................................................................. 7 T ower models ..................................................................................................................................7 Rack m ...

  • MGE UPS Systems 800 Tower - page 6

    Page 6 - 3400723200/AC Contents 4. Maintenance 4.1 T rouble-shooting ..........................................................................................................................22 4.2 Replacement of the battery module ..........................................................................................2 3 T ower models .......... ...

  • MGE UPS Systems 800 Tower - page 7

    3400723200/AC - Page 7 1. Presentation 1.1 Overall view T ower models Rack models P U L S A R Evolution 1 1 0 0 W H D W H D P U L S A R Evolution 1500 Rack Dimensions in inches (W x H x D) Evolution 800 T ower 5.9 x 9.3 x 16.3 Evolution 1 100 T ower 5.9 x 9.3 x 16.3 Evolution 1500 T ower 5.9 x 9.3 x 19 Weight in lbs Evolution 800 T ower 23 Evolutio ...

  • MGE UPS Systems 800 Tower - page 8

    Page 8 - 3400723200/AC 3.7 36Vdc, 9Ah Pb AC Output AC Input Volt 120V~1O Hertz 50/60 Hz Hertz 50/60 Hz Amps 12A MAX Volt 120V~1O W/VA 1000W/1440VA U.P.S. 34Z5 R Vac IN RS232 T20A/125V~ 2 1 Programmable Data line protection 344-50248-00 SITE WIRING FAULT U.S. PAT. No. 6,094,363 IN OUT Vac OUT I max 12A 1. Presentation 1.2 Back Pulsar Evolution 500 / ...

  • MGE UPS Systems 800 Tower - page 9

    3400723200/AC - Page 9 1 2 % % 1.3 Control panel Bargraph indicating percent load at output. Group 1 programmable receptacles supplied with power . Illuminated ON/OFF button for the receptacles. Group 2 programmable receptacles supplied with power . Operation on battery power . 10 11 12 15 14 18 17 13 16 1. Presentation UPS fault. Battery fault. Ov ...

  • MGE UPS Systems 800 Tower - page 10

    P U L S A R Evolu tion 1 1 0 0 Page 10 - 3400723200/AC 2. Installation 2.1 Unpacking and parts check RS232 communications cable for Windows Operating Systems. For Unix/Linux Operating Systems, please order for free the following part number: 66090 USB communications cable. CD-ROM with the Solution-Pac and UPS Driver software. Product documentation. ...

  • MGE UPS Systems 800 Tower - page 11

    P U L S A R Evolution 1500 Rack 3400723200/AC - Page 11 2. Installation RS232 communications cable for Windows Operating Systems. For Unix/Linux Operating Systems, please order for free the following part number: 66090 USB communications cable. CD-ROM with the Solution-Pac and UPS Driver software. Product documentation. T elescopic rails for mounti ...

  • MGE UPS Systems 800 Tower - page 12

    Page 12 - 3400723200/AC 2. Installation 2.2 Installation T ower models P U L S A R Evolution 1 1 0 0 P U L S A R Evolution 1 1 0 0 ...

  • MGE UPS Systems 800 Tower - page 13

    P U L S A R Evolution 1500 Rack 3400723200/AC - Page 13 2. Installation Follow steps 1 to 6 for rack mounting of the UPS on the rails. The rails and the necessary mounting hardware are supplied by MGE UPS SYSTEMS. For step 1, screw quantity shown is for 1500 V A. 800 and 1 100 V A use two screws for each side. 1 2 2 2 2 5 3 6 6 5 4 3 800/1100/1500 ...

  • MGE UPS Systems 800 Tower - page 14

    P U L S A R Evolution 1500 Rack Page 14 - 3400723200/AC 2. Installation 500 Rack model Follow steps 1 to 3 for rack mounting of the UPS on the rails. 1 2 3 3 1 P U L S A R Evolut io n 1500 Rack P U L S A R Evolution 1500 Rack W all Mount Configuration Floor Mount Configuration ...

  • MGE UPS Systems 800 Tower - page 15

    Pb Hertz 50/60 Hz W/VA 1000W/1440VA Ausg Hertz 50/60 Hz Amps 12A MAX Netz Util Load Mains Reseau Volt 120V~1O Volt 120V~1O 36Vdc, 9Ah U.S. PAT. NO. 6,094,363 Programmable 2 1 Vac OUT I max 12A U.P.S. 34Z5 R Vac IN SITE WIRING FAULT Data line protection T20A/125V~ RS232 344-50254-00 IN OUT 1 - Remove the power cord supplying the equipment to be prot ...

  • MGE UPS Systems 800 Tower - page 16

    Page 16 - 3400723200/AC Pb Hertz 50/60 Hz W/VA 1000W/1440VA Ausg Hertz 50/60 Hz Amps 12A MAX Netz Util Load Mains Reseau Volt 120V~1O Volt 120V~1O 36Vdc, 9Ah U.S. PAT. NO. 6,094,363 Programmable 2 1 Vac OUT I max 12A U.P.S. 34Z5 R Vac IN SITE WIRING FAULT Data line protection T20A/125V~ RS232 344-50254-00 IN OUT 2. Installation 2.4 Connection to th ...

  • MGE UPS Systems 800 Tower - page 17

    3400723200/AC - Page 17 2. Installation 2.6 Installation of the communications-card option 1 - Remove the slot cover 4 secured by two screws. 2 - Insert the card in the slot. 3 - Secure the card with the two screws. Restricted-access slot for the communications card 4 Pb Hertz 50/60 Hz W/VA 1000W/1440VA Ausg Hertz 50/60 Hz Amps 12A MAX Netz Util Lo ...

  • MGE UPS Systems 800 Tower - page 18

    The booster and fader functions maintain the output voltage supplied by the UPS within close tolerances around the rated value even if significant voltage variations occur in the AC-input power . This avoids calling on bat- tery power . The values defining the voltage range may be set using the UPS Driver software. During operation in booster or fa ...

  • MGE UPS Systems 800 Tower - page 19

    3400723200/AC - Page 19 1 2 % % 1 2 % % 3. Operation 3.3 Operation on battery power (following failur e of AC-input power) T ransfer to battery power The AC-input power is out of tolerances, LED 1 1 goes ON. During operation on battery power , the buzzer beeps every ten seconds. The equipment connected to the UPS is supplied by the battery . Thresh ...

  • MGE UPS Systems 800 Tower - page 20

    Page 20 - 3400723200/AC 3. Operation 3.4 Personalization (optional) Function Default setting Enabled Enabled Enabled Disabled Enabled Personalization parameters can be set and modified using the UPS Driver software installed on a computer that is connect- ed to the UPS (see section 2.4 Connection to the RS232 or USB communications port). Check that ...

  • MGE UPS Systems 800 Tower - page 21

    Configurable function UPS sensitivity level Default setting Normal Options High or low 3400723200/AC - Page 21 3. Operation Configurable function Output voltage on battery power Upper threshold for transfer to battery power Fader-mode cut-in threshold Booster-mode cut-in threshold Lower threshold for transfer to battery power Maximum input-voltage ...

  • MGE UPS Systems 800 Tower - page 22

    Indication LED 12 goes ON and the buzzer sounds contin- uously . Signification UPS electronics have detected a UPS fault. ◗ The connected equipment is no longer supplied. The equipment connected to the UPS is no longer protected. Correction Call the after-sales support depart- ment. Indication LED 13 flashes and the buzzer beeps once. LED 12 flas ...

  • MGE UPS Systems 800 Tower - page 23

    3400723200/AC - Page 23 P U L S A R Evolution 1 1 0 0 B A C 4.2 Replacement of the battery module 4. Maintenance Removal of the battery module When replacing batteries, use the Battery Replacement Chart below to determine the correct battery . This operation may be carried out with the UPS supplying power to the load. Safety rules Servicing of batt ...

  • MGE UPS Systems 800 Tower - page 24

    Page 24 - 3400723200/AC 4. Maintenance Installation of the new battery module Carry out the above operation in reverse order . ◗ CAUTION: risk of electric arc when connecting the battery . ◗ T o maintain an identical level of performance and safety , use a battery module identical to that previously mounted in the UPS. ◗ Press the two parts o ...

  • MGE UPS Systems 800 Tower - page 25

    3400723200/AC - Page 25 D A B C PULSAR Evolution 1500 Rack 4. Maintenance Removal of the battery module This operation may be carried out with the UPS supplying power to the load. A - Unclip the small plate with the MGE logo on the front panel of the UPS. B - Remove the two screws. C - Remove the left-hand side of the front panel by pulling it forw ...

  • MGE UPS Systems 800 Tower - page 26

    Page 26 - 3400723200/AC F E 4. Maintenance Installation of the new battery module Carry out the above operation in reverse order . ◗ CAUTION: risk of electric arc when connecting the battery . ◗ T o maintain an identical level of performance and safety , use a battery module identical to that previously mounted in the UPS. ◗ Press the two par ...

  • MGE UPS Systems 800 Tower - page 27

    3400723200/AC - Page 27 5. Environment This product has been designed to respect the environment: It does not contain CFCs or HCFCs. UPS recycling at the end of service life: MGE UPS SYSTEMS undertakes to recycle, by certified companies and in compliance with all applicable regulations, all UPS products recovered at the end of their service life (c ...

  • MGE UPS Systems 800 Tower - page 28

    Page 28 - 3400723200/AC 6. Appendices 6.1 T echnical data Simplified diagram Input Output Battery Charger Inverter Booster / fader transformer Filter ...

  • MGE UPS Systems 800 Tower - page 29

    3400723200/AC - Page 29 6. Appendices T echnical characteristics (1) The upper and lower thresholds may be set using the UPS Driver software. (2) Or 40 Hz in low-sensitivity mode (may be set using the UPS Driver software). (3) Adjustable from 100 to 127 V using the UPS Driver software. Output rating AC-input power ◗ V oltage ◗ Frequency Output ...

  • MGE UPS Systems 800 Tower - page 30

    Page 30 - 3400723200/AC 6. Appendices Examples of battery backup times Pulsar Evolution 500 Pulsar Evolution 800 Pulsar Evolution 1100 1 hub 1 router 1 data server + 1 hub + 1 router Pulsar Evolution 1500 2 file/print servers 0 10 20 50 100 t (min) 30 40 60 70 80 90 1 10 120 0 10 20 50 100 t (min) 30 40 60 70 80 90 1 10 120 2 rack-optimized dense s ...

  • MGE UPS Systems 800 Tower - page 31

    3400723200/AC - Page 31 6. Appendices 6.2 Glossary Backup time T ime that the connected equipment can operate on battery power if AC-input power fails. Bargraph Device on the front panel indicating the percent remaining backup time or the percent load. Booster mode Automatic UPS operating mode whereby the input-power voltage is increased if it drop ...

  • MGE UPS Systems 800 Tower - page 32

    Page 32 - 3400723200/AC 6. Appendices 6.3 Index A Automatic start ................................................................20 B Bargraph ............................................................................9 Battery Backup time ............................................................30 End of backup time .......................... ...

  • MGE UPS Systems 800 Tower - page 33

    ...

  • MGE UPS Systems 800 Tower - page 34

    ...

  • MGE UPS Systems 800 Tower - page 35

    ...

  • MGE UPS Systems 800 Tower - page 36

    1660 Scenic Avenue Costa Mesa, CA 92626 USA www .mgeups.com ...

Fabricant MGE UPS Systems Catégorie Power Supply

Les documents que nous recevons du fabricant de l'appareilMGE UPS Systems 800 Tower peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques MGE UPS Systems
- manuels d’utilisations 800 Tower
- fiches produit MGE UPS Systems
- dépliants
- ou étiquettes-énergie MGE UPS Systems 800 Tower
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation MGE UPS Systems 800 Tower.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation MGE UPS Systems 800 Tower, manuels d’entretien, brefs manuels ou manuels de l’utilisateur MGE UPS Systems 800 Tower. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit MGE UPS Systems 800 Tower.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil MGE UPS Systems 800 Tower, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser MGE UPS Systems 800 Tower par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs MGE UPS Systems 800 Tower.

Le manuel d’utilisation complet MGE UPS Systems, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel MGE UPS Systems 800 Tower - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières MGE UPS Systems 800 Tower, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lMGE UPS Systems 800 Tower qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil MGE UPS Systems 800 Tower - qui devraient nous aider dans les premières étapes lors de l'utilisation MGE UPS Systems 800 Tower
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de MGE UPS Systems 800 Tower
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service MGE UPS Systems 800 Tower dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de MGE UPS Systems 800 Tower?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec MGE UPS Systems 800 Tower, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec MGE UPS Systems 800 Tower il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)